Optional Modules
2.15.3 RTM-8F Option Module Installation
WARNING: Disconnect all sources of pow er (AC and DC) before installing or removing any modules or
!
wiring
Insert the three supplied nylon standoffs into the holes located on the right-side edge of the MS-9200 main circuit
board. Insert the supplied metal standoff on the lower-right corner. Carefully align the pins of J6 on the main circuit
board with connector J1 on the RTM-8F option board. Press firmly on the RTM-8F until it locks in place on the
standoffs. Be certain to tighten the screw into the metal standoff on the lower-right corner. This is critical to the
RTM-8F transient protection. Affix the terminal identification labels provided with the option module.
RTM-8F Module Installation
FIGURE 2-35:
50
RTM-8F Option Module
insert here
Main Circuit Board
Main Circuit Board
Standoffs
¾" nylon standoffs
RTM-8F
¾" aluminum standoff with nut
required for transient protection
Document #50428
Rev.C1
2/15/99
Use metal screw and standoff here
P/N 50428:C1