3: Point Edit - Fire-Lite Alarms MS-9200E Programming, Installation, Maintenance And Operating Instruction Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Program Change - Level One
Control modules default to Zone 00 (general alarm). All type code options are silenceable except Relay and Strobes.
The selection of control module type codes may change their function. Select the type code from the library list
below. Use the arrow keys as described in the New Detectors section.
TYPE CODE
1
CONTROL
2
BELL CKT
3
HORN CKT
4
SOUNDERS
5
___________
6
RELAY
7
STROBES
Select an adjective descriptor from the library list shown in the New Detectors section. Use the arrow keys as
described in the New Detectors section. Control modules may be assigned to a maximum of three software zones
(refer to "Software Zones" on page 81). Zone Z00 represents general alarm. All control modules are assigned to
Zone Z00 upon initial power-up.
3.3.3 Point Edit
While displaying the Program Level 1 Menu screen (see "Program Change - Level One" on page 56), pressing '2'
allows for editing of the point (addressable device) descriptor screens. These screens show the device type, the device
address, adjective and noun field descriptors and the software zone locations that the point is assigned to. Point edit-
ing is performed after autoprogramming and may be done at any time, except during an alarm condition. The follow-
ing display will appear:
For example, select Detector address 3 program edit by pressing * key (* = detector), followed by numeric key '3', fol-
lowed by ENTER. Select Module address 3 program edit by pressing the # key (# = module), followed by the
numeric key '3', followed by ENTER. If there is no device installed at this address, the panel displays the next higher
address where a device is installed. After editing is complete and ENTER is pressed, the display returns to the above
menu. Rather than reentering the next point number, the user may press the up or down arrow key to display the next
lower or higher existing point. Using software P/N 73750 or greater, to edit NAC 1 or NAC 2, press the * key, then
the # key, the press '1' for NAC 1 or '2' for NAC 2. Select either 'BELL_CKT' for silenceable functionality or
'STROBE' for nonsilenceable functionality. Use the system edit menu described in "System Edit" on page 61, to
select coding. Coding is only possible if the NAC is programmed as 'BELL_CKT'. The point display formats and the
method of editing are described in "Autoprogram" on page 56.
60
SPECIAL FUNCTION
NONE (DEFAULT) Silenceable
Silenceable
Silenceable
Silenceable
(BLANK LABEL) Silenceable
IGNORE OPEN CIRCUIT (Nonsilenceable)
Nonsilenceable
Document #50428
Rev.C1
2/15/99