Read Status
In the preceding display:
NORMAL is the present status (could be ALARM, TRBL_#, DISABL, etc.)
SMOKE (DET) is the device type P indicates that this is a photoelectric detector (could be I if
ionization or PULL BOX, HORN CKT, etc.) and 01 is the device address
WEST HALLWAY is the custom label programmed for this device
Z56 is the assigned software zone
If the point is not installed, a Read Status command to that point will result in a NOT INSTALLED message on the
display.
Read History
The MS-9200 has a 500-event history buffer. Stored events include Point Status, System Troubles, and Acknowl-
edge/Step, Alarm Silence, Drill and System Reset key presses. All events are recorded with the time and date. His-
tory events are stored in volatile memory, therefore, removal of primary AC power and secondary battery power will
clear the history buffer. To clear the History file without removing power, see "Clear History" on page 65. To view
events in the history file, use the Up and Down arrow keys to step through the events.
Print Program
All user programmed options, including device types, software zone assignments and system parameters, may be
printed. The printout also includes current system status. See "Printer/PC Interface Module" on page 52, for instruc-
tions on connecting a printer.
Print History
The entire 500-event history file may be printed using the Print History feature. Refer to "Printer/PC Interface Mod-
ule" on page 52, for instructions on connecting a printer.
76
Document #50428
Rev.C1
2/15/99
P/N 50428:C1