Fire-Lite Alarms MS-9600LS Manual

Fire-Lite Alarms MS-9600LS Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Addressable Fire Alarm Control Panel
MS-9600LS/MS-9600LSE
MS-9600UDLS/MS-9600UDLSE
MS-9600LSC
Manual
B2
Document 52646
2/12/2010
Rev:
P/N 52646:B2
ECN 10-098

Advertisement

Table of Contents
loading

Summary of Contents for Fire-Lite Alarms MS-9600LS

  • Page 1 Addressable Fire Alarm Control Panel MS-9600LS/MS-9600LSE MS-9600UDLS/MS-9600UDLSE MS-9600LSC Manual Document 52646 2/12/2010 Rev: P/N 52646:B2 ECN 10-098...
  • Page 2: Fire Alarm System Limitations

    (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of Limit-C1-2-2007 flammable materials, etc.). MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 3: Installation Precautions

    LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. ©Tuesday, August 14, 2012 9:31 am by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 4 •Brief description of content you think should be improved or corrected •Your suggestion for how to correct/improve documentation Send email messages to: FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 5: Table Of Contents

    2.6.2: 4XTMF Transmitter Module Installation ..................55 2.6.3: Auxiliary Trouble Input (J16 & J17)....................57 2.6.4: SLC-2LS Expander Module ......................57 2.6.5: Printer/PC ............................58 2.6.6: Annunciators............................59 Legacy ACM-8RF Relay Control Module ...................59 Legacy ACM Series Annunciators.......................60 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 6 3.7.1: Disable Point............................139 3.7.2: History .............................140 3.7.3: Program Check ..........................141 3.7.4: Walktest ............................142 3.7.5: System..............................143 3.7.6: Zone Setup ............................144 Zones Installed............................146 Zones Enabled ............................146 Zones Disabled ...........................147 Zone Type............................147 Zones Available ..........................148 Zone Message .............................149 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 7 5.3: Calculating the System Current Draw .......................174 5.3.1: Overview ............................174 5.3.2: How to Use Table 5.3 on page 176 to Calculate System Current Draw .........175 5.4: Calculating the Battery Size ........................177 5.4.1: NFPA Battery Requirements ......................177 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 8 Appendix F: HVAC Control ....................198 F.1: Control Module Operation .........................198 F.1.1: HVAC SHUTDN..........................198 F.2: Monitor Module Operation ........................198 F.2.1: HVAC RESTART ...........................198 F.2.2: HVAC OVRRIDE ...........................199 Appendix G: Canadian Application..................200 Index ............................201 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 9 Units and Accessories for Fire Alarm Systems, 9th Edition. Operation of this product with products not tested for ANSI/UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ). MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 10 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 11 Doc. # 53037 4XTMF Reverse Polarity module J10, J11 Connectors SLC Loop Addressable Devices and SLC Wiring Doc. # 51309 Battery Connector TB2 CHG-75 Charger CHG-120F Charger Doc. # 51315 Doc. # 50888 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 12 Notes MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 13: Section 1: Product Description

    The MS-9600LSC is a ULC approved Canadian version of the FACP which offers the same fea- tures as the MS-9600LS, but is supplied standard with a DP-9692 dress panel. Refer to “Canadian Option” on page 113 for a full description.
  • Page 14 Continuous, March Time, Temporal or California code for main circuit board NACs with two- stage capability • Selectable strobe synchronization per NAC • Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, legacy ACS annunciators or ANN-80 Remote annunciator MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 15: Specifications

    1.3 Specifications AC Power - TB1 of Power Supply Board MS-9600LS(C) & MS-9600UDLS: 120 VAC, 50/60 Hz, 3.0 amps (L1=Hot, L2=Neutral) MS-9600LSE & MS-9600UDLSE: 240 VAC, 50 Hz, 1.5 amps (L1=Hot Leg 1, L2=Hot Leg 2) Wire size: minimum 14 AWG (2.00 mm...
  • Page 16 Terminal Mode annunciator connector, Terminal 5 (In +), 6 (In -), 7 (Out +), 8 (Out -) Supervised, power-limited. EIA-232 Serial - TB7 Local serial PC/Printer Connector, Terminal 1 (Transmit), 2 (Receive), 3 (DTR), 4 (Ground) Non-supervised, power-limited. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 17: 1: Current Availability

    LED backlight will turn off to conserve batteries. LED Indicators LED indicators are provided to annunciate the following conditions: • AC Power (green) • Fire Alarm (red) • Supervisory (yellow) • Trouble (yellow) MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 18: Circuits

    • 24 VDC Resettable (smoke detector power) output - 1.5 amps maximum • 24 VDC Nonresettable power output #1 - 1.5 amps maximum • 24 VDC Nonresettable power output #2 - 1.5 amps maximum • 24 VDC Battery Charger (up to 26 AH batteries) MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 19: Components

    18 Amp Hour). Batteries larger than 18 Amp Hour up to 26 Amp Hour require use of the BB-26 or similar UL listed battery cabinet. The CHG-75 can be used for charging 26 to 75 AH batteries and MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 20: 1: Intelligent Addressable Detectors: Newer Series

    1.6.3 300 Series Intelligent Addressable Devices Fire•Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9600LS FACP. The FACP must be configured for CLIP Mode operation if the control panel is installed in an existing system with 300 Series devices. The address of 300 Series devices cannot be set above 99.
  • Page 21: Optional Modules

    MS-9600UDLS for local connection of the PC to the USB port J4 on the DACT-UD2. The MS-9600LS requires connection to the Serial Port on FACP con- nector TB7. Remote programming requires that the PC have a 2400 baud or faster modem.
  • Page 22: 2: Dress Panel: Dp-9692

    1.8.5 Battery Charger CHG-75 Battery Charger The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the MS-9600LS FACP. The FACP battery charger must be disabled when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box.
  • Page 23: 6: New Ann-Bus Annunciators/Devices

    FACP on a single wire run. The table ensures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges, MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 24: Wiring Distance Calculation Example

    Wiring Distance Calculation Example: Suppose a system is configured with the following ANN-BUS modules: • 3 ANN-80 Remote Fire Annunciators • 1 ANN-S/PG Serial/Parallel Printer Interface Module • 1 ANN-I/O LED Driver Module MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 25: Wiring Configuration

