Huawei FusionDC1000A Manual
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

Quick Links

FusionDC1000A Prefabricated All-in-One Data
Center
V100R021C00
Product Description (IT Scenario)
Issue
01
Date
2021-04-20
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei FusionDC1000A

  • Page 1 FusionDC1000A Prefabricated All-in-One Data Center V100R021C00 Product Description (IT Scenario) Issue Date 2021-04-20 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    Indicates a potentially hazardous situation which, if not avoided, could result in equipment damage, data loss, performance deterioration, or unanticipated results. NOTICE is used to address practices not related to personal injury. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 4 Change History Changes between document issues are cumulative. The latest document issue contains all the changes made in earlier issues. Issue 01 (2021-04-20) This issue is the first official release. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    4.1 Overview....................................26 4.2 Integrated UPS..................................30 4.2.1 Product Structure................................30 4.2.2 Technical Specifications..............................32 4.3 rPDU......................................35 4.4 SmartLi..................................... 36 4.4.1 Battery Module...................................38 4.4.2 BCU......................................40 4.4.3 Monitoring Interface Unit...............................41 Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 6 7.3.2 Heptafluoropropane Automatic Fire Extinguisher....................96 7.4 Fire Detection and Extinguishing Equipment for Lithium Battery Modules.............97 8 Surge Protection and Grounding..................100 8.1 Surge Protection................................. 100 8.2 Grounding..................................... 100 9 Integrated Cabling......................102 Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 7 FusionDC1000A Prefabricated All-in-One Data Center Product Description (IT Scenario) Contents A Acronyms and Abbreviations................... 104 Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 8: Overview

    Overview 1.1 Positioning Huawei has developed the FusionDC1000, a green data center solution, based on a thorough study on the reform and impact of the cloud computing to traditional data centers and the practical experience of dozens of global cloud computing centers.
  • Page 9 The pre-fab. module can be easily relocated as it can be transported on level-3 roads and applies to various scenarios such as dynamic data service deployment, military affairs, disaster relief, and field operations. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 10 Provides standard Simple Network Management Protocol (SNMP) ports to communicate with third-party network management systems (NMSs). Intelligent Features ● Local PAD 3D NMS + app view, power supply/cooling 2D link visibility inside the pre-fab module. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 11 FusionDC1000A Prefabricated All-in-One Data Center Product Description (IT Scenario) 1 Overview ● Early warning, rack resource automation, management automation, 3D temperature map, and cooling/power linkage to eliminate hot spots. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 12: Typical Application Scenarios And Typical Configuration

    Distributed and mobile single-module deployment applies to equipment room construction or modernization. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 13 The FusionDC1000 is the first choice when a data center needs to be quickly constructed and deployed due to urgent service requirements. Figure 2-2 Application in an enterprise park Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 14: Typical Configuration

    ● Fire detection and extinguishing system: fire-trace tube, valve, fire cylinder, and pressure gauge Monitori ECC800-Pro, smart ETH gateway, access actuator, AC actuator, water sensor, PAD, camera, card reader, door status sensor, and magnetic system lock Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 15: Key Technical Specifications

    4 PCS: 600 mm x 1200 mm x 2000 1200 mm x 2000 1200 mm x 2000 1200 mm x 2000 System 15 minutes 20 minutes 15 minutes 20 minutes backup time Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 16 A 1200 mm deep cabinet can slide 200 mm in both directions. sliding Power Power 380/400/415 V, 50/60 Hz (three-phase, four-wire, and PE) supply system Input 380/400 V (tolerance: ±15%), 415 V (tolerance: –15% to +10%) distribu voltage tion range system Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 17 Cooling Cooling 25 kW @ 37°C, 20% RH/35°C system capacit Redund 3+1 redundancy configu ration Device 2000 mm x 300 mm x 1100 mm dimensi ons (H x W x Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 18 Customization will change the pre-fab. module and its internal structure. Monito Pre-fab. IC card access control by default, supporting the customization of three-in- ring module one access control system access control Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 19 ● The battery storage temperature must be in the range from 0°C to 40°C. ● Batteries can be stored without power-on for a maximum of 90 days. If the storage period exceeds 90 days, recharge the batteries promptly. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 20: Structural System

