Fire-Lite Alarms MS-5210UD Manual
Fire-Lite Alarms MS-5210UD Manual

Fire-Lite Alarms MS-5210UD Manual

Fire alarm control panel
Table of Contents

Advertisement

PN: 50193:E
ECN 01-685
Fire Alarm Control Panel
MS-5210UD/MS-5210UDE
Document #50193
E
01/30/02
Rev.

Advertisement

Table of Contents
loading

Summary of Contents for Fire-Lite Alarms MS-5210UD

  • Page 1 PN: 50193:E ECN 01-685 Fire Alarm Control Panel MS-5210UD/MS-5210UDE Document #50193 01/30/02 Rev.
  • Page 2 While a fire alarm system may lower insurance Fire Alarm System Limitations rates, it is not a substitute for fire insurance! An automatic fire alarm system–typically made up of smoke Heat detectors do not sense particles of combustion and detectors, heat detectors, manual pull stations, audible warn- alarm only when heat on their sensors increases at a prede- ing devices, and a fire alarm control with remote notification termined rate or reaches a predetermined level.
  • Page 3 Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be con- Like all solid state electronic devices, this system may nected to the fire alarm control panel. Disconnect all sources operate erratically or can be damaged when subjected to light- of power before servicing.
  • Page 4 Notes Document #50193 Rev.E 01/30/02 P/N 50193:E...
  • Page 5: Table Of Contents

    Table of Contents CHAPTER 1: Product Description ......................... 11 1.1: Product Features ............................11 FIGURE 1-1: Optional DP-5210UD....................12 FIGURE 1-2: MS-5210UD Panel ......................13 1.2: Specifications ..............................14 1.3: Controls and Indicators ..........................15 FIGURE 1-3: Display and Keypad ......................15 1.4: Circuits ................................15 1.5: Digital Communicator..........................16 1.6: Components..............................17...
  • Page 6 Table of Contents FIGURE 2-19: Wiring LED-10IM to ACM-16ATF ................38 CHAPTER 3: Programming Instructions.......................39 3.1: Entering Program Mode ..........................39 3.2: Switch Functions ............................40 FIGURE 3-1: Control Panel Keypad ....................40 3.3: Program Options............................40 3.3.1: Level 1 - Main Panel Options ......................40 TABLE 3-1: Zone Functions .......................44 TABLE 3-2: Event Code Changes for ID Contact Format ..............46 FIGURE 3-2: Verification Timing Diagram..................47...
  • Page 7 Table of Contents FIGURE 5-1: Handset/Speaker Connection ..................83 5.3.5: NACs 1, 2, 3 and 4 ..........................84 5.3.6: Resettable Power..........................84 5.4: Lamp Test ..............................84 5.5: Print Mode..............................84 5.6: Printer Output ..............................85 CHAPTER 6: Remote Site Upload/Download .......................86 6.1: Downloading Program: General........................86 6.1.1: Security Features..........................87 6.2: Downloading Initiated at Control Panel......................88 6.3: Downloading Initiated at a Service Terminal....................89...
  • Page 8 Notes Document #50193 Rev.E 01/30/02 P/N 50193:E...
  • Page 9 This control panel has been designed to comply with standards set forth by the following regulatory agencies: • Underwriters Laboratories Standard UL 864 • NFPA 72 National Fire Alarm Code Before proceeding, the installer should be familiar with the following documents. NFPA Standards This Fire Alarm Control Panel complies with the following NFPA Standards: NFPA 72 National Fire Alarm Code for Central Station Signaling Systems Protected Premises Unit...
  • Page 10 MS-5210UD Terminals and Connectors Document #50193 Rev.E 01/30/02 P/N 50193:E...
  • Page 11: Chapter 1: Product Description

    Product Description CHAPTER 1 The MS-5210UD is a combination control panel and digital communicator all on one circuit board. It is a 10-zone panel, which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally-open contact devices. Outputs include two Notification...
  • Page 12 Product Features • Interfaces with Fire•Lite annunciators (requires LED-10IM Option Module) LED-10 Series Remote Annunciator provides one red alarm and one yellow trouble LED per zone LDM-32F Graphic Annunciator ACS Series LED Annunciators • Small Size 16.900" (42.9 cm) X 14.500" (36.8 cm) X 4.625" (11.8 cm) •...
  • Page 13 Software for the Fire Control Communicator is located in a PROM inserted in the IC socket labeled U14. The MS-5210UD and MS-5210UDE each contain unique software. For specific panel software information, refer to the MS-5210UD/MS-5210UDE Field Software Change Procedure Document #50479.
  • Page 14: Specifications

    Battery (lead acid only) - J1 Maximum Charging Circuit: Normal Flat Charge—27.6V @ 0.8 amp Maximum Charger Capacity: 18 Amp Hour battery (MS-5210UD cabinet holds maximum 12 Amp Hour battery. Larger batteries require Fire•Lite BB-17F or other UL listed battery cabinet)
  • Page 15: Controls And Indicators