    B A (+) (-) 4 3 2 1 ANN-BUS/ ANN-BUS Device 24 VDC ACS BUS nonresettable + - + - + - FACP Figure 1.3 FACP wiring to ANN-BUS Device MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 26: Ann-Bus Device Addressing

    NOTE: Address (ID Number) DIP switches on some devices may have more than 5 switch positions. Unless otherwise specified in the documentation supplied with each device, switch positions 6 and above must be set to OFF. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 27: Remote Fire Annunciator

    To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the cover closed, snapping it shut. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 28 The cover cannot be reattached or removed after the annunciator has been mounted. Annunciator mounted on Annunciator mounted on Annunciator mounted on stacked surface wedge from the surface backbox from the surface wedge and backbox from ANN-SB80KIT ANN-SB80KIT the ANN-SB80KIT MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 29 ANN-BUS and power wiring are supervised and power-limited ANN-BUS B A (+) (-) 24 VDC ANN-BUS/ nonresettable 4 3 2 1 ANN-80 ACS BUS + - + - + - FACP Figure 1.6 ANN-80 Wiring to FACP MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 30: Ann-S/Pg Serial/Parallel Interface Installation

    + - + - + - FACP Figure 1.7 ANN-S/PG Connection to FACP Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address) to the module. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 31: Setting Printer Options

    Country E-US ASCII Serial Auto CR Baud 9600 or 2400 Color Option Not Installed Format 7 Bit, Even, 1 Stop Formien Protocol XON/XOFF Lines 6LPI=60 Character Set Standard Table 1.2 PRN-6F Setup Options MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 32: Ann-I/O Led Driver Module

    FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN-BUS ID number. Terminals not used (future) ANN-BUS (ID#) Address DIP switch ANN-BUS Connector Figure 1.8 ANN-I/O Board Layout MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 33 “ANN-I/O Options” on page 123 of this manual. The LEDs are wired as illustrated in Figure 1.10. Note that the illustration depicts only connectors P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40). MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 34: Ann-Led Annunciator Module

    (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones or addressable points. The ANN-LEDR provides alarm (red) indication for up to 30 input zones or addressable points. Multiple ANN-(R)LED modules may be used for full system coverage. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 35 F (0 C to 49 • For indoor use in a dry location only Mounting/Installation  Refer to the documentation supplied with the ANN-LED module for mounting information. Figure 1.12 Exploded View of ANN-LED MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 36: Ann-Rly Annunciator Module

    2 amps @ 30 VDC (resistive) • 0.5 amps @ 30 VAC (resistive) • Operating Temperature: 32 F to 120 F (0 C to 49 • For indoor use in a dry location only MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 37 ANN-MBRLY mounting bracket grounding wire mounting holes ANN-MBRLY mounting bracket ANN-RLY mounting holes mounting holes ROME Series Installation using ANN-MBRLY mounting bracket ANN-RLY on ANN- mounting holes MBRLY mounting bracket Figure 1.14 ANN-RLY Mounting Options MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 38: Ann-Bus Audio Panel Control

    The programmer can select which of the five audio messages at the audio panel will play when an FACP input zone goes into alarm (refer to “Zone Message” on page 149). The message will play over the corresponding audio panel output circuit. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 39 A(+)/B(-) terminals on TB9 of the FACP and TB1 terminals 2 & 3 of the ACC-ZPMK module on the audio panel. ACC-ZPMK on ACC-25/50ZS Series A (+) B (-) ANN-BUS FACP Figure 1.16 FACP Connection to ACC-25/50ZS Series Audio Panel MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 40: 7: Legacy Acs Annunciators

    The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are used to provide an interface to a custom graphic LED annunciator. 1.9 Getting Started The following is a brief summary of the minimal steps involved in bringing an MS-9600LS/MS- 9600UDLS on-line: •...
  • Page 41 Enter Autoprogramming (refer to “Autoprogram” on page 66). • Resolve Programming Conflicts. • Go to Point Program to Enter Specific Data (refer to “Point Program” on page 67). Use the right and left arrow keys to navigate between devices. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 42: Section 2: Installation

    • Secure the chassis to the mounting studs with the supplied nuts. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 43 (refer to mounting slots “AC Power and Earth Ground Connection” on page 46) FACP Backbox Figure 2.1 FACP Main Circuit Board Installation MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 44 16.00“ (40.64 cm) 2.00“ 5.207“ 4.128 cm 13.23 cm Hinge Slot for optional Dress Panel 4.535“ 13.23 cm 5.207“ 11.52 cm 1.00“ (2.54 cm) 1.30“ 3.30 cm Figure 2.2 FACP Cabinet Mounting MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 45 Door = 16.821" (42.73 cm) 5.325" Backbox = 16.65" (42.29 cm) (13.526 cm) Door = 19.26" (48.92 cm) Backbox = 19.0" (48.26 cm) Left Side Right Side Bottom Figure 2.3 FACP Cabinet Dimensions MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 46: Power

    2.2.1 AC Power and Earth Ground Connection Primary power required for the FACP is 120 VAC, 60 Hz, 3.0 amps for the MS-9600LS(C) and MS-9600UDLS or 240 VAC, 50 Hz, 1.5 amps 120 VAC for the MS-9600LSE and MS-9600UDLSE. Overcurrent protection for...
  • Page 47: 3: Special Application Dc Power Output Connection

    VDC notification appliances only. Circuits are supervised and power-limited. Refer to the Device Compatibility Document for a listing of compatible notification appliances. The NACs, which are located on the main circuit board, may be expanded via the FCPS Series field charger/power sup- plies. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 48: 1: Configuring Nacs

    JP8. This will allow room NACKEY card slot for the 4XTMF module. 4XTMF OPT BD 4XTMF Module connectors connectors for 4XTMF option module Figure 2.6 NAC Configuration Using NACKEY MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 49: 2: Style Y (Class B) Nac Wiring

