York YVAA Installation Operation & Maintenance page 51

Air-cooled screw liquid chillers, air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

Form 201.47-ICOM1
Issue date: 17/11/2022
Table 4 - Electrical lug data (cont'd)
FIELD WIRING LUGS
YVAA-B MODEL
EVAP
0294/1034
2205
0331/1161
2205
0306/1076
2205
JOHNSON CONTROLS
STANDARD 2HP (with & Without VSD) CONDENSER FANS
TERMINAL BLOCK
INPUT
INPUT
WIRES
VOLTS
FREQ
PER
PHASE
SINGLE POINT WIRING
200
60
230
60
380
60
3
400
60
3
400
50
3
460
60
3
575
60
3
200
60
230
60
380
60
3
400
60
3
400
50
3
460
60
3
575
60
3
200
60
230
60
380
60
3
400
60
3
400
50
3
460
60
3
575
60
3
CIRCUIT BREAKER
LUG
WIRES
LUG WIRE
WIRE
PER
RANGE
RANGE
PHASE
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
40 ~ 500
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 - 500
kcmil
kcmil
#2 – 600
3
3/0 - 400
kcmil
kcmil
#2 – 600
3
3/0 - 400
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 - 500
kcmil
kcmil
#2 – 600
3
3/0 - 400
kcmil
kcmil
#2 – 600
3
3/0 - 400
kcmil
kcmil
SECTION 4 - INSTALLATION
NON-FUSED DIS-
CONNECT SWITCH
WIRES
LUG
PER
WIRE
PHASE
RANGE
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
51