Controls and Indicators

Current for all external devices: 3.0 amps expandable to 6.0 amps
Current-limit: Fuseless, electronic, power-limited circuitry
Maximum signaling current per circuit: 2.50 amps
End-of-line resistor: 4.7K ohms, ½ watt (P/N 71252 UL listed) for NACs
Alarm, Trouble and Supervisory Relays - TB3
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Alarm and Trouble relays: Form-C
Refer to Figure 2-6, "Relay Connections," on page 26 for information on power-limited wiring for relay circuits
Four-Wire Smoke Detector Power (24 VDC nominal) - TB4, Terminals 5(+) and 6(-)
Maximum ripple voltage: 10 mV
Up to 300 mA is available for powering 4-wire smoke detectors
Power-limited circuit
Nonresettable Filtered 24 VDC Power (24 VDC nominal) - TB4, Terminals 3(+) & (4-)
Maximum ripple voltage: 10mV
Total DC current available from this output is up to 300 mA
Power-limited circuit
Nonregulated Special Purpose 24 VDC Power - TB4, Terminals 1(+) & 2(-)
Operating voltage range: 18V to 30V
Total DC current available for powering external devices is 2.5 amps
This power is not recommended for AFM, LDM or LCD-40 annunciators
Power-limited circuit
1.3
Controls and Indicators
LCD Display
The MS-9200 uses a 40-character (2 lines X 20
characters) high viewing angle LCD display with a
character height of 3/16". The display includes a
long-life LED backlight that remains illuminated. If
AC power is lost and the system is not in alarm, the
LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
• AC Power (green)
• Fire Alarm ((red)
• Supervisory (yellow)
• Alarm Silence (yellow)
• System Trouble (yellow)
• Ground Fault (yellow) - located on bottom of main circuit board (refer to figure on page 7)
1. Total current for special purpose power, nonresettable power, 4-wire smoke power and two NACs must not exceed 6.0 amps.
Total external system current in excess of 3.6 amps requires XRM-24E Transformer and 12 AH or 18 AH batteries, not 7.0 AH.
2. For power supply calculations, refer to Appendix A.
3. Total current for resettable 4-wire smoke detector power and nonresettable power must not exceed 600 mA.
10
Supervisory relay: Form-A
Maximum standby current: 50 mA
RMS
Maximum standby current: 150 mA
RMS
Document #50428
1
1
2 3
1 2 3
2
Rev.C1
2/15/99
P/N 50428:C1