    Circuits, supervised and power-limited Polarized Bell Polarized Bell Polarized Strobe Polarized Strobe Polarized Horn Polarized Horn Notification Appliance Circuit polarity shown in alarm state NAC 1 NAC 2 Figure 2.8 NAC Style Z (Class A) Wiring MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 50: Power-Limited Wiring Requirements

    A typical wiring diagram for the FACP is shown below. 4XTMF SLC-2LS Figure 2.9 Typical Power-limited Wiring Requirements MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 51: Optional Modules And Devices

    NOTE: When installing the DACT-UD2, the main motherboard must be removed from the chassis. Unplug the power supply cable from J1 before proceeding. Keypad/Display Mounting Screw Access Hole screw standoff standoff screw screw screw screw screw Keypad/Display Mounting Screw Access Holes Figure 2.10 Keypad/Display Removal MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 52: 1: Dact-Ud2 Installation

    The DACT-UD2 module plugs into connector J2 on the FACP main circuit board. Primary Phone Line Secondary Phone Line J5 Connector (located on back of module) plugs into J2 on FACP main circuit board USB Port Figure 2.11 DACT-UD2 Module MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 53 Secure the module to the standoffs on the main circuit board with two of the screws supplied with the DACT-UD2 and the supplied male/female standoff which becomes the new Keypad/Display support in that location ( see Figure 2.13) NOTE: It is important that the supplied hardware be used to secure the module in order to help protect against electrical transients. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 54 11. Refer to the Telephone Requirement and Warnings section of the DACT-UD2 Installation and Programming Manual Document #53037, before proceeding with this step. Connect the premises primary and secondary phone lines to the DACT-UD2 as illustrated in Figure 2.14 and test the system for correct operation MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 55: 2: 4Xtmf Transmitter Module Installation

    Trip Current: 350 mA (subtracted from notification appliance power) Coil Voltage: 3.65 VDC Maximum Coil Resistance: 14.6 ohms Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 56 Reapply power to the FACP For proper 4XTMF operation, the output relays must be programmed for the factory default settings as shown on the PC board silkscreen: Alarm Relay, Trouble Relay and Supervisory Relay MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 57: 3: Auxiliary Trouble Input (J16 & J17)

    Remove all power (AC and DC) from the FACP before installing the SLC-2LS module Remove four screws from main FACP motherboard, from locations indicated in following illustration, and replace with four supplied metal standoffs MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 58: 5: Printer/Pc

    Carefully plug connector J3 on the SLC-2LS module into connector J3 on the MS-9600LS/MS-9600UDLS main circuit board, being careful not to bend any pins Secure the SLC-2LS Expander Module to the four standoffs installed in step 2 with the four supplied screws (or the screws removed in step 2) Connect the SLC wiring and devices to TB8 on the SLC Expander Module.
  • Page 59: 6: Annunciators

    The Windows-based PK-CD Programming Utility Kit contains a CD-ROM with on-line help file. 2.6.6 Annunciators Legacy ACM-8RF Relay Control Module The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 60: Legacy Acm Series Annunciators

    Optional Modules and Devices Legacy ACM Series Annunciators ACM and AFM Series Annunciators provide visual indications of FACP status in remote locations. Refer to the appropriate annunciator manual for information on installation, wiring and operation. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 61: Section 3: Programming

    Local or remote programming and editing can also be accomplished using the DACT-UD2 Digital Alarm Communicator/Transmitter which is optional for the MS-9600LS and supplied standard with the MS-9600UDLS. Refer to the DACT-UD2 Manual P/N 53037 for detailed information.
  • Page 62: User Programming

    Windows-based computer and the DACT-UD2 USB connection on the MS-9600UDLS or Serial Port connection on TB7 of the MS-9600LS. For programs requiring a large amount of data entry, this method may be preferred. A PK-CD programming CD-ROM...
  • Page 63: Initial Power-Up

    From either of the screens, access to specific system and device features or programming may be obtained. All user programming entries are stored in non- volatile memory. The factory set passwords can be changed by the user as described in “Password MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 64 PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 65: Master Programming Level

    ‘up’ arrow key will display the previous screen. PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOPS Programming Screen #2 PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES Programming Screen #3 PROGRAMMING 1=PASSWORD CHANGE 2=CLEAR PROGRAM 3=PROGRAM CHECK Programming Screen #4 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 66: 1=Autoprogram

    In the preceding example, the first display indicates that Loop 1 has 55 addressable detectors, 35 monitor modules and 30 control modules installed. The second display indicates that Loop 2 has no devices installed. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 67: 2: Point Program

    Add Detector  Pressing 1 while viewing the Detector Screen will display the following screen which allows the programmer to add a new detector address to programming: ADD DETECTOR ENTER DETECTOR# Add Detector Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 68: Add Detector

    005. When the last digit is keyed-in, the following screen will be displayed: DELETE DETECTOR DETECTOR# IS DELETED The programmer can continue deleting detectors by pressing the ESC or left arrow key which will return the display to the Delete Detector Screen. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 69: Edit Detector

    If a detector (such as a photoelectric detector) with the selected address is not physically installed on the SLC or has a communication fault but the address is programmed in the system, the follow- ing screen will be displayed: TROUBL SMOKE(PHOTO) ******************** ZNNN 1D017 Edit Detector Screen #1 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 70 • V or * - indicates whether or not alarm verification is enabled (V = alarm verification enabled and * = alarm verification disabled) • 1D017 - represents the Loop, Device type and Device address (1 = SLC Loop 1, D=Detector and 017 = Detector Address 017) MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 71 To select the type of detector being programmed, press the 2 key while viewing the Edit Detector Screen #2. This will cause the control panel to display the following Detector Type Screens: DETECTOR TYPE 1=SMOKE PHOTO 2=USER DEFINED-1 3=SMOKE (ION) Detector Type Screen #1 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 72 Refer to “Positive Alarm Sequence” on page 158. For example, if a detector with address 005 is to be configured for PAS operation: • Select PAS Yes when editing the detector set to address 005 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 73: Zone Assignment

