R-513A Conversion Table; Table 34 - R-513A Refrigerant Pressure To Saturated Temperature - York YVAA Installation Operation & Maintenance

Air-cooled screw liquid chillers, air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

SECTION 9 - MAINTENANCE

R-513A conversion table

The following table can be used for conversion of refriger-
ant R-513A from pressure to saturated temperature.

Table 34 - R-513A refrigerant pressure to saturated temperature

Pressure
Temperature
(psig)
average (°F)
0
-20.5
5
-8.4
10
1.4
15
9.8
20
17.2
25
23.8
30
29.8
35
35.3
40
40.4
45
45.1
50
49.5
55
53.7
60
57.7
65
61.5
70
65.1
75
68.5
80
71.9
85
75.0
90
78.1
95
81.0
100
83.9
105
86.6
110
89.3
115
91.9
120
94.4
125
96.9
Notes:
1. Temperature data is mean of vapor temperature and liquid temperature.
2. Source of the tabulated data above: REFPROP 9.1214, R513a.MIX, HMX.BNC from Chemours, saturation table.
Data generated by Justin P. Kauffman on and as of 07/29/2016.
182
Pressure
Temperature
(psig)
average (°F)
130
99.3
135
101.6
140
103.9
145
106.1
150
108.3
155
110.4
160
112.4
165
114.5
170
116.4
175
118.4
180
120.3
185
122.2
190
124.0
195
125.8
200
127.6
205
129.3
210
131.0
215
132.7
220
134.3
225
136.0
230
137.6
235
139.1
240
140.7
245
142.2
250
143.7
255
145.2
Pressure
Temperature
(psig)
average (°F)
260
146.7
265
148.1
270
149.6
275
151.0
280
152.4
285
153.7
290
155.1
295
156.4
300
157.7
305
159.0
310
160.3
315
161.6
320
162.9
325
164.1
330
165.3
335
166.6
340
167.8
345
168.9
350
170.1
355
171.3
360
172.4
365
173.6
370
174.7
375
175.8
380
176.9
385
178.0
Form 201.47-ICOM1
Issue date: 17/11/2022
Pressure
Temperature
(psig)
average (°F)
390
179.1
395
180.2
400
181.2
405
182.3
410
183.3
415
184.3
420
185.4
425
186.4
430
187.4
435
188.4
440
189.4
445
190.3
450
191.3
455
192.2
460
193.2
465
194.1
470
195.1
475
196.0
480
196.9
485
197.8
490
198.7
495
199.6
500
200.4
505
201.3
JOHNSON CONTROLS