    Controls and Indicators Nonresettable Regulated 24 VDC Power - TB2 Terminals 1(+) & 2(-) Maximum ripple voltage: 10 mV Operating Voltage nominal 24 volts Total DC current available from this output is up to 500 mA Power-limited Circuitry. Recommended maximum Standby current is 150 mA Refer to Fire•Lite Device Compatibility Chart for compatible listed devices Controls and Indicators Front Panel Switches...
  • Page 16: Digital Communicator

    Battery Charger Battery Charger will charge up to 18 AH batteries. The MS-5210UD cabinet holds a maximum of 12 AH batter- ies. The Fire•Lite BB-17F is required to hold 18 AH batteries. The charger is rated for 850 mA maximum cur- rent.
  • Page 17: Components

    Components • Communicate in the following formats: ✓ 12 Tone Burst Type: 20 pps (3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.) ✓ 3 Touchtone Types: 4 + 1 Ademco Express 4 + 2 Ademco Express Ademco Contact ID (Refer to Table 4-3 on page 78). Components Main Circuit Board The main circuit board contains the system's CPU, power...
  • Page 18: Optional Modules

    The PK-5210UD Program Kit includes three 3½" diskettes plus Instruction Manual P/N 50363. When the soft- ware is loaded into an IBM compatible computer, it creates an off-line Service Terminal that allows any MS-5210UD panel to be uploaded or downloaded over standard telephone lines. Requires panel firmware P/N: MS52102.0 or greater.
  • Page 19 Optional Accessories LED-10 Series Annunciator (LED Zone Type Annunciator) The LED-10 Series is a 10 zone LED annunciator which mounts on a 3-gang electrical box and provides LED indication of the following: • Alarm Zones 1 through 10 • Trouble Zones 1 through 10 •...
  • Page 20 (expander modules are not required when interfacing to the MS-5210UD). The LDM-32F and LDM-E32F have output connectors which are used to drive lamps or LEDs and input connectors which are used for remote switch functions. The LDM Series requires the use of the LED-10IM Interface Module.
  • Page 21 Optional Accessories FCPS-24F(E) Remote Power Supply (System Power Expansion) The FCPS-24F (FCPS-24FE for 220/240 VAC applications) is a compact, remote power supply and battery charger. This remote power supply consists of a filtered 24 VDC output that may be configured to drive up to four Notification Appliance Circuits [four Style Y (Class B) or two Style Z (Class A) and two Style Y (Class B)].
  • Page 22: Telephone Requirements And Warnings

    The following information is provided if required by the local telephone company: Manufacturer: Fire•Lite One Fire-Lite Place Northford, CT 06472 Product Model Number: MS-5210UD FCC Registration Number: 1W6USA-74525-AL-E Ringer Equivalence: 0.6B Note: The FCC ID label is located on the inside of the FACP door. 1.9.3 Telephone Company Rights and Warnings: The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel.
  • Page 23: Chapter 2: Installation

    Installation Installation CHAPTER 2 Mounting Options The cabinet may be either semi-flush or surface mounted. The door is removable during the installation period by opening and lifting the door off the pin hinges. The cabinet mounts using two key slots and two additional 0.250"...
  • Page 24 Backbox Mounting Draw wires through the respective knockout locations. Cabinet Dimensions and Knockout Locations FIGURE 2-1: 4.445 cm 4.445 cm (5.08 cm) 2.00" 2.00" 2.00" 2.00" 2.00" 2.00" 1.75“ 1.75“ Back (3.81 cm) 1.50“ Left Side Right Side (3.81 cm) (3.81 cm) 14.5"...
  • Page 25 Backbox Mounting FACP Backbox and Battery Box FIGURE 2-2: TR-4-R Optional BB-17F When batteries larger than 12 Amp Hour are being used, the BB-17F battery box (or equivalent) must be installed. To install the BB-17F: Mount the FACP cabinet to the wall. Remove knockouts on the bottom of the FACP cabinet and top of the BB-17F.
  • Page 26: Operating Power

    Primary Power Source (AC) and Earth Ground Connections AC power connections are made inside the control panel cabinet. The primary power source for the MS-5210UD is 120 VAC, 60 Hz, 2.3 amps and for the MS-5210UDE is 220/240 VAC, 50 Hz, 1.2 amps. Run a pair of wires (with ground conductor) from the protected premises main breaker box to TB1 of the main circuit board.
  • Page 27: Input Circuits

    Input Circuits Input Circuits The control panel has 10 zone input circuits. The maximum loop resistance limit for each input circuit is 100 ohms. All field wiring of each zone is supervised for opens and ground faults. Both conditions are visually and audibly annunciated as well as communicated to a central station.
  • Page 28: Output Circuits

    Output Circuits Style B Initiating Device Circuit Connections FIGURE 2-4: Style B (Class B) Initiating Device Circuit (supervised and power-limited). 4.7K, ½watt, P/N: 71252 UL listed. UL listed compatible 2-wire smoke detector UL listed compatible 2-wire smoke detector Manual Pull Station Manual Pull Station Heat Detector Heat Detector...
  • Page 29 Output Circuits Notification Appliance Circuits The MS-5210UD provides two Notification Appliance Circuits standard as Style Y (Class B). Each circuit is capable of 3.0 amps of current. Total current drawn from these as well as other DC power outputs cannot exceed 3.6 amps with the standard transformer, 6.0 amps if an optional XRM-24 Transformer (XRM-24E for the...
  • Page 30: Digital Communicator