    A maximum of five zones can be programmed to each addressable detector. Pressing 1 while view- EDIT DETECTOR ing Edit Detector Screen #4 displays the following screen: 1=ZONE ASSIGNMENT 00 ** ** ** ** ZONE ASSIGNMENT Edit Detector Screen #4 Z00 Z** Z** Z** Z** Zone Assignment Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 74 Pressing 1 while viewing Edit Detector Screen #5 will cause the 1=NOUN/ADJECTIVE 2=DESCRIPTION following screen to be displayed: ***************** Edit Detector Screen #5 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 75 1=MAIN 1=REAR 2=FIRST 2=UPPER 3=2ND 3=LOWER Adjective Screen #4 Adjective Screen #3 ********************** ********************** 1=3RD 1=FLOOR1 2=4TH 2=FLOOR2 3=5TH 3=FLOOR3 Adjective Screen #5 Adjective Screen #6 ********************** 1=FLOOR4 2=FLOOR5 3=ROOM Adjective Screen #7 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 76 3=HVAC RM Noun Screen #3 Noun Screen #4 ********************** ********************** 1=KITCHEN 1=PATIENT 2=LOBBY 2=RESTROOM 3=OFFICE 3=ROOM Noun Screen #5 Noun Screen #6 ********************** ********************** 1=STAIRWAY 1=ZONE 2=STOREROOM 3=WING Noun Screen #8 Noun Screen #7 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 77 With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun field. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 78: Module Programming

    A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 005. When the last digit is keyed-in, the following screen will be displayed: ADD MODULE 1=CONTROL 2=MONITOR Add Module Screen #2 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 79: Add Module

     The programmer can change a modules existing or factory default programming by pressing 3 in the Modules Screen. The following screen will be displayed: EDIT MODULE ENTER MODULE ADDRESS Edit Module Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 80 If the selected address corresponds to a control module, a screen displaying information about the control module with the selected address will be displayed as shown in “Edit Module Screen for Control Modules” on page 88. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 81 No is selected, the module will not be polled by the control panel, preventing the module from reporting alarms and troubles to the panel. The control panel will indicate a system trouble condi- tion and the Disable LED with turn on if any devices are disabled. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 82 Monitor Type screens, select the type of monitor module being programmed by pressing the corresponding keypad number key. The display will return to the Edit Monitor Screen #2 which will show the new type selection. Table 3.1 lists the Monitor Types and their respective functions. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 83 Wiring Manual (document number 51309). Fire and non-fire devices must not be used on the same SLC branch. 3 For all entries ending in AR, AR refers to AutoResettable. 4 For HVAC RESTART and HVAC OVRRIDE descriptions, refer to “Monitor Module Operation” on page 198. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 84 Pressing 1 while viewing Edit Monitor Screen #5 will ***************** cause the following screen to be displayed: Edit Monitor Screen #5 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 85 3=LOWER Adjective Screen #4 Adjective Screen #3 ********************** ********************** 1=3RD 1=FLOOR 1 2=4TH 2=FLOOR 2 3=5TH 3=FLOOR 3 Adjective Screen #5 Adjective Screen #6 ********************** 1=FLOOR 4 2=FLOOR 5 3=ROOM Adjective Screen #7 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 86 Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previ- ous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PS-Tools programming kit. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 87 Press the right arrow key to advance the zone field. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01 through Z99 may be selected to link software zones. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 88 (NNN = the three digit zone number from 000 - 099). • 1M002 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module and 002 = Module Address 02). MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 89 Control Screen #2 and indicate the new type selection. NOTE: A control relay module set to the Resettable Power type will follow the main circuit board 24 VDC resettable power unless the control relay module is disabled. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 90 Enter the two digit number corresponding to the zone that is to be assigned to this device. The cursor moves to the next Z** designation. Continue entering zone assignments or the MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 91 Pressing 1 while viewing Edit Control Screen #4 will cause the following screen to be displayed: Edit Control Screen #4 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 92 3=LOWER Adjective Screen #4 Adjective Screen #3 ********************** ********************** 1=3RD 1=FLOOR 1 2=4TH 2=FLOOR 2 3=5TH 3=FLOOR 3 Adjective Screen #5 Adjective Screen #6 ********************** 1=FLOOR 4 2=FLOOR 5 3=ROOM Adjective Screen #7 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 93 Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previ- ous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PS-Tools programming kit. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 94 Press the right arrow key to advance the zone field. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01 through Z99 may be selected to link software zones. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 95: 3=Zone Setup

    Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second digit is entered, the zone will be enabled and the cursor returns to the original position next to the Z. Another zone can then be enabled. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 96: Disable

    Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to “Two Stage Opera- tion” on page 111 for a description of this feature. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 97: Zones Installed

    This display will show all of the zones that are disabled in the control panel. Note that an up and/or down arrow may appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the additional zones. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 98: Zone Type

    To program a waterflow circuit as nonsilenceable, refer to “System Setup” on page 100. NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will only change how it is reported to the Central Station. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 99: Zones Available

    6, the trouble condition will latch at the FACP. When the SLC Loop has been repaired, the Reset button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired) to clear the SLC trouble. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 100: Loop Protocol

    Important! For Canadian Applications, this option must be set to ON prior to any other panel programming. • Waterflow Silenceable: This option provides the ability to silence any output circuit activated by a monitor module programmed as a waterflow type. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 101: Trouble Reminder

    The top line of the display, which appears when the control panel is in normal mode, can be changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause the following to be displayed: BANNER 1=FACTORY 2=USER DEFINED Banner Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 102 * (QZ) key four times to place a blank in the desired position. When all charac- ters have been entered, press Enter to store the information and return to the Banner Screen. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 103: Time-Date

    To change the date, enter the two-digit month followed by the two-digit day and then the two-digit year (09 for 2009, 10 for 2010, etc.). The cursor will move one position to the right each time a MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 104: Daylight Savings

    1 will select the first week, 2 will select the second week, and 3 will select the third week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will select the last week of the selected month. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 105: Timers

    The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of 001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen #1. The following screen will be displayed: PRESIGNAL DELAY RANGE 0-180 SECONDS Pre-signal Delay Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 106: Waterflow Delay

    1=NO DELAY 2=ENTER DELAY AC Loss Delay Screen #1 Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss report immediately to the central station. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 107: Nac (Notification Appliance Circuit)

    NAC 2, 3 for NAC 3, or 4 for NAC 4. Note that 3=NAC 3 and 4=NAC 4 will only be displayed if the NACKEY NAC option card is installed, in JP8 of the main circuit board, for Class B operation. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 108 Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 109 Silence key is pressed. The visual devices (strobes, etc.) will continue to operate. If the Strobe Sil Sync feature is selected, Silence will turn off both audible and visual devices. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 110: Auto Silence

    Pressing 2 while viewing NAC Screen #2 will cause the following displays to appear: CODING 1=STEADY 2=MARCH TIME 3=CALIFORNIA Coding Screen #1 CODING 1=TEMPORAL 2=TWO STAGE 3 MIN 3=TWO STAGE 5 MIN Coding Screen #2 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 111 A maximum of five zones can be programmed to each main circuit board NAC. Pressing 1 while 00 00 00 00 00 2=SIL INHIBITED NO viewing NAC Screen #3 displays the following screen: NAC Screen #3 ZONE ASSIGNMENT Z00 Z** Z** Z** Z** Zone Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 112: Relays

    Pressing 3 while viewing System Setup Screen #2 allows the programmer to configure two of the 2=NAC main circuit board Form-C relays from the following screen: 3=RELAYS System Setup Screen #2 RELAYS 1=RELAY 1 2=RELAY 2 3=RELAY 3 Relays Selection Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 113: Canadian Option

    Canadian Opt. On and Canadian Opt. Off.: System Setup Screen #3 SYSTEM SETUP 1=CANADIAN OPT. 2=WATERFLOW SIL. Important! For Canadian Applications, this option must be set to ON prior to any other panel pro- gramming. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 114: Waterflow Silenceable

    When Loop verification has been completed, the display will indicate that the system is OK or, if problems have been detected, any device type programming errors. Use the up and down arrow keys to view all detected errors. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 115: 7: History

    Pressing 1 while viewing the Erase History Screen will erase all events from the History file. Dur- ing this process, the display will read as follows: ERASING HISTORY PLEASE WAIT Erase History Wait Screen After the History file has been erased, the display will return to the History Screen. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 116: 8: Walktest

    All stored events can be scrolled on the screen by pressing the up or down arrow keys. To return to the first event, press the 1st Event key. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 117: 9: Option Modules

    Options available for the FACP include ACS, Graphic, LED, Relay and LCD annunciators, printer 1=HISTORY 2=WALKTEST connection for acquiring hardcopy printouts of panel data and PC (Personal Computer) connection 3=OPTION MODULES for uploading and downloading panel data. Programming Screen #3 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 118: Annunciators/Udact

    While viewing the Annunciators Screen, each press of the 1 key for Term Options, will cause the display to toggle between Term Enabled No and Term Enabled Yes. NOTE: The LCD-80F is a Terminal Mode annunciator. To enable the FACP for LCD-80F operation, press 1 for Term Enabled Yes. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 119: Acs Options

    No to Yes. Each press of the number key will cause the display to toggle between No and Yes. The address of each installed annunciator must be enabled to allow communication between the FACP and annunciator. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 120 NAC Fault Pressing 3 while viewing the ACS Options screen will toggle the display between UDACT NO and UDACT YES. This allows the connection of an external UDACT (Universal Digital Alarm Com- municator/Transmitter). MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 121 Addresses 1-8. To program an ANN-BUS module to a specific address, press the number key cor- responding to the desired address in each screen. The following screen will be displayed for each address: ANN-BUS MODULES ANN-BUS ADDRESS # 1=TYPE NONE ANN-BUS Address Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 122 ANN-BUS Address Screen Since the options for each of these module types can be individually set, pressing 2 for Module Options, while viewing the ANN-BUS Address Screen will display the available options as described below. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 123 The LED assignments for each ANN-I/O module will be as follows. ANN-I/O Module #1 ANN-I/O Module #2 ANN-I/O Module #3 Module LED Function Function Function AC Fault Zone 30 Zone 70 Fire Alarm Zone 31 Zone 71 Supervisory Zone 32 Zone 72 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 124 Zone 64 Not Used Zone 25 Zone 65 Not Used Zone 26 Zone 66 Not Used Zone 27 Zone 67 Not Used Zone 28 Zone 68 Not Used Zone 29 Zone 69 Not Used MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 125 Point 147 Not Used Point 28 Point 68 Point 108 Point 148 Not Used Point 29 Point 69 Point 109 Point 149 Not Used Point 30 Point 70 Point 110 Point 150 Not Used MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 126 Pressing 2 while viewing ANN-LED Address Screen #3 will select either addressable detectors or addressable modules to be annunciated. Pressing 3 while viewing ANN-LED Address Screen #3 will select the SLC loop with the address- able devices to be annunciated. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 127 Active/Alarm Active/Alarm Active/Alarm Active/Alarm ANN-RLED Module #2 The LED assignments for the modules annunciating Zone Ranges 60 - 89 and 90 - 99, will follow the same pattern as the second ANN-RLED module. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 128 The LED assignments for the modules annunciating Zone Ranges 20 - 29, 30 - 39, 40 - 49, 50 - 59, 60 - 69, 70 - 79, 80 - 89 and 90 - 99, will follow the same pattern as the second ANN-LED module. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 129 ANN-RLED Module #2 (Point Range 31 - 60) The LED assignments for the modules annunciating Point Ranges 61 - 90, 91 - 120, 121 - 150, and 151 - 159, will follow the same pattern as the second ANN-RLED module. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 130 60, 61 - 70, 71 - 80, 81 - 90, 91 - 100, 101 - 110, 111, 120, 121 - 130, 131 - 140, 141 - 150 and 151 - 159, will follow the same pattern as the second ANN-LED Module. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 131 Configure feature to work. ANN-BUS Screen #1 Pressing 3 while viewing ANN-BUS Screen #1 will begin the Auto-Configure process and cause the following screen to be displayed: ANN-BUS AUTO-CONGFIGURE IN PROGRESS PLEASE WAIT Auto-Configure Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 132 No Parity, Even Parity, or Odd Parity. Pressing 1 for Stop Bits while viewing ANN-S/PG Options screen #3 will cause a screen to appear which allows the user to select between 1.0 or 2.0 Stop Bits. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 133 Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Drl Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill button never func- tions). MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 134: On Board Dact

    Pressing 3 while viewing the Printer-PC Screen will program the control panel for a PC connection. The display will return to the Option Module Screen which will indicate Printer/PC PC for per- sonal computer installed. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 135: 10: Password Change

    10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed: VERIFY NEW PASSWORD Password Change Screen Re-enter the new password to accept the change. The display will return to the initial Password Change Screen. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 136: 11: Clear Program

    WARNING! SYSTEM CHANGE PROCEED? 1=YES 2=NO Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will pre- vent programming from being cleared. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 137: 12: Program Check

    (control module in this example) with an address of 001 on loop 1 but have not been programmed to any input devices. Use the up and down arrow keys to view all the zones without input assignments. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 138: Maintenance Programming Level

    To enter the Maintenance Programming mode, press 2. The display will read as follows: PROGRAMMING ENTER PASSWORD When the Maintenance level password (default 11111) is entered, the following screen will appear: PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 139: 1: Disable Point

    Select the device type by pressing 1 for an addressable detector or 2 for an addressable module. The operator will be prompted to enter the three digit device address as shown in the following example for a detector: EDIT DETECTOR ENTER POINT ADDRESS Address Select Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 140: 2=History

    To view all of the selected events, press the up or down arrow keys to scroll through the list of events. If no events have occurred, the display will read NO EVENTS IN HISTORY. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 141: 3: Program Check

    NOTE: If the NACs have been configured for Class A in the Setup option, only NAC1 and NAC2 will display test information. NAC3 and NAC4 will display asterisks (*) and will not be included in the test. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 142: 4: Walktest

    UNIT IN WALKTEST. To end the Walktest, press the Esc (Escape) key. Pressing 3 after the walktest has been completed, will allow the operator to view the results of the walktest. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 143: 5: System

    (0000 - 1259). When the fourth digit is entered, the cursor will move one position to the right. Press 1 for AM or 2 for PM to complete entering the time. The display will return to the Time and Date Screen displaying the new time. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 144: 6: Zone Setup

    2=DISABLE 3=ZONE 97 98 99 Zone Setup Screen #1 ZONE SETUP 1=ZONES INSTALLED 2=ZONES ENABLED 3=ZONES DISABLED Zone Setup Screen #2 ZONE SETUP 1=ZONE TYPES 2=ZONES AVAILABLE 3=ZONE MESSAGE Zone Setup Screen #3 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 145 PAS 97 On and PAS 97 Off. When Zone 97 is programmed On, a PAS (Positive Alarm Sequence) activation of any detector will cause Zone 97 to activate. By assigning Zone 97 to a control module in the Programming Zone Assignment Screen, an output device con- MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 146: Zones Installed

    This display will show all of the zones that are enabled in the control panel. Note that an up and/or down arrow may appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the additional zones. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 147: Zones Disabled

    Note that an up and/or down arrow will appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view zones Z00 through Z99. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 148: Zones Available

    The display will show all of the zones that are still available for programming. Note that an up and/or down arrow may appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow key to view additional screens. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 149: Zone Message

    Messages 1 through 5. When a message is selected, the display will return to the Zone Message screen, showing the message selected for that particular zone. In the example above, Zone 01 has been programmed for Message 1. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 150: Section 4: Operating Instructions

    This red LED flashes when one or more alarms occur. It illuminates steady when the Acknowl- edge/Step or Alarm Silence key is pressed. The Fire Alarm LED turns off when the Reset key is pressed. The LED will remain off if all alarms have been cleared. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 151: Normal Operation

    • Refreshes LCD display and updates time • Scans control panel keypad for key presses • Performs autotest for all SLC devices • Tests memory • Updates and reads all communications busses (EIA-485, EIA-232, etc.) MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 152: Trouble Operation

    INVREP - maintenance alert indicating a hardware problem in the detector  TEST F - indicating a detector has failed the automatic test operation which functionally  checks its sensing chamber and electronics MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 153: Alarm Operation

    Terminate upload or download communications • Alarms must be Acknowledged before the FACP can be reset A typical alarm display would be as illustrated below: ALARM PULL STATION <ADJ> <NOUN> Z000 10:00A 010810 1M001 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 154: Supervisory Operation

    Silenced alarms are not resounded • Timers are not started • Store event in history buffer • Terminate upload or download communications • Supervisory condition must be Acknowledged before the FACP can be reset MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 155: Process Monitor Operation

    Hazard condition must be Acknowledged before the FACP can be reset Hazard conditions latch and will therefore clear only when the hazard condition is cleared and the panel reset. They can be assigned to software zones. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 156: Medical Alert Condition Operation

    5 hours (if the loop has the maximum number of devices installed). The detector’s sensing chamber and electronics are functionally tested for normal, safe operation. A trouble message is displayed upon failure of this test. A System Reset will clear this trouble. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 157: Time Functions: Real-Time Clock

    Pulses at ½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ second Off • California Code: 10 seconds On, 5 seconds Off • Two-Stage Pulses at 20 ppm (pulses per minute) for 5 minutes and then changes to Temporal MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 158: Presignal

    Alarm Silence or Acknowledge/Step button is pressed, the annunciators will be inhibited from activating for an additional time delay • outputs (NACs and control modules) of associated zones will be inhibited from activating for a factory set duration of 15 seconds MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 159: Special System Timers

    FACP. If a different detector alarms any time during the first detector's verification period, the panel will immediately activate MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 160: Walktest

    Read Status mode. This mode can be entered while the control panel is in alarm or trouble. If a new alarm or trouble occurs during these functions, the Read Status is exited to pre- vent confusion. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 161: 3=Power

    1=ANNUNCIATORS 2=PROGRAM CHECK 2=PHONE LINE 3=HISTORY 3=CENTRAL STATION Read Status Screen #3 Read Status Screen #4 READ STATUS READ STATUS 1=SERVICE TERMINAL 1=TIME-DATE 2=PRINTER/PC 3=PRINT Read Status Screen #5 Read Status Screen #6 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 162: 1=System Point

