Alarm
Alarm
ID
Name
3818
Air
Conditio
ner
Ambient
Temper
ature
Sensor
Fault
3819
Air
Conditio
ner
Evapora
tor
Frozen
3820
Frequen
t Air
Conditio
ner
System
High
Pressure
Alarm
Issue 02 (2023-02-28)
Alarm
Possible Cause
Severit
y
Minor
Cause ID = 1–13
1. [HVAC-No] The
cable is not
connected securely
or correctly.
2. The sensor is
damaged, open-
circuited, or short-
circuited.
Minor
Cause ID = 1–13
1. [HVAC-No] The air
intake or exhaust of
the cabinet is
blocked.
2. The indoor fan is
faulty.
3. The cooling system
cannot be shut
down in a timely
manner.
4. The evaporator
temperature sensor
is faulty.
Major
Cause ID = 1–13
1. [HVAC-No] The
condenser is
blocked or has
scale.
2. The condenser fan
is faulty.
3. The external air
flow is short-
circuited or blocked.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Suggestion
1. Shut down the system at a proper
time and take security protection
measures.
2. Check whether any cable is loose.
3. Replace the ambient temperature
sensor.
1. Check whether the air intake or
exhaust vent is blocked. If yes, clean it.
2. If the fault persists, contact your
technical support.
1. Check whether the outdoor heat
exchanger is blocked by dirt. If yes,
clean it using a high-pressure water
gun.
2. Check whether the outdoor fan is
running properly. If not, replace it.
3. Check whether the air intake or
exhaust vent of the outdoor fan is
blocked. If yes, clean the air intake or
exhaust vent.
4. If the fault persists, contact your
technical support.
13 Alarm Reference