NFPA Standard-Specific Requirements
NFPA 72 Remote Station Protective Signaling System
Notes:
Cut Jumper JP4 on the MS-9200 main circuit board to supervise placement of the RTM-8F module.
1.
Refer to Figure 2-8, "Typical UL Power-limited Wiring Requirements," on page 27, and "UL Power-limited
2.
Wiring Requirements" on page 27, for information on UL Power-limited wiring requirements.
Remote Station Connection Using RTM-8F Module
FIGURE E-4:
Jumper JP2 must be in position
ALARM/TROUBLE REVERSE
POLARITY for use in alarm and
trouble transmission or ALARM
ONLY for alarm transmission only
JP2 Jumper Settings:
A larm/Trouble Polarity
Reversal Remote Station
A larm only Polarity
Reversal Remote Station
Fire•Lite RS82 Remote Station Receiver UL listed.
Refer to Fire•Lite Alarms, Inc., Instruction Manual for
Remote Station Receiver Model RS82.
Cut JP1
Document #50428
RTM-8F Relay
Transmitter
Module
(not suitable for
transmission of
separate alarm and
trouble signals to
Remote Station)
Power-limited
+
-
Rev. C1
2/15/99
P/N 50428:C1
+
-
Polarity Shown is
Normal Standby
97