    NORTH CLASSROOM - the Adjective/Noun label for this device • Z005 - the first of five possible assigned software zones • 1D001 - 1 = Loop 1, D = Detector, 001 = Address 001 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 163: 2=Zones

    Pre-signal and 99 reserved for future use • Zone Type - the Type assigned to each installed zone (default is Alarm) • Zone Message - the message assigned to each installed zone MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 164 21.25 to 27.50 VDC 24V Nonresettable Normal 21.25 to 27.50 VDC Charger Normal 27.05 to 28.15 VDC Normal -1.3 to -1.6 VDC NACs Open Circuit -2.3 to -2.5 VDC Short Circuit 0 to 1.0 VDC MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 165: 4: Trouble Reminder

    Pressing 2 while viewing Read Status Screen #2 will cause the following Timer screens to be dis- played: TIMERS PAS DELAY PRE SIGNAL WATERFLOW TIMERS AC LOSS DELAY These screens indicate the delay time, in seconds, for each of four possible delay options. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 166: 6: Nac

    Pressing 1 while viewing Read Status Screen #3 will display the following screen: 1=RELAYS 2=PROGRAM CHECK 3=HISTORY RELAYS Read Status Screen #3 1=RELAY 1 2=RELAY 2 3=RELAY 3 The operator can view the programmed option for each relay by pressing the corresponding number key. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 167: 8: Program Check

    Pressing 1 while viewing Read Status Screen #4 will display the following screens: READ STATUS ANNUNCIATORS 1=ANNUNCIATORS TERM ENABLED 2=PHONE LINES 3=CENTRAL STATION 2=ACS OPTIONS 3=ANN-BUS OPTIONS Read Status Screen #4 Annunciator Screen MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 168 Pressing 3 for ANN-S/PG Options while viewing ANN-BUS Screen #1 will display the options selected for the installed serial or parallel printer. Pressing 1 for ANN-80 Options while viewing ANN-BUS Screen #2 will display the options selected for the installed ANN-80 annunciators. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 169: 11: Phone Line

    Screen #2 provides information on the Report Style (Zone or Point) as well as the Primary and Sec- ondary Central Station programming which includes: • Test Time Interval • Account Code • 24 Hour Test Time • Phone Number • Communication Format • Event Codes MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 170: 13: Service Terminal

    4800 and PR indicates that the printer is being supervised. If NS appeared in place of PR, it would indicate that the printer is not supervised. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 171: 15: Print

    If the addressable smoke detector’s Chamber reading is not within the acceptable range, clean the detector and check the Chamber value again. If the reading is still not within the acceptable range, immediately replace the detector. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 172: Drift Compensation

    Dust accumulation above the allowed limit. Table 4.1 Maintenance Alert Levels Figure 4.1 illustrates a graphic representation of the maintenance levels: DIRTY Maintenance Urgent Maintenance Alert Acceptable Range Low Chamber Reading VALUE Figure 4.1 Diagram of Maintenance Levels MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 173: 16: Time-Date

    Pressing 1 while viewing Read Status Screen #6 will display the following READ STATUS screens: 1=TIME-DATE Read Status Screen #6 DAYLIGHT SAVINGS ENABLED START MONTH START WEEK WEEK-2 DAYLIGHT SAVINGS END MONTH END WEEK WEEK-1 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 174: Section 5: Power Supply Calculations

    Calculation Column 3 in Table 5.3 on page 176. When calculating current draw and the battery size, note the following: • ‘Primary’ refers to the main power source for the control panel MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 175: 2: How To Use Table 5.3 On Page 176 To Calculate System Current Draw

    AC power applied. Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm  condition during a loss of AC power. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 176 3 & 4, 5 & 6) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maximum ratings specified. Current limitations of TB3 circuits is 3.0 amps per output 10 Total current draw listed above cannot exceed 7.0 amps in alarm. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 177: Calculating The Battery Size

    The control panel can charge batteries in the 12 AH to 26 AH range. The control panel cabinet is capable of housing batteries up to 18 AH. Batteries larger than 18 AH require the BB-26, BB-55F, or other UL-listed external battery cabinet. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 178: Appendix A: Software Zones

    1 to 99. Newer LiteSpeed devices (modules and detectors) can have unique addresses of 1 to 159 which means each zone can have up to 159 input and output devices assigned to it. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 179 ZONE CMF-300 CP300 SD350 CMF-300 SD350 ZONE SD350 CMF-300 MMF-302 The zone correlations which are shown graphically above are also presented in Table A.1 on page 180 and Table A.2 on page 181. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 180 ADJ/NOUN Address ADJ/NOUN Type Number Type Number SD350 FIRST HALL SD350 ELEV. LOBBY CP350 2ND FLOOR CP350 ROOM 210 SD350 3RD FLOOR SD350 MEZZANINE SD350 MECH. ROOM Table A.1 Detector Programming Sheet Example MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 181 Device Type ADJ/NOUN Address ADJ/NOUN Number Type Number MMF-300 MMF-302 1, 2 MMF-302 1, 2 MMF-302 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 1, 2, 3 CMF-300 CMF-300 CMF-300 CMF-300 Table A.2 Module Programming Sheet Example MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 182 Software Zones Correlations DETECTOR ZONE ASSIGNMENT Device Zone Device Zone Address ADJ/NOUN Address ADJ/NOUN Type Number Type Number Table A.3 Blank Detector Programming Sheet - 1 of 2 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 183 Correlations Software Zones DETECTOR ZONE ASSIGNMENT Device Zone Device Zone Address ADJ/NOUN Address ADJ/NOUN Type Number Type Number Table A.4 Blank Detector Programming Sheet - 2 of 2 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 184 Software Zones Correlations MONITOR/CONTROL MODULE ZONE ASSIGNMENT Device Zone Device Zone Address ADJ/NOUN Address ADJ/NOUN Type Number Type Number Table A.5 Blank Module Programming Sheet - 1 of 2 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 185 Correlations Software Zones MONITOR/CONTROL MODULE ZONE ASSIGNMENT Device Zone Device Zone Address ADJ/NOUN Address ADJ/NOUN Type Number Type Number Table A.6 Blank Module Programming Sheet - 2 of 2 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 186: Appendix B: Default Programming

