Air-cooled centrifugal liquid chiller
Hide thumbs Also See for YVAM:

Advertisement

Quick Links

YVAM Air-Cooled Centrifugal Liquid
Chiller
Field Installation Procedure for YVAM Units with R-134a
and R-1234ze, 60 Hz
Installation Guide
Issue Date: 2024-01-29
035-28539-000
Form Number: 160.88-N1 (124)
Supersedes: 160.88-N1 (922)

Advertisement

Table of Contents
loading

Summary of Contents for York YVAM

  • Page 1 YVAM Air-Cooled Centrifugal Liquid Chiller Field Installation Procedure for YVAM Units with R-134a and R-1234ze, 60 Hz 035-28539-000 Installation Guide Form Number: 160.88-N1 (124) Issue Date: 2024-01-29 Supersedes: 160.88-N1 (922)
  • Page 2 YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 3: Table Of Contents

    Isolators..............................29 Make piping connections........................34 Wiring connections..........................38 Apply insulation........................... 39 Verifying OptiView panel condensate hose routing................39 Unit heater operation verification..................... 39 Reassembly..............................41 Refrigerant tubing reassembly......................42 Dimensions, nozzle arrangements, and weights..................46 Unit conversion...............................53 YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 4 YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 5: General Safety Guidelines

    Note: Highlights additional information useful to the technician in completing the work being performed correctly. Note: YORK air-cooled chillers incorporate an earth connection for functional purposes only. YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 6: Wiring Warning

    It is the responsibility of any service technician or operator to adhere to these requirements. See 160.00-AD10 for greater details regarding the application and use of A2L refrigerants. YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 7: Changeability Of This Document

    YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 8: Revision Notes

    Updated nomenclature. 12 and 13 Added YVAM mod level B images. Added data plate image for YVAM1150, YVAM1500, and YVAM1650. 19 to 21 Added YVAM mod level B dimensions and rigging locations images. 26 and 27 Added Table Table 5, and...
  • Page 9: Nomenclature

    Nomenclature Figure 1: System nomenclature Figure 2: Compressor nomenclature Figure 3: Evaporator vessel nomenclature YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 10 Figure 4: Variable speed drive nomenclature YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 11: Overview

    Overview This manual provides instructions for rigging and installing a Johnson Controls YVAM Liquid Chilling Unit. Chillers are shipped as a single factory-assembled, piped, and wired package. The units require a minimum of field labor to make chilled water connections and electrical power connections.
  • Page 12 Motor cooling filter drier Direct drive motor and MBC Expansion valve Compressor Cooling piping for VSD Figure 7: YVAM0350 (Mod Level A) VSD end view Callout Component Callout Component Single point power panel UPS power panel YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 13 Figure 9: YVAM1150, YVAM1500, and YVAM1650 (Mod Level B) compressor side view Callout Description Callout Description Expansion valve Direct drive motor and MBC Cooling piping for compressor drive Compressor OptiView panel Motor cooling filter drier Transformer Evaporator Battery panel YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 14 Figure 10: YVAM1150, YVAM1500, and YVAM1650 (Mod Level B) VSD end view Callout Description Callout Description HYP model compressor drive Single point combined power panel with UPS OptiView panel YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 15: Receiving The Chiller

    The services of a qualified Johnson Controls service representative are required for the installation and start-up of all YVAM model chillers installed in the continental United States. Do not attempt to install or start the chiller without the presence of this qualified representative.
  • Page 16: Chiller Data Plate

    Additional information is provided on the evaporator, compressor, and motor data plates. This information must be included when contacting the factory on any problem. Figure 11: YVAM0350 (mod level A) chiller data plate Figure 12: YVAM1150, YVAM1500, and YVAM1650 (mod level B) chiller data plate YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 17: Rigging

    It is beyond the scope of this manual to specify rigging and lifting details. Scope This following section covers the rigging, locating, and final assembly of the YVAM units. It is intended for use by the qualified field service teams. WARNING The unit must only be lifted by the base frame at the points provided.
  • Page 18: Lifting Weights

    Figure 14 for lug installation technique and Figure Figure Figure 23, and Figure 27 installation locations. Figure 14: YVAM chiller rigging using accessory lifting lugs Callout Component Callout Component Flange Lifting hole in base frame Locking pin YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 19 Never lift the chiller using a forklift or by a hook connected to the top rails. Use only the lifting holes provided. • Lifting instructions are placed on a label on the chiller and on the shipping bag. YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 20: Chiller Dimensions And Rigging Locations

