Huawei LUNA2000-200KWH-2H1 Smart String ESS User Manual page 178

Hide thumbs Also See for LUNA2000-200KWH-2H1 Smart String ESS:
Table of Contents

Advertisement

LUNA2000-200KWH-2H1 Smart String ESS
User Manual
Alarm
Alarm
ID
Name
3016
Battery
Side
Undervolt
age on
Rack
Controller
Issue 02 (2023-02-28)
Severity
Possible Cause
Major
Cause ID = 1–3
The batteries are
abnormal or not
securely connected.
Copyright © Huawei Digital Power Technologies Co., Ltd.
13 Alarm Reference
Suggestion
1. Determine the positions of the
input and output circuit breakers
associated with [ESC-No] and the
AC input power switch of the
PSU.
2. Issue a hibernation command to
all ESRs.
3. Check whether the switch on the
battery side is turned on. If not,
turn on the switch and issue a
running command.
4. If the switch on the battery side is
ON, turn off the switch, the
switch on the bus side, and the
AC input power switch of the
PSU. Then wait for 5 minutes.
5. Check the cable connections on
the battery side of the power
control module by referring to the
maintenance manual of the
product.
6. After checking that the battery
power cable is correctly
connected, turn on the AC input
power switch of the PSU, the
switch on the battery side, and
the switch on the bus side in
sequence, and issue a running
command.
7. If the alarm persists, contact your
dealer or technical support.
170

Advertisement

Table of Contents
loading

Table of Contents