    ANN-RLY Relay 1 Zone 1 Verification ....through........Ring Count ANN-RLY Relay 10 Zone 10 PAS Timer ANN-LED Point/Zone Zone Presignal Timer ANN-LED Alarms/ATS (Alarm, Trbl, Supv) Waterflow Retard Timer ANN-LED Range 0 - 9 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 187: Appendix C: Nfpa Standard-Specific Requirements

    Transmitter Module,” on page 190. NFPA 72 Proprietary Fire Alarm System FACP Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure C.5, “Proprietary Protective Signaling System,” on page 192, for installation instructions for this unit. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 188 FACP Figure C.1 Central Station Service Using 411UDAC 411UDAC FACP TB2-1 TB1-3 Alarm TB2-2 TB1-1 TB2-3 TB5-3 Trouble TB2-4 TB5-2 TB2-5 TB5-6 Supervisory TB2-8 TB5-4 Table C.1 411UDAC Connections to FACP MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 189 1 2 3 4 5 6 FACP Figure C.2 FACP Connection to 411UD 411UD FACP Alarm TB2-1 TB1-1 TB2-2 TB1-3 Trouble TB2-3 TB5-2 TB2-4 TB5-3 Supervisory TB2-5 TB5-4 TB2-6 TB5-6 Table C.2 411-UD Connections to FACP MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 190 Refer to “4XTMF Transmitter Module Installation” on page 55 for detailed information. FIRE Municipal Box Circuit Gamewell Model M34-56 Local Energy Municipal Box Polarities shown in alarm condition Nonpower-limited 4XTMF Figure C.3 Municipal Box Connected to 4XTMF Transmitter Module MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 191 Cutting TBL Jumper allows the 4XTMF Transmitter Module reverse polarity circuit to open with a system trouble condition if no alarm condition exists. Figure C.4 Remote Station Connection Using 4XTMF Module MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 192 NFPA 72 Proprietary Protective Signaling System. Potter Electric Model EFT-C has not been tested for UL 864 9th Edition and is for use in retrofit applications only. Figure C.5 Proprietary Protective Signaling System MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 193: C.1: Central Station/Remote Station Transmitter: Connection To Facp Dry Contacts

    FACP and no troubles in the panel, the wiring should be connected to the NO and C contacts as indicated in the illustration. FACP Main Circuit Board Figure C.6 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 194: C.2: Mbt-1 Municipal Box Trip - Silenceable

    The CMF-300 must be + on SLC Loop programmed as Silenceable brown wire Braided-shield/Drain Wire and General Alarm. black EOLR-1 Power Alarm polarity shown! Supervision Relay CMF-300 SLC Loop Shield 24 VDC, Nonresettable FACP MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 195: Appendix D: Facp With Keltron

    Fire Alarm Control Panel (terminal blocks are not shown in their actual positions in order to clarify wiring connections) Figure D.1 Wiring to Keltron Printer MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 196: Appendix E: Wire Requirements

    (power-limited) Circuit volt drop allowed at end of by 1.2 volt maximum circuit line drop Table E.1 FACP Wire Specifications When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 197: E.1: Nac Wiring

    1.59 2.25 1.41 1.27 Table E.2 NAC Wiring Requirements for FACP Notes: Calculations are based on Direct-Current Resistance data for uncoated copper wire, per National Electrical Code (2005 Edition) Table 8, Conductor Properties. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 198: Appendix F: Hvac Control

    HVAC SHUTDN control relay module only if there are no alarm conditions. The HVAC SHUTDN control relay module can be deactivated if trouble conditions exist on the FACP. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 199: F.2.2: Hvac Ovrride

    HVAC Shutdown from occurring only if it is initiated prior to an alarm condition. NOTE: Activation of the HVAC OVRRIDE module causes a supervisory event that will be communicated to the Central Station if enabled. MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 200: Appendix G: Canadian Application

    Figure G.1 FACP Minimum Configuration - Single ANN-LED Annunciator metal conduit (max. 20 ft.) ANN-LED annunciators must be in same room as FACP FACP ANN-LED Annunciators Figure G.2 FACP Maximum Configuration - Eight ANN-LED Annunciators MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 201: Index

    AEM-16ATF Annunciator 40 see also battery charger 22 AEM-32AF Annunciator 40 see also remote battery charger 15 Alarm 153 Class A 47 Alarm Silence 18 Class B 47 alarm verification 14 NAC wiring 49 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 202 Erase History 115 Default Programming 186 exiting Delete Detector 68 programming 63 Delete Module 79 Read Status 63 Description Expander Module 57 control module 94 see also SLC-2 21 detector label 77 monitor module 87 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 203 AC Power 150 see also Notification Appliance Circuit 14 Alarm Silenced 151 Battery 151 silence inhibit 112 Disabled 151 silenceable 109 Fire Alarm 150 Style configuration 48 Ground 151 Style Y wiring diagram 49 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 204 Process Monitor 155 supervisory 154 PROCMON AR 113 trouble 152 Program waterflow 156 check 137 Option Modules 21 check correlations 137 annunciators/UDACT 118 clear 136 Printer/PC 134 Program Check Options 13 Maintenance Level 141 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 205 Relay Control Module NC configuration 48 see also ACM-8RF 59 Style Z 47 Relay options 100 NAC configuration 48 Remote Programming 62 wiring 49 Remote Station Service 56 subscreen 63 remote switch functions 14 supervise MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 206 Zones Disabled 97 Zones Enabled 97 Zones Installed 97 UL power-limited wiring requirements zones per device 73 see also power-limited and nonpower-lim- ited 47 Verification detector 72 Verify Loops 114 View Events 115 voltage MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 207 Manufacturer's Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM. Warn-HL-08-2009.fm MS-9600LS Series Manual — P/N 52646:B2 2/12/2010...
  • Page 208 World Headquarters 1 Firelite Place Northford, CT 06472-1653 USA 203-484-7161 fax 203-484-7118 www.firelite.com...

This manual is also suitable for:

Ms-9600udlseMs-9600lscMs-9600lseMs-9600udls

Table of Contents