1: Addressable Devices: 300 Series Detectors; 2: Addressable Devices: 300 Series Modules - Fire-Lite Alarms MS-9200E Programming, Installation, Maintenance And Operating Instruction Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Components
1.5.1 Addressable Devices: 300 Series Detectors
Fire•Lite's 300 Series Addressable Detectors consist of the SD300 Photoelectric smoke detector, SD300T Photoelec-
tric smoke detector with thermal sensor and the CP300 Ionization smoke detector. The detectors communicate with
the main circuit board CPU via an SLC loop. The MS-9200 CPU determines the alarm, maintenance or normal status
of each device. Each detector responds to an address that is manually set via built-in rotary decimal switches. Each
detector head has a removable plug-in connector for ease of wiring and maintenance (or service), as well as a single
LED and test connections.
Voltage Range:15-28 Volts DC peak
Standby Current:150 uA @ 24 VDC
LED Current:7 mA @ 24 VDC (latched 'ON')
Loop Resistance:40 ohms maximum
Air Velocity:CP300 = 1,500 ft./minute (7.6 m/S) max.,
SD300, SD300T
The SD300 is an addressable photoelectric smoke detector which provides smoke sensing uti-
lizing optical sense technology. The detector sends a unique 'type' code to aid the automatic
programming feature in the control panel. The SD300T includes a 135
CP300
The CP300 is an addressable ionization smoke detector which measures the level of com-
bustion products in its chamber using the 'ionization principle.' The detector sends a unique
'type' code to aid the automatic programming feature in the control panel.
RA400Z
The RA400Z is a remote single LED annunciator that can be wired directly to an address-
able detector for annunciation of that detector's alarm status.
1.5.2 Addressable Devices: 300 Series Modules
The C304 Control Module plus the M300, M301 and M302 Monitor Modules provide an interface between the
MS-9200 and conventional initiating devices and notification appliances. All modules respond to an address that is
set by the installer via two built-in rotary decimal switches. A flashing LED indicates power is applied to the mod-
ules (except for M301). A thermoplastic cover is provided with all modules, except the M301, for mounting to a 4"
square mounting box.
M300
The M300 is an addressable monitor module that can be used to monitor conventional nor-
mally open contact alarm initiating devices, such as manual pull stations, 4-wire smoke detec-
tors, heat detectors, waterflow and supervisory devices. The supervised circuit can be wired
NFPA Style B (Class B) or Style D (Class A). The M300 module will not support 2-wire
smoke detectors. The M300 modules can be tested with a test magnet available from Fire•Lite
(M02-04-00). The magnet test checks the module electronics and connections to the control
panel. The module mounts to a 4" square electrical box with a minimum depth of 2-1/8".
M301
The M301 is an addressable monitor module that is a miniature version of the M300. It con-
nects with wire pigtails (Style B [Class B] only), and may be mounted directly in the electri-
cal box of the device being monitored. Dimensions of 2.75" (6.985 cm) L x 1.30" (3.302 cm)
W x 0.50" (1.27 cm) D, allow for mounting in existing single-gang electrical boxes, the
device being monitored or similar locations.
Diameter: 5.0 inches (12.7 cm)
Height: 3.0 inches (7.6 cm)
Temperature: 0
Rel. Humidity: 10% to 85% Non-condensing
SD300 = 3,000 ft./minute (15 m/S) max.
O
F fixed thermal sensor.
Document #50428
Rev. C1
2/15/99
O
to 49
O
C (32
O
to 120
O
F)
P/N 50428:C1
13

Advertisement

Table of Contents
loading

Table of Contents