    Structural system 3.1 Pre-fab. Module Figure 3-1 Appearance 1 (1) End door (for maintaining outdoor units) (2) Lock rod (3) Ventilation window for the outdoor unit (4) Pre-fab. module feeder windows compartment Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 21: Pre-Fab. Module Thermal Insulation Structure

    The current standard pre-fab. module coating solution passes the 1440-hour salt spray test. According to the ISO12944 standard, the pre-fab. module provides the VH protection level in C3 and C4 environments. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 22: Pre-Fab. Module Doors

    FusionDC1000A Prefabricated All-in-One Data Center Product Description (IT Scenario) 3 Structural system 3.4 Pre-fab. Module Doors Figure 3-3 Fireproof door layout (1) End door (main entrance) (2) Emergency door Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 23 48 hours with a static load of 15 kg at any part. Waterproof structure The fireproof door uses rubber strips with a framework and composite adhesive to ensure the waterproof performance Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 24: Pre-Fab. Module Interior Layout

    (2) IT cabinet (3) Smart cooling product outdoor unit compartment indoor unit (4) Cold aisle (5) Integrated UPS (6) Hot aisle (7) SmartLi (8) Entrance room 3.6 Components Inside the Pre-fab. Module Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 25: Overhead Cable Tray

    Cable trays are secured to the aluminum guide rails using sliding nuts. ● The load-bearing capacity of cable trays is 150 kg/m. Figure 3-7 Overhead cable tray (1) Overhead cable tray Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 26: Suspended Ceiling

    3.6.3 IT Cabinet A cabinet provides stable installation space for servers, thereby ensuring safe operation of servers. The cabinet dimensions are unified, and both front and rear air channels are designed. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 27 ● 2000 mm x 600 mm x 1100 mm Color Black (PANTONE426C/RAL9005) Material High-intensity class A carbon cold rolled steel plate and zinc-coated steel plate Air channel Front and rear air channels Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 28: Raised Floor

    The legs can be adjusted in height, and are galvanized to provide efficient anti-corrosion performance. ● The compression strength of both the raised floor and legs is greater than 1500 kg/m Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 29: Aisle Sliding Door

    The dimensions of a sliding door are 2250.8 mm (H) x 1928 mm (W) and the glass door is 755.0 mm wide. Figure 3-11 Aisle sliding door Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 30: Cabinet Base

    Pipe feature an anti-backflow design, adapting to different configuration demands. Fire extinguishing devices on the pre-fab. module exterior meet sealing conditions. Figure 3-13 External ports Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 31 No. 11 is used for the ECC800-Pro 4G antenna. Figure 3-15 Positions of the reserved ports (1) Port reserved for the humidifier water refill (2) Port reserved for the condensate drainpipe pipe Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 32 The port reserved for the condensate drainpipe is a DN25 PP-R pipe port. ● When the temperature is lower than 0°C, take thermal insulation measures for the water refill port and drain port. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 33: Power Supply And Distribution System

    ECC800-Pro, and other auxiliary devices inside the pre-fab. module. The power supply and distribution system mainly consists of the integrated UPS, power PDB, AC actuator, AC PDB, and rPDU. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 34 FusionDC1000A Prefabricated All-in-One Data Center Product Description (IT Scenario) 4 Power Supply and Distribution System N+X Scenario Figure 4-1 System conceptual diagram (N+X scenario) Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 35 4 Power Supply and Distribution System Figure 4-2 Layout of power supply and distribution devices (N+X scenario) (1) Integrated UPS (2) SmartLi (3) Power PDB (4) AC PDB Figure 4-3 Power density (N+X scenario) Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 36 Figure 4-4 System conceptual diagram (2N scenario) Figure 4-5 Layout of power supply and distribution devices (2N scenario) (1) Integrated UPS (2) SmartLi (3) Power PDB (4) AC PDB (in the pre- fab. module) Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 37: Integrated Ups

    ● The appearance of the UPS5000-E-60K-HASBS (02312TVX) is similar to that of the UPS5000- E-125K-HASBS-01 (02312TWA). Figure 4-7 UPS5000-E-60K-HABBS front view (1) Power input status (2) Input circuit breaker (3) Lighting circuit breaker indicator Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 38 (7) UPS input circuit breaker (8) UPS maintenance bypass (9) Control module circuit breaker (10) Bypass module (11) Power module (12) Monitor display unit (MDU) (13) Power distribution (14) UPS output circuit breaker monitoring board Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 39: Technical Specifications

    IEC 62040-3. The upper limit of the altitude is 4000 m. Table 4-3 Safety and EMC Item Specifications Safety compliance EN 62040-1, 2013 IEC 62040-1, 2013 Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 40 Three-phase four-wire + PE Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage) Input frequency range 50/60 Hz ±6 Hz (adjustable with a tolerance of 0.5–6 Hz, ±2 Hz by default) Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 41 100 ms. Derating coefficient of ● 40 A circuit breaker: 0.75 output circuit breakers ● 63 A circuit breaker: 0.7 Table 4-7 System electrical specifications Item Specifications System efficiency 95% (linear load) Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 42: Rpdu

    ● If the power density of a single IT cabinet is 9 kW, configure the half height rPDU. Figure 4-9 IEC full-height rPDU Figure 4-10 IEC half-height rPDU Figure 4-11 Chinese-standard full-height rPDU Figure 4-12 Chinese-standard half-height rPDU Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 43: Smartli

    PDU2000-32-1PH-9/3-B3 GB 9×10A+3×16A 4.4 SmartLi ● The SmartLi is a battery energy storage system solution developed for Huawei UPSs. ● The product uses lithium cells with superior charge and discharge characteristics and high cycle performance. ● The modular design of key components facilitates replacement and greatly reduces O&M costs.
  • Page 44 < 800 kg Circuit breaker 690 V AC/750 V DC, 500 A, 4-pole Fuse 800 V DC, 250 A (one fuse for each battery string) Operating 0–40°C iron temperature Storage 0–40°C ntal temperature Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 45: Battery Module

    20 connected in series). The electrochemical cells are made of lithium iron phosphate. All external ports of the module are located on its front panel for ease of installation and maintenance. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 46 Dimensions (H x W x D): 157 mm x 200.5 mm x 592 mm ● Weight: ≤ 35 kg ● Rated voltage: 64 V ● Rated capacity: 40 Ah ● Rated discharge current: 240 A Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 47: Bcu

    Description Green The battery cabinet is working properly. Yellow The battery cabinet has generated a minor alarm. The battery cabinet has generated a critical alarm. The battery cabinet is shut down. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 48: Monitoring Interface Unit

    Connects to a third-party network management communicati device over two wires. ons port Northbound Connects to an UPS. communicati ons port DB26 Supports FE, RS485, I2C, CAN, and other signals. DO_1 DO_1 Reserved. DO_2 DO_2 Reserved. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 49 If the normally closed (NC) port is disconnected from the EPO_12V port, EPO is triggered. Figure 4-17 COM pins Table 4-13 COM pin definition Description RS485+ RS485- RS485+ RS485- CANH0 CANL0 Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 50: Mdu

    4 Power Supply and Distribution System Figure 4-18 RS485 pins Table 4-14 RS485 pin definition Description RS485_T+ RS485_T– RS485_R+ RS485_R– 4.4.4 MDU The MDU interworks with the monitoring interface unit to implement SBCU management functions. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 51 The SmartLi is running properly or a warning has been generated. The MDU is powered off. The ports of the MDU are located at the side of the LCD. Figure 4-20 MDU ports Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 52 Specifications Dimensions (H x W x D): 175 mm x 264 mm x 40 mm Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 53: Power Pdb

    Two copper bar inputs Operating temperature –25°C to +45°C Operating humidity 5%–95% RH Installation mode Installed on the wall Cabling mode Routed in from the bottom and out from the rear Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 54: Ac Pdb

    Two 1-pole 16 A MCBs One 1-pole 10 A MCB+YO+AUX+relay Operating temperature –5°C to +40°C Operating humidity 5%–95% RH Installation mode Installed on the wall Cabling mode Routed in and out from the top Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 55: Cooling System

    Fresh air fans are deployed to introduce fresh air from outside of the module to ensure the fresh air ventilation volume required by the personnel inside the module. Figure 5-1 Cooling principle Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 56 Figure 5-2 Cooling system diagram Figure 5-3 Temperature simulation of the cooling system graph Figure 5-4 Layout of cooling components (1) Smart cooling product outdoor unit (2) Smart cooling product indoor unit Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 57 Figure 5-6 Fresh air ventilation diagram (1) Air inlet window (2) Air exhaust window (3) Fans Figure 5-7 High temperature derating curve for IT AIO NO TE The return air temperature is 37.8°C. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 58: Netcol5000-A025 Smart Cooling Product