    Digital Communicator Digital Communicator Two independent telephone lines can be connected to the control panel. Telephone line control/command is made possible via double line seizure as well as usage of an RJ31X style interconnection. It is critical that the panel's dig- ital communicator be located as the first device on the incoming telephone circuit to properly function.
  • Page 31: Ul Power-Limited Wiring Requirements

    0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the MS-5210UD is illustrated in Figure 2-9. Typical Wiring Diagram for UL Power-limited Requirements...
  • Page 32: Installation Of Optional Modules

    (Class A) IDCs and the two Style Y (Class B) Notification Appliance Circuits to two Style Z (Class A) NACs. J1 of the module plugs into connector J10 of the MS-5210UD, which is located at the top center of the FACP main circuit board.
  • Page 33 The NAC-REM Module can be used to add two Style Y (Class B) or Style Z (Class A) NACs (1.5 amps maximum each) and two Form-C relays to the MS-5210UD. Connector J1 of the NAC-REM module plugs into connector J7 which is located at the top left corner of the MS-5210UD main circuit board.
  • Page 34 Installation of Optional Modules Installation - Remote printers require a separate external primary power source. Also required is the PRT-24 which includes the Printer Interface Module and a 6-foot (1.83 m) interface cable prewired to a DB25 connector. Connect the interface cable to the PRT-24 as illustrated in Figure 2-13. Insert the two supplied standoffs into mounting holes near the J4 connector on the main circuit board.
  • Page 35 6,000 feet (1,800 m) @ 18 AWG (0.75 mm ) be used. Regulated power can be supplied by the MS-5210UD or a remote UL listed filtered, regulated power supply such as the Fire•Lite FCPS-24.
  • Page 36 ACM-8RF Address and SW3 DIP Switch Settings - Each of the ten MS-5210UD IDCs can be assigned to an ACM-8RF relay. Two relay modules are required, with both set to the same address. Use the decade rotary switches to set the address (i.e. for address '01', position the first [left] switch so the arrow points to '0' and the second [right] switch so the arrow points to '1').
  • Page 37 Installation of Optional Modules LDM-32F Lamp Driver Module The Lamp Driver Module is used to provide an interface to a custom graphic annunciator. The LDM-32F has 32 alarm lamp/LED driver outputs which sink current to system common (-) on activation. A single positive (+) volt- age is required to supply total operating power for all lamps or LEDs when all drivers are activated.
  • Page 38 Installation of Optional Modules ACM-16ATF and AFM-16ATF Annunciators The Annunciator Control Modules-16ATF and 16ATF each contain 16 red alarm and 16 yellow trouble LEDs, a system trouble LED, an ON LINE/POWER LED and a local piezo sounder with switches for FACP Acknowl- edge, Silence, Reset and Drill.
  • Page 39: Chapter 3: Programming Instructions

    Programming Instructions Programming Instructions CHAPTER 3 This section describes programming the panel from the onboard keyboard or the remote site upload/download soft- ware which allows programming the control panel off premises. Programming of the control panel is possible at any time except when an alarm condition is present or during a fire drill.
  • Page 40: Switch Functions

    Switch Functions Once in any of the four levels of the Programming Mode, the control panel will: • Blink the Trouble LED • Activate the trouble relay • Disable the Notification Appliance Circuit(s) • Disable the alarm relay • Display 00_F •...
  • Page 41 Program Options ✓ Enter the remaining numbers in their respective addresses as shown below: Entry 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 Address Valid entries for both the primary and secondary phone numbers are 0 to 9 and A to F with the numeric digits as dialed numbers and the hexadecimal digits representing the following functions: •...
  • Page 42 Program Options Primary Central Station Number 24 Hour Test Time (21-24) Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four locations, from addresses 21-24. The default is 00:00 (12:00 midnight). The limits for each location are as fol- lows (do not use values of A-F as entries): 21: enter 0, 1 or 2 22: enter 0-9...
  • Page 43 Program Options Secondary Central Station Number Account Code (43-46) Four locations at addresses 43-46 default to all '0s'. Valid entries are 0-9 and A-F. The number of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 42, enter three digits (one digit each in locations 43, 44 and 45 - location 46 is ignored).
  • Page 44 Program Options Make/Break Ratio for Primary Phone (59) Use this address only if you have chosen '1' for address 58. The Make/Break ratio is factory set to '0' which is 67/ 33 ratio, but may be changed to '1' which is 62/38 ratio. Touchtone/Rotary Select for Secondary Phone (60) A '0' programmed in this address by the factory triggers Touchtone dialing over the secondary phone line.
  • Page 45 Program Options Zone 2 Function Selection (65) Factory default for zone 2 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow, nonsilenceable;...
  • Page 46 Program Options Zone 10 Function Selection (73) Factory default for zone 10 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open con- tact device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow, nonsilenceable;...
  • Page 47 Programmable Relay #1 (78) Relay #1 on TB3 of the MS-5210UD main circuit board can be programmed to activate for any one of seven FACP conditions. The factory default for address 78 is '0' for activation on alarm. Program a '1' for supervisory, '2' for supervisory autoresettable, '3' for trouble, '4' for communication fail, '5' for process monitoring or '6' for pro- cess monitoring autoresettable.
  • Page 48 00:01 (military time). The far left digit will be flashing, indicating that this is the first digit to be programmed. Note that the software for the MS-5210UD operates the internal clock based upon 60 Hz. The software for the MS-5210UDE operates the internal clock based upon 50 Hz.
  • Page 49: 2: Level Two - Event Codes/Transmission Formats

