FORM 150.64-EG1 Introduction YORK Air-Cooled Scroll Chillers provide chilled water for all air conditioning applications using central station air handling or terminal units. They are completely self-contained and are designed for outdoor (roof or ground level) installation. Each unit includes hermetic scroll compressors, a liquid cooler, air cooled condenser, and a weather resistant microprocessor control center, all mounted on a pressed steel base.
The fan guards are constructed of heavy- gauge, rust-resistant, PVCcoated steel wire. Motors – The fan motors are Totally Enclosed Air-Over, squirrel-cage type, current protected. They feature ball bearings that are double-sealed and permanently lubricated. YORK INTERNATIONAL...
• Suction pressure cutout setting • Each system suction pressure • Discharge pressure (optional) • Liquid Temperature Reset via a YORK ISN DDC or Building Automation System (by others) via: - a pulse width modulated (PWM) input as stan- dard - a 4-20 milliamp or 0 -10 VDC input, or contact closure with the optional B.A.S.
• Compressor motor starting contactors per l.E.C.** • Control power terminals to accept incoming for 115-1-60 control power • Fan contactors & overload current protection The power wiring is routed through liquid-tight conduit to the compressors and fans. YORK INTERNATIONAL...
(load) limiting depending on model.) (The standard control panel can be directly connected to a YORK Building Automated System via the standard onboard RS485 communication port.) LANGUAGE LCD AND KEYPAD DISPLAY – Spanish, French, and German unit LCD controls and keypad display available.
The DX cooler and outdoor section will have a nitrogen holding charge. Interconnecting rigid piping, wiring and refrigerant are by others. Includes YORK Service startup. See Form 150.62-NM1.1 (200) for other application information. (This option includes the Crankcase Heater option.)(Field-Mounted.)
Page 9
fiber of 5/8” (15mm) thickness; one layer of anti-vibrating heavy material thickness of 1/8” (3mm). Both are closed by two sheets YORK INTERNATIONAL of welded PVC, reinforced for temperature and UV resistance. (Factory-Mounted.) ULTRA QUIET FANS – Lower RPM, 8-pole fan motors are used with steeper-pitch fans.
Page 10
This page intentionally left blank. YORK INTERNATIONAL...
Liquid Chillers, shown on pages 16 through 39 cover the majority of design applications for these units. For unusual applications or uses beyond the scope of this catalog, please consult your nearest YORK Office or representative. SELECTION RULES 1. Ratings – Ratings may be interpolated, but must not be extrapolated.
Page 12
See E.G. correction factors for 30% by weight E.G. READ: 1.258 Pressure Drop factor b. See page 14 at 88.7 GPM for YCAL0045 READ: 6.5_Water H O PD c. Cooler Pressure Drop = 6.5 x 1.258 or 8.17 A YCAL0045 is suitable. YORK INTERNATIONAL...
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK Office for application requirements. 2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK Office for application guidelines. 3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
Water Pressure Drop Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges. See page 13 for minimum and maximum flow points. ENGLISH FLOW, GPM 1000 YORK INTERNATIONAL...
Page 15
1000 Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges. See page 13 for minimum and maximum flow points. YORK INTERNATIONAL FLOW, L/S FORM 150.64-EG1...
Page 17
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with ARI Standard 550/590-98 6. The shaded points are certified in accordance with ARI Standard 550/590-98 YORK INTERNATIONAL AIR TEMPERATURE ON - CONDENSER (°F) 110.0 115.0...
Page 19
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with ARI Standard 550/590-98 6. The shaded points are certified in accordance with ARI Standard 550/590-98 YORK INTERNATIONAL AIR TEMPERATURE ON - CONDENSER (°F) 110.0 115.0...
Page 21
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with ARI Standard 550/590-98 6. The shaded points are certified in accordance with ARI Standard 550/590-98 YORK INTERNATIONAL AIR TEMPERATURE ON - CONDENSER (°C) 35.0 40.0...
Page 23
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with ARI Standard 550/590-98 6. The shaded points are certified in accordance with ARI Standard 550/590-98 YORK INTERNATIONAL AIR TEMPERATURE ON - CONDENSER (°F) 110.0 115.0...
Page 25
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with ARI Standard 550/590-98 6. The shaded points are certified in accordance with ARI Standard 550/590-98 YORK INTERNATIONAL AIR TEMPERATURE ON - CONDENSER (°F) 110.0 115.0...
Page 27
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor 5. Rated in accordance with ARI Standard 550/590-98 6. The shaded points are certified in accordance with ARI Standard 550/590-98 YORK INTERNATIONAL AIR TEMPERATURE ON - CONDENSER (°C) 35.0 40.0...
Coils, lb sor 1 sor 2 sor 3 sor 4 sor 5 10.0 10.0 10.0 10.0 10.8 12.5 12.5 10.8 10.8 12.5 16.7 12.5 12.5 12.5 16.7 16.7 12.5 12.5 YORK INTERNATIONAL Com- pres- sor 6 Com- pres- sor 6...
Page 31
2.0 / 2.0 17.0 2.0 / 2.0 116.0 3.0 / 2.0 17.0 2.0 / 2.0 128.0 3.0 / 3.0 13.0 2.0 / 2.0 YORK INTERNATIONAL 60Hz Condenser Fans, Ultra Quiet Number of Fans Total Total Chiller Fan hp Chiller ckt1/ckt2...
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall –...
END CAP WIDTH 45 5/16" 1 1/16" 9 13/16" 9 13/16" ORIGIN TOP VIEW 21 13/16" 5 5/16" 38" CONTROL PANEL 25 3/8" 13 5/8" TWO LIFTING HOLES BOTH SIDES 13 15/16" 15 1/16" 144 13/16" FRONT VIEW YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall –...
Page 37
END CAP WIDTH 45 5/16" 1 1/16" 9 13/16" 9 13/16" ORIGIN 20 1/16" TOP VIEW 5 5/16" 38" CONTROL PANEL 25 3/8" 13 5/8" TWO LIFTING HOLES BOTH SIDES 13 15/16" 15 1/16" 144 13/16" FRONT VIEW YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall –...
Page 39
END CAP WIDTH 45 5/16" 1 1/16" 9 13/16" 9 13/16" ORIGIN TOP VIEW 20 1/16" 5 5/16" 38" CONTROL PANEL 25 3/8" 13 5/8" TWO LIFTING HOLES BOTH SIDES 13 15/16" 15 1/16" 144 13/16" FRONT VIEW YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall –...
Page 41
90 9/16" END CAP WIDTH 45 5/16" 1 1/16" 9 13/16" 9 13/16" ORIGIN TOP VIEW 18 7/16" 5 3/16" 38" CONTROL PANEL 25 3/8" 28 9/16" TWO LIFTING HOLES BOTH SIDES 14" 15 1/16" 144 13/16" FRONT VIEW YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall –...
Page 43
90 9/16" END CAP WIDTH 43 5/16" 1 1/16" 9 13/16" 9 13/16" ORIGIN TOP VIEW 16 11/16" 5 3/16" 38" CONTROL PANEL 25 3/8" 28 9/16" TWO LIFTING HOLES BOTH SIDES 14" 15 1/16" 144 13/16" FRONT VIEW YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall –...
Page 45
90 9/16" END CAP WIDTH 43 5/16" 1 1/16" ORIGIN 9 13/16" 9 13/16" 16 11/16" TOP VIEW 5 3/16" 38" CONTROL PANEL 25 3/8" 28 9/16" TWO LIFTING HOLES BOTH SIDES 16" 15 1/16" 153 5/8" FRONT VIEW YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;...
Page 47
FORM 150.64-EG1 14 DIA MOUNTING HOLES(typ) COIL COOLER 2301 END CAP WIDTH 1150 ORIGIN TOP VIEW CONTROL PANEL TWO LIFTING HOLES BOTH SIDES 3678 FRONT VIEW YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;...
Page 49
COOLER 2301 END CAP WIDTH 1150 ORIGIN YORK INTERNATIONAL 14 DIA MOUNTING HOLES(typ) TOP VIEW CONTROL PANEL TWO LIFTING HOLES BOTH SIDES 3678 FRONT VIEW FORM 150.64-EG1 COIL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;...
Page 51
COOLER 2301 END CAP WIDTH 1150 ORIGIN YORK INTERNATIONAL 14 DIA MOUNTING HOLES(typ) TOP VIEW CONTROL PANEL TWO LIFTING HOLES BOTH SIDES 3678 FRONT VIEW FORM 150.64-EG1 COIL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;...
Page 53
FORM 150.64-EG1 14 DIA MOUNTING HOLES(typ) COIL COOLER 2301 END CAP WIDTH 1151 ORIGIN TOP VIEW CONTROL PANEL TWO LIFTING HOLES BOTH SIDES 3678 FRONT VIEW YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;...
Page 55
FORM 150.64-EG1 14 DIA MOUNTING HOLES(typ) COIL COOLER 2301 END CAP WIDTH 1100 ORIGIN TOP VIEW CONTROL PANEL TWO LIFTING HOLES BOTH SIDES 3678 FRONT VIEW YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;...
Page 57
COOLER 2301 END CAP WIDTH 1100 ORIGIN YORK INTERNATIONAL 14 DIA MOUNTING HOLES(typ) TOP VIEW CONTROL PANEL TWO LIFTING HOLES BOTH SIDES 3678 FRONT VIEW FORM 150.64-EG1 COIL...
1022 to 1332 kg CIP-C- W SW HCL HCW MBD SBC / 16 / 16 / 16 Color White Blue Gray Black Color Black Yellow Black Yellow w/ Yellow w/ Green Red w/ Red Red w/ Green YORK INTERNATIONAL Free...
Page 59
69.9 ND-E 114.3 120.7 Weight Range (lbs) Up to 751 lbs 751 to 1651 lbs 1651 to 3226 lbs YORK INTERNATIONAL ND-X "CS" Cap Screw ENGLISH 5 1/ 2 1/ 4 2 5/16 6 1/ 4 5/16 7 3/ 8...
933 to 1188 kg SLRS-2-C2- 1188 to 1442 kg SLRS-2-C2- SLRS-2-C2 has 2 springs. MBD -Max Bolt Diameter Adjustment Bolt HCW MBD 5/8" HCW MBD 5/8" Color White Black Blue Green Gray Silver Gray w/ red Silver w/ red YORK INTERNATIONAL...
Page 61
FORM 150.64-EG1 INTENTIONALLY LEFT BLANK YORK INTERNATIONAL...
8. The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100, and is intended for isolating the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device. 9. Field Wiring by others which complies to the National Electrical Code & Local Codes. YORK INTERNATIONAL...
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker VOLTAGE CODE LEGEND ACR-LINE C.B. D.E. DISC SW FACT MOUNT CB MIN NF S.P. WIRE UNIT MTD SERV SW YORK INTERNATIONAL OVER CURRENT PROTECTION, CONTROL POWER NOTE A 115-1-60/50 200-1-60 230-1-60 380-1-60 460-1-60 380/415-1-60...
Control Wiring CTB1 YORK INTERNATIONAL FLOW SW REMOTE START/STOP PWM INPUT LOAD LIMIT INPUT * Factory wired with optional transformer. FORM 150.64-EG1 LD03611...
A flow switch is available as an accessory on all units. The flow switch (or its equivalent) must be installed in the leaving water piping of the cooler and must not be YORK INTERNATIONAL...
Page 73
5. A strainer with a mesh size between .5 and 1.5 mm is recommended upstream of the heat exchanger to prevent clogging. Vibration Eliminators Vent Strainer INLET Isolation Pressure Valves Gauge Flow Switch OUTLET Drain Vibration Eliminators YORK INTERNATIONAL Shut Off Valves FORM 150.64-EG1...
fins with full height collars. Subcooling coil an integral part of condenser. Design working pressure shall be 450 PSIG (31 bar). YORK INTERNATIONAL 2. Low Noise Fans: Shall be dynamically and statically bal anced, direct drive, corrosion re sistant glass fiber reinforced composite blades...
(standard on YCAL0041-0065 models), liquid temperature reset via a YORK ISN DDC or Building Automation System (by others) via PWM input as standard or a 4-20milliamp or 0- 10 VDC input or contact closure with optional...
Page 77
(with the exception of strong alkalis, oxidizers, and wet bromine, chlorine and fluorine in concentrations greater than YORK INTERNATIONAL 100ppm). Protective Chiller Panels (Factory or Field Mounted 1. Louvered Panels (condenser coils only): Painted steel as per remainder of unit cabinet, over external condenser coil faces.
Electrical Con- tractor (Division 16). E. Controls: Coordinate all control requirements and connections with Controls Contractor. F. Finish: Installing Contractor shall paint damaged and abraded factory finish with touch-up paint matching factory finish. YORK INTERNATIONAL...