    Figure 5-8 Indoor unit Dimensions Table 5-1 Dimensions of the NetCol5000-A025 indoor unit Cabinet H (mm) x W (mm) x D (mm) Expansion Method Dimensions Standard 2000 x 300 x 1100 dimensions Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 59 The indoor unit of the 25 kW smart cooling product mainly consists of a compressor, oil separator, fan, heat exchanger, electronic expansion valve, check valve, filter dryer, sight glass, electric heater (optional), wet film humidifier (optional), and water pump (optional). Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 60 The finned-tube evaporator with a high cooling efficiency adopts the synergy field principle and computational fluid dynamics (CFD) to optimize the flow path design, which greatly improves the heat exchange efficiency. ● Electronic expansion valve (EEV) Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 61: Operating Environment Specifications

    ● Work with NetCol500-A040MS1E0: –20°C to +45°C ● Work with NetCol500-A040MS1E0: –20°C to +55°C ● Work with NetCol500-A040MS1E0 (with a low temperature component): –40°C to +45°C Protection level ● Outdoor unit: IPX5 Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 62 ● If the indoor unit is placed higher than the outdoor unit, the vertical distance between them should be less than or equal to 8 Thermal insulation foam ≥ 13 mm thickness Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 63: Technical Specifications

    (RCCB) that is insensitive to single-phase DC pulsation and transient impulse current. Note: If certain conditions are not met, contact Huawei technical support. 5.2.3 Technical Specifications Table 5-5 General specifications Item...
  • Page 64: Outdoor Unit

    Pipe routing Top and bottom pipe routing Condensate pump Water pump lift 5.3 Outdoor Unit Figure 5-11 Composition of the NetCol500 outdoor unit (1) Electric control box (2) Rack (3) Fan Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 65 Certification RoHS, REACH, CE Storage temperature –40°C to +70°C Storage humidity 5%–95% RH (non-condensing) Altitude 0–4000 m, derated at above 1000 m. For details about derating data, contact Huawei technical support. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 66: Fan

    ● Pressure preservation is performed on the condenser before delivery, and the pipe ports are properly sealed to prevent foreign matter from entry. 5.4 Fan Figure 5-13 Fan Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 67: Low Temperature Component

    When detecting that the condensing pressure exceeds the threshold, the pressure stabilizing valve automatically closes the bypass. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 68 944 mm x 632 mm x 507 mm (with packing) 828 mm x 470 mm x 300 mm (without packing) Expansion bolt hole M12x60 Storage temperature –40°C to +70°C Storage humidity 5%–95% RH (non-condensing) Maximum operating pressure 4.35 MPa Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 69: Management System

    (O&M), security management, log management, and system management. ● The NetEco is the centralized O&M part of the Huawei data center infrastructure management solution. The system uses an open architecture and connects to various types of devices using device access packages.
  • Page 70 ● Scenario with an IVS: Connect the signal cables of the indoor and outdoor cameras to the LAN switch. Table 6-1 Management system configurations Function ECC800-Pro NetEco Client 16 PCS One license manages up to 25 smart nodes. authorization Work order management Energy efficiency management Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 71 With the help of energy consumption reports, you can continuously optimize the PUE and improve the unit energy consumption output. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 72: Ecc800-Pro

    (4) Access actuator (5) AC actuator (6) Camera (monitors the entrance room and main entrance) (7) PAD (8) Water sensor NO TE The ECC800-Pro is deployed in the Rack-A1 cabinet. 6.2 ECC800-Pro Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 73: Product Configuration

    Weight 7.5 kg (dual power supplies + main control module) Color Black Installation Can be installed in a 1 U space in a standard 19-inch cabinet Environmental protection RoHS5, REACH, WEEE Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 74: Main Control Module

