5.1 Site Selection Requirements

Refer to the GB 51048
NFPA 855
local laws and regulations.
The ESS applies only to outdoor scenarios and can only be deployed outdoors. The
general requirements for site selection are as follows:
Issue 02 (2023-02-28)
NO TICE
Design code for electrochemical energy storage station ,
Standard for the Installation of Stationary Energy Storage Systems , and
The site must not be located in a low-lying land. The horizontal level of the
installation site must be above the highest water level of that area in history.
There must be no vegetation, especially flammable plants within 3 m of the
ESS and the site to protect the ESS from possible fires.
The distance between the top of the ESS and flammable materials must be
greater than or equal to 2 m.
For safety purposes, the distance between the ESS and residential buildings
must be greater than or equal to 12 m, and the distance between the ESS and
densely populated buildings such as schools and hospitals must be greater
than 30.5 m. If the safety distance requirement cannot be met, fire walls must
be installed between the ESS and the buildings.
The safety distances between the ESS and production buildings must comply
with local fire protection regulations or standards.
The ESS located outdoors must be at least 10 ft (3.048 m) away from lot
lines, public ways, buildings, combustible materials, hazardous materials,
high-piled stock, and other exposure hazards not associated with
electrical grid infrastructure.
If either of the following conditions is met, the distance between the ESS
and the production building can be reduced to 3 ft (0.914 m). In addition,
space requirements for equipment transportation, installation, and
maintenance must be considered.