2.2.3 Special Application DC Power Output Connection
All Special Application DC power outputs are power-limited (refer to "UL Power-limited Wiring Requirements" on page 29).
Power-limited Non-resettable or Resettable Power
1.0 amperes max., 24 VDC nominal filtered, non-
resettable or resettable power is programmable. PWR1
can be programmed as Class B or Class A.

2.3 Relays

The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble relay,Note that relay connections may be
power-limited or nonpower-limited, provided that 0.25" spacing is maintained between conductors of power-limited and nonpower-lim-
ited circuits. Refer "UL Power-limited Wiring Requirements" on page 29.
Note that the programmable relay
labeled as Relay 1 is factory default
programmed as Alarm and
programmable Relay 3 is factory default
programmed as Supervisory.
The relay labeled Relay 2 is fixed as a
Trouble relay and cannot be changed. It
is a fail-safe relay which will transfer on
any trouble or total power failure.

2.4 Notification Appliance Circuits

The control panel provides four Class B or four Class A NACs (Notification Appliance Circuits). Each circuit is capable of 2.5 amps of
current. Total current in alarm for all external devices cannot exceed 6.0 amps (refer to "Calculating the System Current Load" on
page 128). Use UL listed 24 VDC notification appliances only. Circuits are supervised and power-limited. Refer to the Device Compati-
bility Document for a listing of compatible notification appliances. The NACs, which are located on the main circuit board, may be
expanded via the FCPS Series field charger/power supplies.
The following sections describe the configuration and wiring of Class B and Class A Notification Appliance Circuits on the ES-200X
main circuit board.
26
Optional Class A
wiring return
TB11
+ - + - + -
Figure 2.5 Special Application Power Outputs - 24 VDC
TB1
RELAY 1
ALRM
NO
NC
C
Figure 2.6 Relay Terminals
Power-limited Resettable or Non-resettable Power
1.0 amperes max., 24 VDC nominal filtered, programmable
resettable or non-resettable power can be drawn from TB11
Terminals 5(+) and 6(-)
PWR1
PWR2
24V
TB2
TB3
Relay contacts shown with power
RELAY 2
RELAY 3
applied to panel and no active
troubles, alarms or supervisories
TRBL
SUPV
NC
NO
C
NO
NC
C
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018