4: Annunciators - Fire-Lite Alarms MS-9200E Programming, Installation, Maintenance And Operating Instruction Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Accessories
1.7.4 Annunciators
AFM Series LED Zone Type Annunciators
The AFM Series Annunciators remotely display system status. The AFM/AEM-16AT annunciators display zone
alarm and trouble status. In addition, they provide remote Acknowledge, Silence, Reset and Drill functions. The
AFM/AEM-32 annunciators display zone alarm status only and provide no remote system switch functions. For
more detailed information, refer to the appropriate AFM Annunciator manual. Refer to "AFM and LDM Series Wir-
ing" on page 89, for detailed wiring requirements and "System Edit" on page 61, for information on programming the
MS-9200 for annunciator use.
AFM-16ATX
The Annunciator Fixed Module-
16ATX contains 16 red alarm
and 16 yellow trouble LEDs, a
System Trouble LED, an On
Line/Power LED and a local
piezo sounder with switches for
MS-9200 Acknowledge,
Silence, Reset and Drill. The
AFM-16ATX is fixed at address
'1' and will accept up to three
AEM-16ATF Expanders.
AEM-16ATF
The Annunciator Expander
Module-16ATF connects to the
AFM-16ATX and adds 16 sets
of red alarm LEDs and yellow
trouble LEDs. Three AEM-
16ATFs may be added to an
AFM-16ATX.
AFM-16ATF
The Annunciator Fixed Module-
16ATF contains 16 red alarm
and 16 yellow trouble LEDs, a
System Trouble LED, an On
Line/Power LED and a local
piezo sounder with switches for
MS-9200 Acknowledge,
Silence, Reset and Drill. The
AFM-16ATF is fixed at address
'1' and communication is via the
EIA-485 data line.
18
AFM-32AX
The Annunciator Fixed Module-
32AX contains 32 red alarm
LEDs, a System Trouble LED, an
On Line/Power LED and a local
piezo sounder with a local
Silence/Acknowledge switch.
The AFM-32AX is fixed at
address '1' and will accept one
AEM-32AF Expander.
AEM-32AF
The Annunciator Expander Mod-
ule-32AF connects to the AFM-
32AX and adds 32 red alarm
LEDs. The AEM-32AF is identi-
cal in frontal appearance to the
AFM-32AX. Only one expander
module is allowed.
AFM-16AF
The Annunciator Fixed Module-
16AF has 16 red alarm LEDs.
Multiple annunciators may be
used by setting all annunciators to
Receive Only, except the last
AFM-16AF in line. Each annun-
ciator's address is internally fixed
at '1', and communication is via
the EIA-485 data line. The Local
Silence/Acknowledge switch
functions as local lamp test and
silence for annunciator piezo.
LEDs include On Line and Sys-
tem Trouble indicators.
AFM-32AF
The AFM-32AF is similar to the
AFM-16AF except it has 32 red
alarm LEDs for annunciating up
to 32 points.
Document #50428
Rev.C1
2/15/99
P/N 50428:C1

Advertisement

Table of Contents
loading

Table of Contents