UL Power-limited Wiring Requirements

2.5
UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all
power-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different
knockouts and/or conduits. A typical wiring diagram for the MS-9200 is shown in Figure 2-8.
Typical UL Power-limited Wiring Requirements
FIGURE 2-8:
Power-limited Circuits
AC Power
RTM-8F UL Power-limited Wiring Requirements
Nonpower-limited and power-limited wiring must have a
minimum distance of 0.25" wire-to-wire. If this module is used to
drive nonpower-limited and power-limited circuits, follow the
instructions below:
Skip a set of dry contacts to maintain the 0.25" required
1.
space between power-limited and nonpower-limited
circuits.
If this module is needed to drive power-limited and
2.
nonpower-limited relays that are next to each other, make
no connection to the Normally Open contact which sepa-
rates the two groups of relays. Refer to the typical wiring
diagram to the right.
Refer to Figure 2-36, "RTM-8F Relay Transmitter Module," on
page 51, for additional information on the RTM-8F.
Nonpower-limited Circuits
Document #50428
Rev. C1
2/15/99
Power-limited Circuits
Power-limited Circuits
Nonpower-limited Circuits
Note: Output is nonpower-
limited only if programmed
as municipal box output.
Power-limited Circuit
Power-limited Circuit
Power-limited Circuit
Power-limited Circuit
No connection
Nonpower-limited Circuit
Nonpower-limited Circuit
Nonpower-limited Circuit
Nonpower-limited Circuit
Nonpower-limited Circuit
P/N 50428:C1
27