6 Parameter Description
 Hope800 has eight built-in multi-function programmable digital input terminals(X1~X6, FWD and REV)
and offers five expansion input terminals.
Each digital input function listed in the table above can also be used as the output of the comparator,
logic unit or timer. Refer to Section FE.
Related monitored parameters: FU-40 and FU-41.
Description of digital input functions:
1~8: Multistep frequency 1~8. Refer to F4-17.
9~11: Accel/decel time select 1~3. The combination of accel/decel time 1, 2 and 3 determines which
accel/decel time is selected. Refer to the following table, where "0" indicates invalid, while "1" indicates valid.
Accel/decel time
select 3
0
0
0
0
1
1
1
1
Note: the function of accel/decel time select is invalid in simple PLC operation, jog operation or emergency
stop.
12: External fault input. This signal sends the error or fault information about the peripherals into the
inverter, causing the inverter to stop and giving the external fault alarm. This fault can not be reset
automatically; it must be reset manually. If you need a normally-closed input, you can negate the digital input
terminal by means of F4-09 or F4-10. The external fault can be indicated by the digital output 10(refer to
Section 6.6).
13: Fault reset. The rising edge of this signal resets the fault. It has the same function as the key
the keypad.
14~15: Jog forward/reverse. Refer to page 62 for details.
16: Emergency stop. When this signal is valid, the inverter will stop according to the time set by F1-18.
17: Inverter run disabled. When this signal is valid, the inverter is prohibited to run or coasts to a stop if
it is running.
18: Coast stop. If this signal is valid when the inverter is running, the inverter will block the output and
the motor will coast to a stop.
19~21: UP/DOWN increase, decrease and clear. Refer to F4-12~F4-16.
22~24: PLC control disable, operation pause and standby state reset. Refer to Section 6.9.
25~31: PLC mode select 1~7. Refer to Section 6.9.
32: Auxiliary reference disabled. When this signal is valid, the auxiliary reference is invalid.
33: Operation interrupted. If this signal is valid when the inverter is running, the inverter will block the
output; after this signal is canceled, the inverter will restart according to the mode set by Fb-25. This signal can
78
terminal
Accel/decel time
select 2
0
0
1
1
0
0
1
1
Accel/decel time
select 1
0
1
0
1
0
1
0
1
Accel/decel time
Accel/decel time 1( F1-00, F1-01)
Accel/decel time 2( F1-02, F1-03)
Accel/decel time 3( F1-04, F1-05)
Accel/decel time 4( F1-06, F1-07)
Accel/decel time 5( F1-08, F1-09)
Accel/decel time 6( F1-10, F1-11)
Accel/decel time 7( F1-12, F1-13)
Accel/decel time 8( F1-14, F1-15)
on