    Program Options • Programming Year - After entering the last digit corresponding to minutes (far right digit), the display will read 1996 with the digit '9', second from the right, flashing. Press [ENTER/STORE] if acceptable. To change the year, enter a digit. Entering a zero '0' will change the display to the year 2000. Press the [ENTER/ STORE] key.
  • Page 50 Program Options 3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded Formats If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' are entered for address 16 in Program Mode Level 1, the data shown in Table 3- 3 is automatically programmed for the Primary Central Station phone number event codes.
  • Page 51 Program Options Event Codes, Primary Central Station Number TABLE 3-3: Address Description Setting Primary # Zone 1 Alarm Restore Code Primary # Zone 2 Alarm Restore Code Primary # Zone 3 Alarm Restore Code Primary # Zone 4 Alarm Restore Code Primary # Zone 5 Alarm Restore Code Primary # Zone 6 Alarm Restore Code Primary # Zone 7 Alarm Restore Code...
  • Page 52 Program Options 4+2 Standard and 4+2 Express Formats If '1, A or C' are entered for address 16 in Program Mode Level 1, the data shown in Table 3-4 is automatically programmed for the Primary Central Station phone number event codes. Enter '00' for the setting to disable the report.
  • Page 53 Program Options Event Codes, Primary Central Station Number TABLE 3-4: Address Description Setting 102-103 Primary # Zone 1 Alarm Restore Code 104-105 Primary # Zone 2 Alarm Restore Code 106-107 Primary # Zone 3 Alarm Restore Code 108-109 Primary # Zone 4 Alarm Restore Code 110-111 Primary # Zone 5 Alarm Restore Code 112-113...
  • Page 54 Program Options Ademco Contact ID Format If 'E' is entered for address 16 in Program Mode Level 1, the data shown in Table 3-5 is automatically pro- grammed for the Primary Central Station phone number event codes. Enter '000' for the setting to disable the report.
  • Page 55 Program Options 3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded Formats If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' are entered for address 42 in Program Mode Level 1, the data shown in Table 3-6 is automatically programmed for the Secondary Central Station phone number event codes.
  • Page 56 Program Options Event Codes, Secondary Central Station Number TABLE 3-6: Address Description Setting Secondary # Zone 2 Alarm Restore Code Secondary # Zone 3 Alarm Restore Code Secondary # Zone 4 Alarm Restore Code Secondary # Zone 5 Alarm Restore Code Secondary # Zone 6 Alarm Restore Code Secondary # Zone 7 Alarm Restore Code Secondary # Zone 8 Alarm Restore Code...
  • Page 57 Program Options 4+2 Standard and 4+2 Express Formats If '1, A or C' are entered for address 42 in Program Mode Level 1, the data shown in Table 3-7 is automatically programmed for the Secondary Central Station phone number event codes. Enter '00' for the setting to disable the report.
  • Page 58 Program Options Event Codes, Secondary Central Station Number TABLE 3-7: Address Description Setting 320-321 Secondary # Zone 2 Alarm Restore Code 322-323 Secondary # Zone 3 Alarm Restore Code 324-325 Secondary # Zone 4 Alarm Restore Code 326-327 Secondary # Zone 5 Alarm Restore Code 328-329 Secondary # Zone 6 Alarm Restore Code 330-331...
  • Page 59 Program Options Ademco Contact ID Format If 'E' is entered for address 42 in Program Mode Level 1, the data shown in Table 3-8 is automatically pro- grammed for the Secondary Central Station phone number event codes. Enter '000' for the setting to disable the report.
  • Page 60: 3: Level Three - Option Module Selections

    Program Options 3.3.3 Level Three - Option Module Selections Each option of the Program Mode is entered by keying in the program mode entry code (7764) and pressing the [ENTER/STORE] key. ☛ 7764 spells PROG on a Touch-Tone ® phone If an incorrect key is entered, reenter the proper 4-digit code before pressing the [ENTER/STORE] key.
  • Page 61 Printer Baud Rate (05) Address 05 is used to set the Baud Rate when a printer is connected to the MS-5210UD. The factory default entry is '0' for 2400 Baud. Enter '1' for 4800 Baud or '2' for 9600 Baud. An entry in address 05 is valid only if a printer has been enabled in address 04.
  • Page 62: 4: Level Four - Upload/Download Option

