Program Change - Level One
If ENTER is pressed, the device is deleted from memory and autoprogram displays the next new device. If the left
arrow is pressed, the program is unchanged and the next new device is displayed.
After all new detectors are presented for editing, the autoprogram feature displays the modules on the SLC loop start-
ing with the device found at the lowest address.
Monitor Module Autoprogram
Monitor Module Autoprogram is similar to Detector Autoprogram. When a new monitor module is presented, a typ-
ical display might be:
The major program editing for monitor modules is the selection of the Type Code on the first line. To change this
selection, use the up and down arrow keys as the entire field blinks. The default selection is monitor as shown in the
screen above. Note that selection of a type code may change the functional operation of the addressable device.
TYPE CODE LABEL
MONITOR
PULL BOX
HEAT DET
SMOKE ZON
WATERFLOW
SUPERVISY
AUTO SUPV
TAMPER_SW
___________
ACK_SW___
SILENC SW
RESET SW
DRILL___
Follow the same procedure as described in New Detectors section, for editing of the ADJ and NOUN fields. The
default zone selection is Z00 (main circuit board NAC outputs 1 & 2) and may be set to Z01 through Z56 if desired.
See "Software Zones" on page 81.
Control Module Autoprogramming
A typical control module Autoprogram screen is shown below:
SPECIAL FUNCTION
NONE (DEFAULT)
NONE
NONE
NONE
CAUSES NONSILENCEABLE ALARM
BECOMES SUPERVISORY POINT (see Chapter 4, Operation)
BECOMES SUPERVISORY POINT (nonlatching supervisory)
BECOMES SUPERVISORY POINT (see Chapter 4, Operation)
NONE (BLANK LABEL)
FUNCTIONS LIKE ACKNOWLEDGE SWITCH
FUNCTIONS LIKE SILENCE SWITCH
FUNCTIONS LIKE RESET SWITCH
FUNCTIONS LIKE DRILL SWITCH