Table 38 - Pressure Transducer Output Voltage, Measured Signal To Return At The Transducer - York YVAA Installation Operation & Maintenance

Air-cooled screw liquid chillers, air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

SECTION 9 - MAINTENANCE

Table 38 - Pressure transducer output voltage, measured signal to return at the transducer

Suction pressure transducer
(125 psig)
Pressure
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
186
Condenser liquid, discharge, and economizer pressure
Voltage
0.50
0.66
0.82
0.98
1.14
1.30
1.46
1.62
1.78
1.94
2.10
2.26
2.42
2.58
2.74
2.90
3.06
3.22
3.38
3.54
3.70
3.86
4.02
4.18
4.34
4.50
transducers
Pressure
0
25
50
75
100
125
150
175
200
225
250
275
300
325
350
375
400
Form 201.47-ICOM1
Issue date: 17/11/2022
Voltage
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
2.50
2.75
3.00
3.25
3.50
3.75
4.00
4.25
4.50
JOHNSON CONTROLS