York YVAA Installation Operation & Maintenance page 59

Air-cooled screw liquid chillers, air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

Form 201.47-ICOM1
Issue date: 17/11/2022
Table 4 - Electrical lug data (cont'd)
FIELD WIRING LUGS
YVAA-B MODEL
EVAP
YVAA0259/0919
2005
YVAA0266/0936
2205
YVAA0219/0769
2004
YVAA0229/0809
2005
JOHNSON CONTROLS
TERMINAL BLOCK
INPUT
INPUT
WIRES
VOLTS
FREQ
PER
PHASE
SINGLE POINT WIRING
200
60
4
230
60
4
380
60
3
400
50
3
460
60
3
575
60
2
200
60
4
230
60
4
380
60
3
400
50
3
460
60
3
575
60
2
200
60
4
230
60
4
380
60
3
400
50
3
460
60
2
575
60
2
200
60
4
230
60
4
380
60
3
400
50
3
460
60
2
575
60
2
EBM CONDENSER FANS
CIRCUIT BREAKER
LUG
WIRES
LUG
WIRE
PER
WIRE
RANGE
PHASE
RANGE
#1/0 ~
700 kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
2
#1 – 500
kcmil
kcmil
#1/0 ~
700 kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
2
#1 – 500
kcmil
kcmil
#1/0 ~
700 kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
2
#1 ~ 500
kcmil
kcmil
#2 – 600
2
#1 ~ 500
kcmil
kcmil
#1/0 ~
700 kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
2
#1 ~ 500
kcmil
kcmil
#2 – 600
2
#1 ~ 500
kcmil
kcmil
SECTION 4 - INSTALLATION
NON-FUSED DIS-
CONNECT SWITCH
WIRES
LUG
PER
WIRE
PHASE
RANGE
3
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
2
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
2
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
2
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
2
#2 ~ 600
kcmil
59
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents