SECTION 9 - MAINTENANCE
Chilled liquid and suction temperature sensor input voltage
Table 36 - Temperature input voltage sensor (Measured signal to shield at the sensor)
Temperature ºF
Voltage
(°c)
16.1 (-8.8)
16.7 (-8.5)
17.3 (-8.2)
17.9 (-7.8)
18.5 (-7.5)
19.1 (-7.2)
19.7 (-6.8)
20.3 (-6.5)
20.9 (-6.2)
21.5 (-5.8)
22.1 (-5.5)
22.7 (-5.2)
23.3 (-4.8)
23.9 (-4.5)
24.5 (-4.2)
25.0 (-3.9)
25.6 (-3.6)
26.2 (-3.2)
26.8 (-2.9)
27.3 (-2.6)
27.9 (-2.8)
28.5 (-1.9)
29.0 (-1.7)
29.6 (-1.3)
30.2 (-1)
30.8 (-0.7)
31.3 (-0.4)
31.9 (-0.1)
32.5 (0.3)
33.0 (0.6)
33.6 (0.9 )
34.2 (1.2)
34.8 (1.5)
35.3 (1.8)
184
Temperature °F
(°c)
1.52
35.9 (2.2)
1.54
36.5 (2.5)
1.56
37.0 (2.8)
1.58
37.6 (3.1)
1.60
38.2 (3.4)
1.62
38.7 (3.7)
1.64
39.3 (4.1)
1.66
39.9 (4.4)
1.68
40.4 (4.7)
1.70
41.0 (5.0)
1.72
41.6 (5.3)
1.74
42.1 (5.6)
1.76
42.7 (5.9)
1.78
43.3 (6.3)
1.80
43.9 (6.6)
1.82
44.4 (6.9)
1.84
45.0 (7.2)
1.86
45.6 (7.5)
1.88
46.2 (7.9)
1.90
46.7 (8.2)
1.91
47.3 (8.5)
1.93
47.9 (8.8)
1.95
48.5 (9.2)
1.97
49.1 (9.5)
1.99
49.7 (9.8)
2.01
50.3 (10.2)
2.03
50.8 (10.4)
2.05
51.4 (10.8)
2.07
52.0 (11.1)
2.09
52.6 (11.4)
2.11
53.2 (11.8)
2.13
53.8 (12.1)
2.15
54.5 (12.5)
2.17
55.0 (12.8)
Temperature °F
Voltage
(°c)
2.19
55.6 (13.1)
2.21
56.3 (13.5)
2.23
56.9 (13.8)
2.25
57.5 (14.2)
2.27
58.1 (14.5)
2.29
58.7 (14.8)
2.30
59.4 (15.2)
2.32
60.0 (15.6)
2.34
60.6 (15.9)
2.36
61.3 (16.3)
2.38
61.9 (16.6)
2.40
62.5 (16.9)
2.42
63.2 (17.3)
2.44
63.8 (17.7)
2.46
64.5 (18.1)
2.48
65.1 (18.4)
2.50
65.8 (18.8)
2.52
66.5 (19.2)
2.54
67.1 (19.5)
2.56
67.8 (19.9)
2.58
68.5 (20.3)
2.60
69.2 (20.7)
2.62
69.9 (21.1)
2.64
70.6 (21.4)
2.66
71.3 (21.8)
2.68
72.0 (22.2)
2.70
72.7 (22.6)
2.71
73.4 (23)
2.73
74.2 (23.4)
2.75
74.9 (23.8)
2.77
2.79
2.81
2.83
Form 201.47-ICOM1
Issue date: 17/11/2022
Voltage
2.85
2.87
2.89
2.91
2.93
2.95
2.97
2.99
3.01
3.03
3.05
3.07
3.09
3.11
3.13
3.14
3.16
3.18
3.20
3.22
3.24
3.26
3.28
3.30
3.32
3.34
3.36
3.38
3.40
3.42
JOHNSON CONTROLS