    Program Options NAC #4 Silence Inhibit (14) This address is used for the silence inhibit feature on NAC #4 if the NAC/Relay Option Module has been enabled in address 06. The factory default entry for NAC #4 is '0' for no silence inhibit. Enter '1' to enable the silence inhibit feature for NAC #4.
  • Page 63 Normal Mode. The MS-5210UD can be programmed remotely from a PC using a modem and the telephone line. Information can also be retrieved from the FACP with the same method. The Upload/Download Option allows an operator to set the necessary parameters to allow the uploading and downloading of data between the FACP and PC.
  • Page 64: 5: Default Programming

    Program Options FAX/Answer Machine, Secondary Phone Line (41) Factory default is '0' for no sharing of the secondary phone line with a FAX, answering machine or other device. An entry of '1' allows the panel to wait for three consecutive calls spaced 30 seconds apart from the Service Ter- minal before responding.
  • Page 65: Chapter 4: Operating Instructions

    New - with ACK lettering Old - without ACK lettering The MS-5210UD has several modes of operation including Normal, Program, Walk Test, Troubleshoot, History, Lamp Test, Print and Upload/Download. There are also four function modes which include Drill, Zone Enable/Dis- able, NAC Enable/Disable and Default Programming.
  • Page 66 Drill switch must be pressed and held for two seconds (time to prevent accidental activation). The MS-5210UD turns on all NACs and turns off the system silence LEDs. The message shown on the display is dril. The drill message is sent to the printer and history files. The system silence keys will silence all silenceable NACs during a fire drill.
  • Page 67: Led Display And Status Leds

    LED Display and Status LEDs DOWN ARROW (ACK) Use the Down Arrow key to view other events (older) that have occurred and are active (not yet cleared). It also acknowledges the event by silencing the local piezo sounder. UP ARROW (ACK) Use the Up Arrow key to view other events (newer) that have occurred and are active (not yet cleared).
  • Page 68 LED Display and Status LEDs System Fire Alarm LED A red LED that flashes when a fire alarm condition is detected during the alarm presignal period. It turns on steady when the system silence or acknowledge switches are pressed. System Trouble LED A yellow LED that blinks to indicate that a fault or abnormal condition exists and that the fire alarm system may be inoperative.
  • Page 69: Operation

    Operation Operation Normal Mode is the standard mode of operation. In this mode, the panel continuously monitors system status. When no alarm or trouble conditions exist, the display will be blank and all LEDs will be off (except the AC Power LED). The Notification Appliance Circuits will be off, all relays are in their normal state, the onboard piezo sounder will be off and the printer (if connected) will not be printing.
  • Page 70: 2: Fire Alarm Restoral

    Operation 4.3.2 Fire Alarm Restoral The control panel returns to normal after all alarms have been cleared and a system reset switch has been pressed (pull stations have been reset, smoke detectors have reset and no smoke is present, waterflow has stopped). The con- trol panel will perform the following upon restoral of all active alarms: •...
  • Page 71: 5: Trouble Condition Response

    Operation 4.3.5 Trouble Condition Response The control panel will perform the following upon detection of one or more trouble conditions: • Blink the FACP trouble LED (1 second On, 1 second Off) • Blink all annunciator general system trouble LEDs •...
  • Page 72: 7: Process Monitored Alarm Response

    Operation 4.3.7 Process Monitored Alarm Response Upon detection of a critical or noncritical process monitored alarm condition on any zone, the control panel will: • Display the alarm message PAXX (where XX = zone number) • Communicate the alarm code programmed for the activated zone •...
  • Page 73: 11: Nac (Bell) Disable/Enable

    Operation A flashing lower case d will appear on the far left of the display. Next, press the zone number to be disabled. The number will appear on the far right display character. Press [ENTER/STORE]. The zone is disabled. All system annunciators will show zone troubles and general trouble status.
  • Page 74: Central Station Communications

    'PH2' for Communicator Failure to the Secondary Central Station phone number. The MS-5210UD meets NFPA 72 National Fire Code reporting requirements for the type of signal, condition and location of the reporting premises. The general priority reporting structure is:...
  • Page 75 Central Station Communications The control panel is capable of reporting detailed messages depending upon the format in use. Table 4-1 shows the reporting structure for all formats. Format Selection Addresses (16+42) Programming Level 1 TABLE 4-1: Format # Format # Format # Format # 0, 2, 4, 6, 8...
  • Page 76 Central Station Communications Format Selection Address Explanation TABLE 4-2: Where: SSS or SSSS = Subscriber ID = Alarm (1st digit) = Alarm (2nd digit) = Zone Number = Alarm Restore (1st digit) = Alarm Restore (2nd digit) = Zone Trouble (1st digit) = Zone Trouble (2nd digit) = Zone Trouble Restore (1st digit) RTZ2...
  • Page 77: 1: Transmittal Priorities