    YVAM0350 mod level A dimensions and rigging locations Figure 15: Unit rigging locations for YVAM0350 (mod level A), mm (in.) Figure 16: Opposite VSD end view, mm (in.) Figure 17: VSD end view, mm (in.) Figure 18: Auxiliary panel view, mm (in.) YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 21 YVAM1150 mod level B dimensions and rigging locations Figure 19: Unit rigging locations for YVAM1150 (mod level B), mm (in.) Figure 20: VSD end view, mm (in.) Figure 21: Opposite VSD end view, mm (in.) Figure 22: Auxiliary panel view, mm (in.) YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 22 YVAM1500 mod level B dimensions and rigging locations Figure 23: Unit rigging locations for YVAM1500 (mod level B), mm (in.) Figure 24: VSD end view, mm (in.) Figure 25: Opposite VSD end view, mm (in.) Figure 26: Auxiliary panel view, mm (in.) YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 23 YVAM1650 mod level B dimensions and rigging locations Figure 27: Unit rigging locations for YVAM1650 (mod level B), mm (in.) Figure 28: VSD end view, mm (in.) Figure 29: Opposite VSD end view, mm (in.) Figure 30: Auxiliary panel view, mm (in.) YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 24: Installation

    Do not damage the roof during installation. If the roof is of bonded construction, consult a building contractor or architect for special installation requirements. • Use spring isolators to minimize vibration transmission into building structure. YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 25: Clearance Requirements

    When units are installed in an enclosure, the enclosure height must not exceed the height of the unit on more than one side. If the enclosure is of louvered construction, the same requirement of static pressure loss applies as for ducts and attenuators. See Other considerations. YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 26 Figure 31: Unit clearance dimensions, ft (m) • Ensure that no more than one wall around the chiller yard is higher than the chiller. • Avoid locations near windows or structures where normal operating sounds might be objectionable. YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 27: Rig The Unit To The Final Location

    Rigging section. Note: The following dimensions are approximate values and must be verified on receipt of the chiller. Figure 32: Isolator locations for YVAM chillers with up to 20 fans YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 28 Isolator Y dimension Metric, mm 41.3 Locations Description Unit Standard, in. 10.49 79.55 159.96 220.59 300.91 433.19 Isolator X dimension Metric, mm 266.5 2,020.6 4,063.0 5,603.0 7,643.1 11,003.0 Standard, in. 86.375 Isolator Y dimension Metric, mm 2,193.9 YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 29: Isolators

    Isolators Vibration isolation Do not install YVAM chillers without isolation. Vibration isolation is an important option that must be accounted for at chiller installation. If isolators are not ordered, they must be selected based on the loading at the specific chiller locations. Contact a Johnson Controls representative for assistance if isolators are not provided.
  • Page 30 8. To complete the installation, fine adjust the isolators to level the equipment. Figure 34: Spring isolator detail Callout Description Callout Description Equipment base Non-skid elastomeric pad Isolator base Lower housing Base slotted holes Upper housing Spring adjusting bolt Positioning pin YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 31 All dimensions are in in. (mm) in accordance with ANSI Y14. • Standard finish for housing is powder coated, for spring is powder coated, and for hardware is zinc electroplate. For color, see the previous tables. YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 32 6. To complete the installation, reinstall the top bolt and washer and tighten. Figure 36: Elastomeric isolator details Callout Description Callout Description Isolator base Cross section points Base slotted holes Top washer Isolator threaded hole Top bolt Note: Isolators are square or rectangular. YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 33 HF = free height of mount, before loading. The operating height is calculated by the free height less the static deflection under load. All dimensions are for reference only. • Hardware uses zinc electroplate coating. YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 34: Make Piping Connections