    48 V GND 6.2.2 Main Control Module Figure 6-5 ECC800-Pro collector main control module (1) USB (2) Status indicator (3) AIDI_1 (4) AIDI_2 (5) COM1/AIDI_4 (6) COM3/12V (7) WAN1 (8) LAN1/POE Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 75 LAN port ● Supports two LAN ports, which can be connected to the LAN. The ports support autonegotiation of 10/100/1000 Mbit/s communication rates. ● Connect shielded network cables to the LAN ports. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 76 (SMS) message sending and 4G communication, is compatible with 3G (WCDMA) communication, and provides a standard SIM card slot. NOTE The prerequisite for using a SIM card is that the site has signal coverage. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 77 Specifications 3G/4G Operation LTE (FDD): BAND1, BAND2, BAND3, BAND4, BAND5, Frequency BAND7, BAND8, BAND20 DC-HSPA+/HSPA+/HSPA/UMTS: 850/900/1900/2100 GSM/GPRS/EDGE: 850/900/1800/1900 MHz 3G/4G EIRP (max.) 23 dBm Communications Port Figure 6-7 RJ45 port pins Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 78 RS485+ Pin5 RS485- Pin6 Pin7 Pin8 Indicator Green Power output indicator indicator ● Steady on: The 12 V DC output is normal. ● Off: No 12 V DC output is provided. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 79 ● Pin 6 and Pin 7 collect sensor data. Pin 7 can detect current type sensors (4–20 mA). Pin 6 and Pin 7 can detect the output status of passive dry contact type sensors. Pin 3 and Pin 7 can detect temperature sensors. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 80 ● Steady on: The 12 V DC output is normal. ● Off: No 12 V DC output is provided. Table 6-14 USB port pin definitions Item Description Pin sequence Pin1 Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 81 1s and then off for 1s). Blinking at A network is set up, and super node access is allowed (the short indicator blinks at 10 Hz, on intervals for 0.05s and then off for 0.05s). Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 82: Power Module

    The converter has no power input or is faulty. Blinking at The converter is being queried long intervals (the indicator blinks at 0.5 Hz, on for 1s and then off for 1s). Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 83 0.5 Hz, on for 1s and then off for 1s). Fault Steady on The converter locks out due to indicator output overvoltage. The converter delivers no output due to internal faults. The converter is working properly. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 84: Uim20A Expansion Module

    (3) COM_IN (reserved) Table 6-18 UIM20A expansion module specifications Item Specifications Width 120 mm Depth 200 mm Height 43 mm Operating –30°C to +65°C temperature Installation Installed in a 19-inch rack requirement Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 85 The following table describes the pin assignment for ports COM1/AIDI_1 to COM8/AIDI_8. Table 6-20 Pin assignment for ports COM1/AIDI_1 to COM8/AIDI_8 Item Description Pin1 RS485+ sequence Pin2 RS485- Pin3 Pin4 RS485+ Pin5 RS485- Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 86 Hz), on for 1s and then off for 1s). Blinking The communication is interrupted or the ECC800-Pro is at short unsuccessfully registered (blinking at 2.5 Hz, on for 0.2s intervals and then off for 0.2s). Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 87: Smart Eth Gateway

    (4) PoE_3–4 ports power port signal port (5) 48V_OUT1 power (6) 48V_OUT2 power (7) FE_2 cascading (8) PWR_OUT output port output port signal port cascading power port (9) BLINK button (10) Status indicator Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 88: Access Actuator

    It has access right management, access event record, and alarm record functions. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 89 IEEE802.15.4, mutual backup with FE communication AI/DI port Two AI/DI ports for connecting to the equipment room fire alarm and exit button DO output One 12 V DC power output for controlling magnetic locks, Phoenix terminal Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 90: Ac Actuator

    The AC actuator is used in a pre-fab. module to receive upstream instructions for controlling lights or fans. The AC actuator can connect to the ECC800-Pro controller by wireless networking (802.15.4). Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 91 Two AC outputs, 90–240 V AC, maximum current 5 A output Wireless One wireless communication port, complying with IEEE802.15.4 communicat RS485 port One route of dual RS485 ports, not isolated (reserved) AI/DI Two AI/DI dry contacts, reserved detection Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 92 Blinking at A network is set up, and no long intervals node access is allowed (the indicator blinks at 0.5 Hz, on for 1s and then off for 1s). Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 93: T/H Sensor

    The appearance of the T/H sensor depends on the onsite delivery. Figure 6-14 Pins of an RJ45 connector Table 6-28 RJ45 port pin definitions Description Pin1 or Pin 4 Pin2 or Pin 5 Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 94: Ip Camera

    Output RS485 6.8 IP Camera Figure 6-15 Camera Table 6-30 Camera technical specifications Item Specifications Image sensor 1/2.7" 2-megapixel progressive scan CMOS Focal length 2.8–12 mm Operating temperature –30°C to +60°C Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 95: Wifi Module