    Central Station Communications 4.4.1 Transmittal Priorities The integral communicator transmits highest priority events first. Events in terms of priority are listed below in descending order: Alarms (Highest Priority Level) Pull Stations Waterflow Smoke Detector Other Alarm Types Supervisory Zone System Troubles Zone/NAC Disabled Fire Drill AC Fail (after delay)
  • Page 78 Central Station Communications The following table contains UL listed receivers compatible with the MS-5210UD. Compatible UL Listed Receivers TABLE 4-3: Format # (Addresses 16 & 42) ✔ ✔ ✔ 4+1 Ademco Express ✔ ✔ ✔ ✔ 4+2 Ademco Express ✔...
  • Page 79: Chapter 5: Servicing

    • Activate the trouble relay • If an audible walktest is performed, the MS-5210UD will turn on the Notification Appliance Circuits for four seconds for the first alarm on a zone. Subsequent alarms will sound for one second. Troubles cause the NACs to remain on.
  • Page 80: History Mode

    History Mode To return the control panel to Normal Mode, press the MODE key followed by the 4- digit code 6676 and then the [ENTER/STORE] key. To go to any other mode, press the MODE key followed by the appropriate 4-digit code and then the [ENTER/STORE] key.
  • Page 81 History Mode Shown below is the list of messages as they will appear on the display: History Mode Messages TABLE 5-1: DISPLAY EVENT DISPLAY EVENT ACn_ Acknowledge key pressed F__E Earth Fault A__! Zone 1 Alarm F__A Annunciator Fault A__2 Zone 2 Alarm F__P Printer Fault...
  • Page 82: Troubleshoot Mode

    Troubleshoot Mode Troubleshoot Mode In this mode, system voltages may be displayed on the 4-character display. An internal voltmeter measures the volt- age present at: ✓ zone inputs ✓ AC power input ✓ battery terminal leads ✓ NAC #1 ✓ NAC #2 ✓...
  • Page 83: 2: Ac Line

    AC line voltage drops below the Low Line threshold, and the trouble LED will turn on. Following is a list of the AC line voltage range: AC Line Voltage Low Line Normal High Line MS-5210UD: 102 VAC 115 VAC 132 VAC MS-5210UDE: 204 VAC...
  • Page 84: 5: Nacs 1, 2, 3 And 4

    Lamp Test 5.3.5 NACs 1, 2, 3 and 4 • Pressing B1, followed by [ENTER/STORE], displays the voltage on NAC #1. • Pressing B2, followed by [ENTER/STORE], displays the voltage on NAC #2. • Pressing B3, followed by [ENTER/STORE], displays the voltage on NAC #3. •...
  • Page 85: Printer Output

    Printer Output Printer Output This section illustrates sample printouts for various panel modes. Real Time Status 06-26-96 14:15:10 Zone 1 Verifying 2-Wire Smoke Detector Active 06-26-1996 14:15:20 Zone 2 2-Wire Smoke Detector Active 06-26-1996 14:15:24 Zone 2 Pull Station Active 06-26-1996 14:15:29 Zone 3 N.O.
  • Page 86: Chapter 6: Remote Site Upload/Download

    Remote Site Upload/Download Remote Site Upload/Download CHAPTER 6 The control panel may be programmed or interrogated off site via the public switched telephone network. Any per- ® ® ™ sonal computer with Windows 3.1 or greater or Windows 95, with a 1200 Baud Hayes compatible modem and Fire•Lite Upload/Download software P/N PK-5210UD, may serve as a Service Terminal.
  • Page 87: 1: Security Features

    Downloading Program: General Two basic communication mechanisms are supported as follows: • Download with callback - The Service Terminal calls the control panel. The control panel answers the call, confirms the calling party then hangs up. The Service Terminal then waits for a callback from the control panel.
  • Page 88: Downloading Initiated At Control Panel

    Downloading Initiated at Control Panel Callback to Service Terminal Anytime that the panel is remotely requested to allow an upload or download with callback, it will confirm the source of the incoming call, hang-up and call the calling party (Service Terminal phone number) back. Panel Identification Number (future) The panel identification number will be used in the future to identify the panel to the Service Terminal (when the panel calls the Service Terminal) automatically.
  • Page 89: Downloading Initiated At A Service Terminal

    Downloading Initiated at a Service Terminal Once the called Service Terminal accepts the incoming call (control panel) and verifies the secret code, the download- ing process is allowed to continue. Downloading progresses until all programmed information has been successfully loaded into the control panel. Communication terminates upon the Service Terminal hanging up or upon the FACP hanging up after a two minute time-out following completion of data transfer.
  • Page 90: Simultaneous Data Transfers

    Simultaneous Data Transfers Once an incoming call is accepted/answered by the control panel, the panel will: Establish basic modem connection Verify secret code Verify callback vs. no callback request from the Service Terminal (if callback is requested, the panel performs steps 4 through 10;...
  • Page 91: Appendix A: Battery Calculations

    Battery Calculations Battery Calculations Appendix A Use the Total Standby and Alarm Load Currents calculated in Table A-2 and Table A-3 for the following battery calculation. Battery Calculation TABLE A-1: Standby Load Required Standby Time in Hours Current (amps) (24 or 60 Hours) _______________ Alarm Load Required Alarm Time in Hours...
  • Page 92: A.1: Main Power Supply

