ICP DAS USA I-7530A-MR-FD User Manual page 77

Hide thumbs Also See for I-7530A-MR-FD:
Table of Contents

Advertisement

2. Reset CAN bus
This command is used to reset CAN bus of module. After successfully
setting, the module will response a successful setting message.
Request command:
Field Name
Node ID
Function Code
Start Address
Word Count
Byte Count
Data-1
Data-2
Note1: This value is command field.
Note2: Except 0001
Response command:
Field Name
Node ID
Function Code
Start Address
Word Count
I-7530A-MR-FD Modbus RTU to CAN Converter User's Manual (Version 1.0, 08/2022) ------------- 77
Size
Value Range
Hexadecimal rule
1 byte
0x01~0xF7
1 byte
0x10
2 bytes
0x0100
2 bytes 0x0002
1 byte
0x04
2 bytes 0x0002(Note1)
2 bytes 0x0001(Note2)
, other values are useless
hex
Size
Value Range
Hexadecimal rule
1 byte
0x01~0xF7
1 byte
0x10
2 bytes
0x0100
2 bytes 0x0002
Example
0x01
0x10
0x0100
0x0002
0x04
0x0002
0x0001
Response
Example
0x01
0x10
0x0100
0x0002