York YVAA Installation Operation & Maintenance page 62

Air-cooled screw liquid chillers, air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

SECTION 4 - INSTALLATION
Table 4 - Electrical lug data (cont'd)
FIELD WIRING LUGS
YVAA-B MODEL
EVAP
0309/1089
2205
0334/1174
2205
0361/1271
2205/2605
62
TERMINAL BLOCK
INPUT
INPUT
WIRES
VOLTS
FREQ
PER
PHASE
SINGLE POINT WIRING
200
60
230
60
380
60
4
400
60
4
400
50
4
460
60
3
575
60
3
200
60
230
60
380
60
4
400
60
4
400
50
4
460
60
3
575
60
3
200
60
230
60
380
60
4
400
60
4
400
50
4
460
60
4
575
60
3
EBM CONDENSER FANS
CIRCUIT BREAKER
LUG
WIRES
LUG
WIRE
PER
WIRE
RANGE
PHASE
RANGE
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
Form 201.47-ICOM1
Issue date: 17/11/2022
NON-FUSED DIS-
CONNECT SWITCH
WIRES
LUG
PER
WIRE
PHASE
RANGE
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
#2 ~ 600
kcmil
4
4/0 ~ 500
kcmil
4
4/0 ~ 500
kcmil
4
4/0 ~ 500
kcmil
4
4/0 ~ 500
kcmil
2
2/0 ~ 500
kcmil
JOHNSON CONTROLS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents