Specifications - Fire-Lite Alarms MS-9200E Programming, Installation, Maintenance And Operating Instruction Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Specifications

• Password and key-protected nonvolatile memory
• User programmable password
• Fully programmable from panel keyboard
• Programmable from an off-line PC
• Rapid poll algorithm for manual stations (U.S. Patent Pending)
• SLC operates up to 10,000 ft. (3,000 m) or 1,000 ft. (300 m) with untwisted, unshielded wire (U.S. Patent
#5,210,523)
• Uses Fire•Lite 300 Series Addressable Devices:
CP300 - Ionization Smoke Detector
SD300 - Photoelectric Smoke Detector
SD300T - Photoelectric Smoke Detector with 135
C304 - Control Module
M300 - Monitor Module
M301 - Miniature Monitor Module
M302 - 2-wire Detector Module
I300 - Isolator Module
• All 300 Series devices (except I300) feature decade code wheels for addressing
• 300 Series addressable smoke detectors feature a plug-in wiring connector for ease-of-installation and
maintenance
• UDACT-F Digital Communicator, reports up to 56 zones or 198 points (all 300 Series devices) to a UL listed
Central Station
1.2
Specifications
AC Power - TB8
240 VAC, 50 Hz, 1.2 amps
Wire size: minimum #14 AWG (2.00 mm
Battery (Lead Acid Only) - J3
Maximum Charging Circuit:
Maximum Battery Capacity:
teries greater than 12 Amp Hour, up to 18 Amp Hour, require Fire•Lite BB-17F or other UL listed battery cabinet).
For 25 to 120 Amp Hour batteries, use the CHG-120F Battery Charger only if the newer MS-9200 main circuit board
#71741, with jumper JP1, is installed. Note: Jumper JP1, on the FACP main circuit board, must be cut to disable
FACP battery charger when using the CHG-120F.
Communication Loop - TB6
15 VDC nominal, 27.6 VDC maximum
Maximum length is 10,000 ft. (3,000 m) total twisted pair length
Maximum loop current is 250 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited
Notification Appliance Circuits - TB1 & TB2
Nonregulated special purpose power
Power-limited circuitry
Maximum voltage drop in wiring: 2.0 V
Nominal operating voltage: 24 VDC
2
) with 600V insulation
Normal Flat Charge — 27.6V @ 0.8 amp
18 Amp Hour (new MS-9200 cabinet holds maximum 12 Amp Hour batteries. Bat-
Document #50428
O
Thermal Detection
Rev. C1
2/15/99
P/N 50428:C1
9