NFPA Standard-Specific Requirements
NFPA Signaling Systems for Central Station Service (Protected Premises Unit)
The following figure illustrates an example of Central Station/Remote Station Reporting using an MS-5012. The
relay contacts from the MS-9200 may be used to trip any dialer UL listed for Central Station/Remote Station Ser-
vices. The UDACT-F may also be used. Refer to Figure 2-31, "UDACT-F Mounting to MS-9200," on page 47 and
Figure 2-32, "External UDACT-F Mounting in ABS-8RF," on page 48, for information on installation.
Notes:
Reference the MS-5012 Manual for additional information
1.
Program the MS-5012 for slave operation
2.
SW2 Trouble/No AC switch located on the bottom right of the MS-9200 main circuit board, must be posi-
3.
tioned in the down position for this application. This prevents the transmission of a trouble on the loss of AC
power
Central Station Service Using MS-5012
FIGURE E-1:
AC wiring for DACT/FACP must be
connected to the same branch circuit.
94
MS-5012
Phone Line
Transformer
MS-5012 Connections to MS-9200
TABLE E-1:
Alarm
Trouble
Supervisory
Document #50428
Trouble
Supv.
MS-9200
MS-5012
MS-9200
TB2-1
TB3-5
TB2-2
TB3-3
TB2-3
TB3-8
TB2-4
TB3-6
TB2-9
TB3-2
TB2-10
TB3-1
Rev.C1
2/15/99
P/N 50428:C1
Alarm
ELR = 2.2K ohms (supplied with MS-5012)