6 Parameter Description
Fb-18=1 or 2 or 3 can prevent undervoltage stop caused by momentary power failure for large-inertia
loads like fans and centrifuges.
Fb-20 is used only when Fb-18 = 1.
If undervoltage occurs during running, the motors coasts to a stop and the undervoltage fault (Er.dcL) is
reported. If undervoltage occurs in standby state, only the alarm of AL.dcL is given.
Fb-22
Setting
0~10
range
Fb-23
Setting
1.0~30.0s
range
Fb-24
Setting
0: No output
range
Restart after momentary stop, auto reset or
Fb-25
Setting
0: Restart according to the preset starting mode
range
1: Restart smoothly
Auto reset function: when a fault occurs during running, the fault is reset automatically according to the
settings of Fb-22 and Fb-23, thus avoiding trip due to misoperation, instantaneous power supply
overvoltage and external non-repeated impact.
Auto reset process: when a fault occurs during running, it is reset automatically after a period of time
(Fb-23). If the fault disappears, the motor restarts according to the mode set by Fb-25; if the fault still
exists and the reset times is less than Fb-22, auto reset is continued being retried, otherwise an alarm is
reported and the motor stops.
Fb-22 is cleared in any of the following cases: no fault occurs for continuous ten minutes after the fault
reset; fault is manually reset after it is detected; power supply resumes after the momentary power
failure.
Fb-24 selects whether the digital output 5 is valid during auto reset.
Faults of "power device protection" (Er.FoP) and "external fault" (Er.EEF) are not reset automatically.
Danger
: Be extremely careful while using the auto reset function, for it may cause injury to people or damage
to equipment.
Danger
: Be extremely careful while using the auto reset function, for it may cause injury to people or damage
to equipment.
Fb-26
Setting
0: Disabled
range
 When terminal is the command source and F4-08=0, 1 or 2, if the run command is valid after power-on,
then Fb-26 can be used to select whether to start the system immediately.
Fb-27
Built-in braking unit working threshold
Setting
620~720V
114
Auto reset times
Auto reset interval
Fault output during auto reset
pause
Power-on auto restart
Default
0
Default
5.0s
Default
0
1: Output
Default
1
Default
1
1: Enabled
Default
680V
Change
×
Change
×
Change
×
Change
×
Change
Change