    Battery Calculations A.1 Main Power Supply The MS-5210UD provides regulated power for operating the fire alarm control panel, operating external devices and operating the standby battery. The power for operating external devices is limited. Use Table A-2 (standby or non- alarm) and Table A-3 (alarm) to determine if external loading is within the capabilities of the power supply.
  • Page 93 Battery Calculations @24 VDC Regulated Load in Alarm TABLE A-3: # of Current Total Current Device Type Devices (amps) (amps) Main Circuit Board 0.245 0.245 LED-10IM (1 max.) 0.017 LED-10 Annunciator 0.040 Misc. Annunciators PRT-24 (1 max.) CAC-10F (1 max.) 0.020 NAC-REM (1 max.)
  • Page 94: Appendix B: Main Panel Options Program Sheets

    Main Panel Options Program Sheets Main Panel Options Program Sheets Appendix B ---To enter Programming Level 1, press the MODE key, 7764, '1', [ENTER/STORE] ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ Addresses 00 to 15 store the Primary Central Station Phone Number.
  • Page 95 Main Panel Options Program Sheets ❏ Zone 1 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open contact devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6' for waterflow (nonsilenceable);...
  • Page 96 Main Panel Options Program Sheets ❏ Zone 10 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open contact devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6' for waterflow (nonsilenceable);...
  • Page 97 Main Panel Options Program Sheets Main Panel Options Programming Sheets (Factory Default Settings) ---To enter Programming Level 1, press the MODE key, 7764, '1', [ENTER/STORE] ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏...
  • Page 98 Main Panel Options Program Sheets ❏ Zone 4 Function Select. '0' for 2-wire smoke detectors. ❏ Zone 5 Function Select. '0' for 2-wire smoke detectors. ❏ Zone 6 Function Select. '0' for 2-wire smoke detectors. ❏ Zone 7 Function Select. '0' for 2-wire smoke detectors. ❏...
  • Page 99: Appendix C: Event Codes/Transmission Format Programming Sheets

    Event Codes/Transmission Format Programming Sheets Event Codes/Transmission Format Appendix C Programming Sheets ---To enter Programming Level 2, press the MODE key, 7764, '2', [ENTER/STORE] 4+2 Standard and 4+2 Express Formats Primary Central Station ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏...
  • Page 100 Event Codes/Transmission Format Programming Sheets Event Codes/Transmission Formats Programming Sheets for 4+2 Standard and 4+2 Express Formats Secondary Central Station ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏...
  • Page 101 Event Codes/Transmission Format Programming Sheets ---To enter Programming Level 2, press the MODE key, 7764, '2', [ENTER/STORE] Event Codes/Transmission Format Programming Reference Sheet (factory defaults) 4+2 Standard and 4+2 Express Formats Primary Central Station ❏ ❏ ❏ ❏ ❏ ❏ ❏...
  • Page 102 Event Codes/Transmission Format Programming Sheets Event Codes/Transmission Formats Programming Reference Sheet (factory defaults) for 4+2 Standard and 4+2 Express Formats Secondary Central Station ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏...
  • Page 103 Event Codes/Transmission Format Programming Sheets ---To enter Programming Level 2, press the MODE key, 7764, '2', [ENTER/STORE] Event Codes/Transmission Format Programming Sheets for All 3+1, All 4+1 and 4+2 Expanded Formats Primary Central Station ❏ ❏ ❏ ❏ ❏ ❏ ❏...
  • Page 104 Event Codes/Transmission Format Programming Sheets ---To enter Programming Level 2, press the MODE key, 7764, '2', [ENTER/STORE] Event Codes/Format Programming Reference Sheets Factory Defaults for All 3+1, All 4+1 and 4+2 Expanded Formats Primary Central Station ❏ ❏ ❏ ❏ ❏...
  • Page 105 Event Codes/Transmission Format Programming Sheets ---To enter Programming Level 2, press the MODE key, 7764, '2', [ENTER/STORE] Event Codes/Transmission Format Programming Sheets for Ademco Contact ID Primary Central Station ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏...
  • Page 106 Event Codes/Transmission Format Programming Sheets Event Codes/Transmission Format Programming Sheets for Ademco Contact ID Secondary Central Station ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏...
  • Page 107 Event Codes/Transmission Format Programming Sheets ---To enter Programming Level 2, press the MODE key, 7764, '2', [ENTER/STORE] Event Codes/Transmission Format Programming Sheet Factory Default for Ademco Contact ID Primary Central Station ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏...
  • Page 108 Event Codes/Transmission Format Programming Sheets Event Codes/Transmission Format Programming Sheet Factory Defaults for Ademco Contact ID Secondary Central Station ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏...
  • Page 109: Appendix D: Ademco Contact Id Format Event Code Descriptions

