The working mode is set to Maximum self-consumption.
Figure 10-19 Working modes
Parameter
Maximum
grid power
during
battery
discharge
Adjustment
deadband
Automatic
SOC
calibration
–
The working mode is set to TOU.
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 SmartLogger Web-based Deployment
Description
Control the maximum target grid power when the
grid-connection point has zero power.
Allowed fluctuation of the target grid power for the
grid-connection point
▪
Enabled: Automatic SOC calibration is enabled. If
the total charge and discharge energy reaches the
threshold or the calibration function has not been
triggered for 30 days, the SOC automatic calibration
is performed. The SOC automatic calibration is
performed in battery racks. During calibration, the
cut-off SOC settings will be ineffective.
▪
Disabled: Automatic SOC calibration is disabled.