Huawei LUNA2000-200KWH-2H1 Smart String ESS User Manual page 214

Hide thumbs Also See for LUNA2000-200KWH-2H1 Smart String ESS:
Table of Contents

Advertisement

LUNA2000-200KWH-2H1 Smart String ESS
User Manual
Fire
● If a fire occurs, power off the system if it is safe to do so.
● Extinguish the fire with carbon dioxide, FM-200 or ABC dry powder fire
● Ask firefighters to avoid contact with high-voltage components during fire
● Overheating may cause batteries to deform, become faulty, and leak corrosive
Fire Alarm Horn/Strobe
When the alarm indicator on the equipment blinks or buzzes:
Gas Exhaust
Extinguishant Release or Fire
Issue 02 (2023-02-28)
D ANGER
extinguishers.
fighting to prevent the risk of electric shock.
electrolyte or toxic gas. Keep away from the batteries to avoid skin irritation
and chemical burns.
Stay away immediately.
Do not approach.
Do not open the door.
Remotely cut off the power supply.
Onsite personal protection: Do not directly face the exhaust vents.
Post-disaster product maintenance: Contact the Company's service engineers
for evaluation.
Suggestions for onsite O&M personnel:
a.
When a fire occurs, evacuate from the building or equipment area, press
the fire alarm bell, and immediately call the fire emergency service.
Notify the professional firefighters and provide them with relevant
product information, including but not limited to battery pack types, ESS
capacity, and battery pack location and distribution.
b.
Do not enter the affected building or equipment area under any
circumstances, and do not open the doors of the ESS. Isolate and monitor
the site. Keep irrelevant personnel away from the site.
c.
After calling the fire emergency service, remotely power off the system
(such as the Smart Transformer Station, Smart PCS, auxiliary power
supply devices, and combiner box power supply) while ensuring your own
safety.
d.
After professional firefighters arrive, provide relevant product
information, including but not limited to battery pack types, ESS capacity,
battery pack location and distribution, and user manuals.
e.
After the fire is extinguished, the site must be handled by professionals in
accordance with local laws and regulations. Do not open the doors of the
ESS without permission.
Copyright © Huawei Digital Power Technologies Co., Ltd.
C Emergency Handling
206