 FC-00 = 1: Only parameters selected by FC-15~FC-46 are displayed. User password is invalid for these
parameters. But changing FC-00 needs the user password.
 FC-00 = 2: Only parameters that have different settings from the factory settings are displayed. This
facilitates the test and maintenance.
FC-01
Units digit: determines which keys are locked.
0: None locked
2: All locked but
4: All locked but
5: All locked but
Tens digit: determines the function of
0: Valid only when keypad is the command source
1: Valid when keypad, terminal or communication is the command source. Stops the motor
Setting
according to preset stop mode.
range
2: Stops the motor according to preset stop mode when keypad is the command source;
makes the motor coast to a stop and give an Er.Abb alarm when any other command source is
selected.
Hundreds digit: determines the function of
0: Invalid
1: Valid only in standby state
2: Valid
Thousands digit: determines the function of
0: Common run
 Keys are locked up automatically if no key is pressed within one minute. In monitoring state, pressing
will lock the keys , and pressing
unlock them.
FC-02
Monitored parameter 1 (in run and standby)
FC-03
Monitored parameter 2 (in run and standby)
FC-04
Monitored parameter 3 (in run and standby)
FC-05
Monitored parameter 4 (in run and standby)
FC-06
Monitored parameter 5 (in run and standby)
FC-07
Monitored parameter 6 (in run and standby)
FC-08
Monitored parameter 7 (in run and standby)
FC-09
Monitored parameter 1 (in run)
FC-10
Monitored parameter 2 (in run)
FC-11
Monitored parameter 3 (in run)
FC-12
Monitored parameter 4 (in run)
-1~59
Setting
Note: -1 indicates null and 0~59 represent FU-00~FU-59 respectively. The minimum value
range
of FC-02 is 0.
 FC-02~FC-08 select(from the FU menu) the parameters to be monitored in both running and standby
states.
 FC-09~FC-12 select(from the FU menu) the parameters to be monitored only in running state.
FC-13
Key function and auto lockup
1: All locked
3: All locked but
and
and
1: Jog
Speed display coefficient
Default
0000
(only when keypad is command source)
(only when keypad is command source)
and holding for three seconds will
Default
Default
-1
Default
-1
Default
-1
Default
-1
Default
-1
Default
-1
Default
Default
Default
Default
-1
Default
1.000
6 Parameter Description
Change
×
1
Change
Change
Change
Change
Change
Change
Change
0
Change
2
Change
4
Change
Change
Change
117