    ● 11b: up to 11 Mbps Frequency band 2.4–2.4835 GHz Wireless 20 dBm (MAX EIRP) transmission power Supported Windows 2000/XP/Vista/Linux/Win 7 operating system Port USB 2.0 Hi-Speed connector Voltage range 5.0 V DC±5% Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 96: Water Sensor

    Insulation resistance > 500 megohms Operating temperature –20°C to +70°C Storage temperature –40°C to +85°C (non-condensing) IP rating IP68 Length of the signal cable Reliability Failure rate: 8000 fits Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 97: Pad

    Figure 6-18 PAD The PAD is a capacitive screen which supports multi-touch. Huawei PAD screen size is 8–12 inches. The PAD uses Android 4.0 or later, and has a memory of 2 GB or more. NO TE If a non-standard PAD is selected, confirm with Huawei engineers.
  • Page 98: Fire Extinguishing System

    At the same time, the extinguishant control panel automatically reports alarms. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 99: Optional) Ce Fire Extinguishing System

    (3) Smoke detector nozzles (4) Indoor horn strobe (5) Alarm bell (6) Emergency light (7) EXIT (8) Outdoor horn strobe (9) Fire control box (10) Fire cylinder 7.2 (Optional) CE Fire Extinguishing System Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 100: Extinguishant Control Panel

    Specifications Input AC input frequency: ≤ 120 W AC input voltage and frequency: 230 V AC (tolerance ±10%), 50 Hz DC backup power voltage: 24 V DC 24 V power output Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 101: Heptafluoropropane Automatic Fire Extinguisher

    (ODP = 0), and short residual time (ATL = 34Y). The design and construction of the Heptafluropropane fire extinguisher comply with BS ISO 14520-2006 and EN 12094-2003. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 102: Optional) Standard Fire Extinguishing System

    Can be connected to an emergency start/abort switch, enabling system operation under control in case of emergency or during onsite equipment maintenance. The controller is restored automatically after a fault is rectified. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 103: Heptafluoropropane Automatic Fire Extinguisher

    Then the fire cylinder valve is opened, and extinguishant is released into the protected zone. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 104: Fire Detection And Extinguishing Equipment For Lithium Battery Modules

    The fire detection and extinguishing equipment consists of a fire cylinder filled with extinguishant, a container valve, and a fire-trace tube that can release extinguishant. It can detect and extinguish fire at the initial stage quickly, accurately, and effectively. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 105 In the FusionDC1000, battery modules are deployed in half of the SmartLi cabinet. The fire- trace tubes are routed in the same way. The following figure uses full-capacity cabinet deployment as an example. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 106 Product Description (IT Scenario) 7 Fire Extinguishing System Figure 7-8 Fire cylinder (1) Fire-trace tube (2) Valve (3) Pressurized container (4) Pressure gauge Specifications Recommended extinguishant: heptafluoropropane Extinguishant amount: 3 kg Operating temperature: 0–50°C Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 107: Surge Protection And Grounding

    The actual cable path varies depending on the site. External Grounding M12 bolt ground points are evenly located on the pre-fab. module exterior. Ensure that the two ground points are connected to the ground grid. There are two Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 108 Product Description (IT Scenario) 8 Surge Protection and Grounding ground points on the pre-fab. module exterior. The ground resistance is within 10 ohms. Figure 8-2 Pre-fab. module ground points (unit: mm) Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 109: Integrated Cabling

    Cable trays on the top of the pre-fab. module are separate from cabinets, and can be moved horizontally along the width direction on the top of the pre-fab. module. Strong- and weak-current cables are routed separately. Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 110 Figure 9-1 Cable routes (1) Signal cable (2) Power cable (3) Cable from the UPS to the battery cabinet (4) Mains inlet port (5) Cables for indoor and outdoor units of smart cooling products Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 111 A Acronyms and Abbreviations Acronyms and Abbreviations application aspirating smoke detector automatic transfer switch Conformite Europende International Organization for Standardization integrated data center International Electrotechnical Commission miniature circuit breaker MCCB molded case circuit breaker Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 112 NetEco Network Ecosystem power usage effectiveness RoHS Restriction of the Use of Certain Hazardous Substances REACH Registration, Evaluation, Authorization and Restriction of Chemicals SNMP Simple Network Management Protocol static transfer switch Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd.

Table of Contents