The M302 Monitor Module
Style D Initiating Device Circuit (Utilizing M302 Monitor Module)
The NFPA Style D IDC (Initiating Device Circuit) is supervised and power-limited.
Style D Circuit using M302
FIGURE 2-22:
Resettable 24 VDC
4-wire smoke
detector power
(300 mA max.)
+
-
+
T
B
1
2
3
4
24V (+) TB4-5
24V (-) TB4-6
40
To Next Device
on Loop
+
-
+
-
4
5
6
End-of-Line
Resistor
-
3.9K ohm
(included)
CAUTION! Do not loop wiring
under any terminals. Break wire
run to maintain supervision.
M302
MS-9200
Document #50428
Rev.C1
2/15/99
-
+
-
+
UL listed
Compatible
Smoke
Detector
-
+
-
+
UL listed
Compatible
Smoke
Detector
-
+
-
+
UL listed
Compatible
Smoke
Detector
Loop Out
Shield
A
B B+ A+ B- A-
T
B
1
2
3
4
5
6
SLC (+) TB6-3
SLC (-) TB6-5