Maintenance Operations; Preparations And Webui Login - Huawei LUNA2000-200KWH-2H1 Smart String ESS User Manual

Hide thumbs Also See for LUNA2000-200KWH-2H1 Smart String ESS:
Table of Contents

Advertisement

LUNA2000-200KWH-2H1 Smart String ESS
User Manual
Main Menu
Second-Level Menu
Device Mgmt.
E.1.2 Maintenance Operations
E.1.2.1 Preparations and WebUI Login
Prerequisites
Procedure
Step 1 Connect the network cable between the network port of the PC and the WAN or
LAN port of the CMU.
Step 2 Set the IP address for the PC on the same network segment as the CMU IP
address.
Issue 02 (2023-02-28)
The operating system of Windows 7 or later is supported.
Browser: Chrome 52, Firefox 58, or Internet Explorer 9, or a later version is
recommended.
When the CMU is connected to the SACU
Connected
Item
Port
LAN port
IP address
Subnet mask
Default gateway
WAN port
IP address
Subnet mask
Default gateway
When the CMU is not connected to the SACU
Copyright © Huawei Digital Power Technologies Co., Ltd.
Third-Level
Function
Menu
Connect
● Adds or removes a device.
Device
● Imports or exports configurations.
SmartModule
● Removes the SmartModule.
● Sets the authentication password.
Clear Alarm
Clears device alarms.
CMU Default
Value
192.168.8.10
255.255.255.0
192.168.8.1
192.168.0.10
255.255.255.0
192.168.0.1
E CMU Commissioning
Example PC
Setting
192.168.8.11
255.255.255.0
192.168.8.1
192.168.0.11
255.255.255.0
192.168.0.1
213