    During operation, the glycol freezing point must also be below the lowest expected refrigerant temperature. If the YVAM chiller is exposed to subfreezing ambient temperatures at any time during its life, it is critical to protect against evaporator freeze damage. The YVAM chiller can be equipped with features to prevent freeze damage to the evaporator.
  • Page 35 Table 12: YVAM freeze damage protection requirements Condition Chiller control of chilled fluid...
  • Page 36 ˂ 1 mg/l Within 5 hr Oxygen ˂0.02 mg/l Within 5 hr Hydrogen sulfide (H ˂0.05 mg/l No limit Free carbon dioxide (CO ˂ 5 mg/l No limit Total hardness (odH) 4.0 to 8.5 mg/l No limit YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 37 Stop valves can be provided in the evaporator water piping adjacent to the chiller to facilitate chiller maintenance. Johnson Controls do not provide the stop valves. To monitor chiller operation, install site thermometer wells and pressure taps in the piping as close to the chiller as possible. YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 38: Wiring Connections

    The factory mounted VSD does not require wiring to the compressor motor. The motor power wiring is factory connected to the VSD. Refer to the YVAM Unit Wiring and Field Control Modifications Manual (Form 160.88-PW2). All wiring to the control panel is completed by the factory. A control power transformer is factory furnished with the VSD.
  • Page 39: Apply Insulation

    Figure 38: Condensate hose routing Unit heater operation verification The YVAM chiller uses various heaters to protect all of the devices that are susceptible to low ambient temperature limits. As part of the commissioning process of the chiller, verify the operation of these heaters to ensure reliability of the various components.
  • Page 40 Heat trace for VSD coolant HT1 and HT2 • VGD actuator heater mat • MBC heater mat • VSD internal heater • OptiView Control Panel heater • OptiView Control Panel cooler • UPS panel heating YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 41: Reassembly

    This section provides technical specifics for the chiller, including weights, dimensions, and torque requirements. Note: The YVAM chiller is completely factory assembled and does not require any field assembly. For occasions where field disassembly or reassembly may need to be conducted for any reason, the following sections are intended to provide technical details for a qualified Johnson Controls Service representative to safely complete these tasks.
  • Page 42: Refrigerant Tubing Reassembly

    The straight threads do not offer sealing action, but they provide the resistance, or holding power, for service pressure. Figure 39: Adjustable end fitting Callout Description Locknut Back-up washer O-ring YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 43 To align the tube end of the fitting to accept incoming tube or hose assembly, unscrew by the required amount, but not more than one full turn. More than one turn makes the locknut push the O-ring into the machine threads beyond the fitting land area during Step 8. YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 44 Tighten to give torque for the required size as specified in Table 14 Table 15 Figure 43: SAE or ISO 6149 straight thread O-ring Callout Description Sealed with an O-ring Threaded for holding power YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 45 O-ring. Lubricate the O-ring with a light coat of synthetic POE oil or POE grease. Thread the nut by hand, and tighten the nut to the appropriate torque value shown in Table Table YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 46: Dimensions, Nozzle Arrangements, And Weights

    Dimensions, nozzle arrangements, and weights The following figures show the detail of the evaporator 150 psi compact two-pass waterboxes for YVAM Mod A and Mod B units. Figure 44: YVAM mod A two-pass waterbox detail, mm (in.) YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 47 Figure 45: YVAM mod B two-pass water box details for chillers with 20 fans, mm (in.) YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 48 Figure 46: YVAM mod B two-pass water box details for chillers with 26 fans, mm (in.) YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 49 The following figures show the detail of the evaporator 150 psi compact three-pass waterboxes for YVAM Mod A and Mod B units. Figure 47: YVAM mod A three-pass waterbox details, mm (in.) YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 50 Figure 48: YVAM mod B three-pass water box details for chillers with 20 fans, mm (in.) YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 51 Figure 49: YVAM mod B three-pass water box details for chillers with 26 fans, mm (in.) YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 52 Compact waterbox weights, lb (kg) Code Weight, lb (kg) One-pass Two-pass Three-pass EB2514-C 3,685 (1,671) 269 (122) 264 (120) EB2514-2 2,999 (1,360) 272 (123) EB2914-C 4,966 (2,252) 277 (126) EB2914-D 4,822 (2,187) 277 (126) EB2914-2 4,513 (2,047) YVAM Air-Cooled Centrifugal Liquid Chiller...
  • Page 53: Unit Conversion

    Example: (45.0°F - 32°) x 0.5556 = 7.22°C To convert a temperature range (that is, a range of 10°F) from Fahrenheit to Celsius, multiply by 5/9 or 0.5556. Example: 10.0°F range x 0.5556 = 5.6 °C range YVAM Air-Cooled Centrifugal Liquid Chiller...