Circuits - Fire-Lite Alarms MS-9200E Programming, Installation, Maintenance And Operating Instruction Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Circuits

Membrane Panel
Mounted on the main circuit board, the membrane switch panel includes a window for the LCD display and five sys-
tem status LEDs. The membrane panel, which is visible with the cabinet door closed, has 21 keys, including a 12 key
alpha-numeric pad similar to a telephone keypad.
Function switches:
• Acknowledge/Step
• Alarm Silence
• Drill
• System Reset (lamp test)
Service/program switches:
• keys labeled 1 to 9
• * (detector) key
• # (module) key
• 0 (recall) key
• four cursor keys (up, down, right and left)
• Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions.
1.4
Circuits
SLC Communication Loop
One SLC loop, configurable for NFPA Style 4, 6 or 7, is provided for communication to addressable monitor (initiat-
ing device) and control (output device) modules.
Output Circuits
The following output circuits are available on the FACP:
• 24 Volt Resettable Power Output 300 mA
• 24 Volt Nonresettable Power Output 300 mA
• 24 Volt Battery Charger (up to 18 AH batteries)
NAC (Notification Appliance Circuits)
Two NACs, configurable for Style Y (Class B) or Style Z (Class A), are provided with various programmable
features.
Relays
Three dry contact relays are provided for System Alarm and System Trouble (Form-C contacts) and Supervisory
(Form-A contacts). Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive).
FIGURE 1-1:
Document #50428
Rev. C1
2/15/99
MS-9200 Membrane/Display Panel
P/N 50428:C1
11