    Ademco Contact ID Format Event Code Descriptions Ademco Contact ID Format Event Appendix D Code Descriptions This appendix describes the various Event Codes and their messages which are available for the Ademco Contact ID Format. The reporting structure for the Ademco Contact ID Format is as follows: SSS 18 QXYZ GG CCC where SSSS...
  • Page 110 Ademco Contact ID Format Event Code Descriptions EVENT CODE CLASSIFICATIONS ALARMS SUPERVISORY TROUBLES DISABLES/ OPEN/CLOSE TEST/ BYPASSES REMOTE ACCESS MISC. Medical Fire System Open/Close System Test Fire Sounder/Relay Remote Access Sounder/Relay Panic System Peripheral Access Control System Peripheral Burglary Communication Communication General Protective Loop...
  • Page 111 Ademco Contact ID Format Event Code Descriptions EVENT MESSAGE 24 Hour Non-Burglary - 150 and 160 150 24-Hour Non-Burg ALARM - 24-Hr. Non-Burg - # 151 Gas detected ALARM - Gas Detected - # 152 Refrigeration ALARM - Refrigeration - # 153 Loss of heat ALARM - Heating System - # 154 Water leakage...
  • Page 112 Ademco Contact ID Format Event Code Descriptions EVENT MESSAGE Communication Troubles - 350 and 360 350 Communication TROUBLE - Communication Trouble 351 Telco 1 fault TROUBLE - Phone Line #1 352 Telco 2 fault TROUBLE - Phone Line #2 353 Long range radio xmitter fault TROUBLE - Radio Transmitter 354 Fail to communicate TROUBLE - Fail to Communicate...
  • Page 113 Ademco Contact ID Format Event Code Descriptions EVENT MESSAGE Sounder/Relay Disables - 520 520 Sounder/Relay disable DISABLE - Sounder/Relay - # 521 Bell 1 disable DISABLE - Bell/Siren - #1 522 Bell 2 disable DISABLE - Bell/Siren - #2 523 Alarm relay disable DISABLE - Alarm Relay 524 Trouble relay disable DISABLE - Trouble Relay...
  • Page 114: Appendix E: Option Modules Programming Sheets

    Option Modules Programming Sheets Option Modules Programming Sheets Appendix E ---To enter Programming Level 3, press the MODE key, 7764, '3', [ENTER/STORE] ❏ CAC-10F Class A Converter Card installed. Factory default is '0' for card not installed; enter '1' to install card. ❏...
  • Page 115 Option Modules Programming Sheets Option Module Programming Reference Sheets Factory Defaults ---To enter Programming Level 3, press the MODE key, 7764, '3', [ENTER/STORE] ❏ CAC-10F Class A Converter Card not installed. ❏ LED-10IM EIA-485 Interface Module not installed. F ❏ ❏...
  • Page 116: Appendix F: Upload/Download Program Sheets

    Upload/Download Program Sheets Upload/Download Program Sheets Appendix F ---To enter Programming Level 4, press the MODE key, 7764, '4', [ENTER/STORE] ❏ ❏ ❏ ❏ Panel Identification Number. Valid entries are 0 - F. ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏...
  • Page 117: Appendix G: Wire Requirements

    Connecting external system accessories to the MS-5210UD main circuits must be carefully considered to ensure proper operation. It is important to use the correct type of wire, wire gauge and wire run length per each MS-5210UD circuit. Reference the chart below to specify wire requirements and limitations for each MS-5210UD.
  • Page 118: Appendix H: Operation And Function Modes

    Operation and Function Modes Operation and Function Modes Appendix H OPERATION MODES TABLE 6-2: CODE ACTIVITY NOTES 6676 (NORM) Returns to normal operation Fire protection on 4 levels of programming may be entered. 7764 (PROG) Enters Program Mode Fire protection is off. May select silent or audible walktest function.
  • Page 119 Index Numerics view 83 NAC-REM 33 Baud Rate 61 End of Line Resistor 1st event 66 BB-17F IDC 14 see also battery box 17, 18, 25, 91 NAC 14 ENTER/STORE 15, 67 AC input voltage error checking 88 view 83 event code 11, 46 cabinet 17 AC loss...
  • Page 120 23 power supply 92 contact rating 16 surface 23 Primary Central Station Number 24 contact ratings 36 MS-5210UD 13, 14, 26 Hour Test Time 42 Form-A 14 110 VAC input 11 Primary Central Station Number 24/12/ trouble application 29...
  • Page 121 see also ACM-8RF 11 switches 15 Waterflow Retard Timer 46 Remote Station 27 system power wire requirements 26, 117 reset 15, 19, 27, 65 see also power 11 wiring resettable power 16, 27, 28 system silence LED 68 ACM-16ATF 38 ACM-8RF 36 resettable power voltage system status 11, 12, 18, 69...
  • Page 122 Notes Document #50193 Rev.E 01/30/02 P/N 50193:E...
  • Page 123 Limited Warranty The manufacturer warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service.
  • Page 124 World Headquarters One Fire-Lite Place, Northford, CT 06472-1653 USA 203-484-7161 • Fax 203-484-7118 www.firelite.com...

This manual is also suitable for:

Ms-5210ude

Table of Contents