2.4 Terminator Resistor Settings

According to the ISO 11898 specifications, the CAN Bus network
must be terminated by two terminal resistors (120
following figure.
Therefore, the I-7530A-MR-FD module supplies a jumper for
activating the terminal resistor. If users want to use this terminal resistor,
please open the I-7530A-MR-FD cover and use the JP3 to activate the
Ω
120
terminal resistor built in the module, as the Figure 2-9. Note that the
default setting is active.
I-7530A-MR-FD Modbus RTU to CAN Converter User's Manual (Version 1.0, 08/2022) ------------- 14
Figure 2-8: Terminal Resistor
Figure 2-9: Terminal Resistor Jumper
Ω
). They are shown as