York YVAA Installation Operation & Maintenance page 145

Air-cooled screw liquid chillers, air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

Form 201.47-ICOM1
Issue date: 17/11/2022
Table 26 - Setup mode programmable values (cont'd)
Unit setup mode
setting
Enhanced Fans Mini-
mum Fan Speed
Extended Leaving
Chilled Liquid Setpoint
****Quarterly Service
Warning
****Yearly Service
Warning
****3 Year Service
Warning
****5 Year Service
Warning
****Replace Oil Filter
Warning
YorkTalk Communica-
tion Protocol Type
Unit Setup Mode Messages
The following messages will be displayed for the Unit
Setup Mode in the order they appear. The first group of
displays relates to setup parameters that relate to unit
configuration and factory set points.
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
SYS 1 NUMBER OF COND FANS = X
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
SYS 2 NUMBER OF COND FANS = X
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
COMP 1 OPERATING HOURS = XXXXX
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
COMP 2 OPERATING HOURS = XXXXX
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
COMP 1 STARTS
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
COMP 2 STARTS
The following setup display is selectable as YES or
NO using the ◄ and ► keys.
SETUP MODE CLEAR HISTORY BUFFERS?
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
The following three setup OPTION displays are select-
able as ENABLED or DISABLED using the ◄ and ►
keys according to the options installed on the chiller:
JOHNSON CONTROLS
Mode to change
Minimum
Any
Any
Free Cooling is
Disabled
Free Cooling is
Disabled
Free Cooling is
Disabled
Free Cooling is
Disabled
Free Cooling is
Disabled
Any
XXXXX
XXXXX
Maximum
0 %
20 %
Disabled / Enabled
Disabled / Enabled
Disabled / Enabled
Disabled / Enabled
Disabled / Enabled
Disabled / Enabled
YORKTALK2 or YORKTALK3
SETUP MODE REMOTE TEMP RESET OPTION
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
SETUP MODE REMOTE CURRENT LIMIT OPTION
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
SETUP MODE
SOUND LIMIT OPTION
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
The following setup option is used for setting a pro-
grammable delay after change of value of a remote in-
put. The remote input is ignored until the service timer
expires.
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
REMOTE INPUTS SERVICE TIME = XXXX SEC
The following setup display is selectable as STAN-
DARD or REMOTE ONLY using the ◄ and ► keys.
SETUP MODE RUN PERMISSIVE CONTROL
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
The following setup OPTION display allows program-
ming of the type of fan control installed. This includes
STD STAGED, OPT STAGED, OPT VSD or OPT EN-
HANCED FANS.
SETUP MODE
CONDENSER FAN CONTROL
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
SECTION 8 - MICROPANEL
Default
10 %
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
YORKTALK 3
145
8