Figure 26 - Optional Three-Pass Inlet/Outlet Connections; Table 9 - Optional Three-Pass Inlet/Outlet Connections - York YVAA Installation Operation & Maintenance

Air-cooled screw liquid chillers, air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

Form 201.47-ICOM1
Issue date: 17/11/2022

Figure 26 - Optional three-pass inlet/outlet connections

Table 9 - Optional three-pass inlet/outlet connections

YVAA
A
Model
1034.4
0161/0571
345.8 (13.61)
(40.72)
1034.4
0201/0701
345.8 (13.61)
(40.72)
1034.4
0166/0586
(40.72)
1034.4
0211/0741
(40.72)
1034.4
0191/0671
(40.72)
1034.4
0169/0599
(40.72)
(101.57)
1034.4
0214/0754
(40.72)
1034.4
0196/0686
(40.72)
(101.57)
1603.6
0176/0616
915.0 (36.02)
(63.13)
1603.6
0224/0782
915.0 (36.02)
(63.13)
1603.6
0254/0894
915.0 (36.02)
(63.13)
Note: The minimum and maximum flow rates listed here only represent the span of flows for a group of available evaporator options. Actual
chiller flow rates vary based on specific evaporator configurations. The application datasheet or nameplate must be referenced for specific flow
limits for every chiller.
Note: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Contact your Johnson Controls Sales Office for ratings and further information.
JOHNSON CONTROLS
All dimensions - in. (mm)
B
C1
C2
1077.3
1117.6 (44.00)
(42.41)
1077.3
1117.6 (44.00)
(42.41)
1461.8
1077.3
1117.6 (44.00)
(57.55)
(42.41)
1461.8
1077.3
1117.6 (44.00)
(57.55)
(42.41)
1461.8
1077.3
1117.6 (44.00)
(57.55)
(42.41)
2579.8
1077.3
1117.6 (44.00)
(42.41)
2579.8
1077.3
1117.6 (44.00)
101.57)
(42.41)
2579.8
1077.3
1117.6 (44.00)
(42.41)
1073.3
1117.6 (44.00)
(42.26)
1073.3
1117.6 (44.00)
(42.26)
1073.3
1117.6 (44.00)
(42.26)
E-nozzle
D
D2
Figure
size
353.1
678.1 (26.70)
4
(13.90)
353.1
678.1 (26.70)
4
(13.90)
353.1
678.1 (26.70)
4
(13.90)
353.1
678.1 (26.70)
4
(13.90)
353.1
678.1 (26.70)
4
(13.90)
353.1
678.1 (26.70)
4
(13.90)
353.1
678.1 (26.70)
4
(13.90)
353.1
678.1 (26.70)
4
(13.90)
366.7
666.1 (26.22)
5
(14.44)
366.7
666.1 (26.22)
5
(14.44)
366.7
666.1 (26.22)
5
(14.44)
SECTION 5 - TECHNICAL DATA
Minimum
Maximum
Water
chilled water
chilled water
volume gal
flow rate
flow rate
(l)
GPM (l/s)
GPM (l/s)
A
31 (116)
130 (8.2)
580 (37)
A
31 (120)
130 (8.2)
580 (37)
A
31 (120)
130 (8.2)
580 (37)
A
31 (120)
130 (8.2)
580 (37)
A
31 (120)
130 (8.2)
580 (37)
A
31 (120)
130 (8.2)
580 (37)
A
44 (170)
130 (8.2)
580 (37)
A
31 (120)
130 (8.2)
580 (37)
A
44 (170)
130 (8.2)
860 (54)
A
44 (170)
130 (8.2)
860 (54)
A
52 (200)
130 (8.2)
860 (54)
5
75

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents