LUNA2000-200KWH-2H1 Smart String ESS
User Manual
Prerequisites
1.
2.
3.
4.
10.1 Preparations and WebUI Login
Prerequisites
●
●
Procedure
Step 1 Connect the network cable between the network port of the PC and the WAN or
LAN port of the SmartLogger.
Step 2 Set the IP address for the PC on the same network segment as the SmartLogger IP
address.
Connected
Port
LAN port
Issue 02 (2023-02-28)
10
All devices onsite have been commissioned.
The system is powered on and alarms are cleared.
The commissioning equipment is available onsite.
Before the deployment, wait until the air conditioner adjusts the temperature
inside the cabinet and the temperature of batteries to the specified
temperature range (5°C to 45°C).
The operating system of Windows 7 or later is supported.
Browser: Chrome 52, Firefox 58, or Internet Explorer 9, or a later version is
recommended.
Item
IP address
Subnet mask
Default gateway
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 SmartLogger Web-based Deployment
SmartLogger Web-based
SmartLogger
Default Value
192.168.8.10
255.255.255.0
192.168.8.1
Deployment
Example PC
Setting
192.168.8.11
255.255.255.0
192.168.8.1
126