3.2.4

Set the CAN parameters

Select the communication parameters of the CAN port and check the
"Enable CAN Filter" item to make the CAN filter enable if necessary.
About how to set the CAN Filter, please refer to the section 3.3.
Figure 3-12: The CAN port of I-7530A-MR-FD configuration.
Enable CAN FD: If the CAN FD mode is checked, the transmitted CAN
message packets are in the format of CAN FD. If not checked,
they are in the format of general CAN messages.
Sample point: It is recommended to use the default value. If you need to
modify it, the recommended range is 75~87.5.
Data Sample point : The recommended range is 75~87.5.
Note: The Baud Rate and Sample point of CAN will be set according to
the value input by the user, but some values may not be available
and use the similar value or default value. The actual value will be
displayed at the bottom of the connected window (Need to use
RS232 connection in Normal Mode).
I-7530A-MR-FD Modbus RTU to CAN Converter User's Manual (Version 1.0, 08/2022) ------------- 29