Program Change - Level One

3.3
Program Change - Level One
When the correct password is entered, the MS-9200 will enter Level 1 program mode. In this mode, the trouble relay
is activated and the System Trouble LED flashes and cannot be changed to steady and the piezo sounder is off. The
following display will appear:
3.3.1 Clear
Pressing '0' will clear all general system programming options described in "System Edit" on page 61, and all pro-
grammed addressable devices from the nonvolatile memory of the MS-9200. Before executing the Clear command,
the display will prompt the user to press ENTER in order to verify the command before the system actually clears
programming data. CLEAR is a useful command when the unit is first installed, prior to autoprogramming. Note
that it is necessary to 'A utoprogram' after using the clear function.
3.3.2 Autoprogram
Pressing '1' enters the Autoprogramming mode. The main purpose of autoprogramming is to allow the installer a fast
and easy way to bring the system on-line as quickly as possible. The first time the system is brought on-line, it must
be autoprogrammed. A utoprogram is also the only way to add or delete devices.
Once Autoprogram is selected, the MS-9200 automatically polls all devices installed/wired to the SLC loop. The
panel communicates with each individual addressable device and displays the type of device at each address location
starting with detectors and then modules.
While autoprogramming the system, the MS-9200 will display the following:
Verification of each device address and type installed on the SLC may now occur. If information is correct, press the
ENTER key, if incorrect, press the left arrow key to delete. In addition, adjective and noun descriptors plus zone
assignments may be added to the display field per device address. If the Reset key is pressed at this time or the panel
is allowed to time-out after 10 minutes of inactivity, a 'System Corrupted' message will appear. Be certain to step
through all devices, using the Enter or left arrow key.
The first time that autoprogramming is selected, all points installed on the SLC loop are identified. Default device
type (monitor, smoke detector, control) and software zone assignments for each device are displayed. On any succes-
sive enabling of the autoprogram feature, the LCD will display only the newly installed, deleted or changed devices
on the SLC loop.
Devices which match the program already in memory are not changed and are not shown to the operator. Devices
which do not match the program (not the same address and/or type) are shown to the operator. Devices inadvertently
set to the same address are identified and displayed on the screen.