CHILLED LIQUID AND SUCTION TEMPERATURE
TABLE 30 - TEMPERATURE INPUT VOLTAGE SENSOR (MEASURED SIGNAL TO SHIELD AT THE SENSOR)
TEMP. (ºF)
VOLTAGE
16.1
16.7
17.3
17.9
18.5
19.1
19.7
20.3
20.9
21.5
22.1
22.7
23.3
23.9
24.5
25.0
25.6
26.2
26.8
27.3
27.9
28.5
29.0
29.6
30.2
30.8
31.3
31.9
32.5
33.0
33.6
34.2
34.8
35.3
336
SENSOR INPUT VOLTAGE
TEMP. (ºF)
1.52
35.9
1.54
36.5
1.56
37.0
1.58
37.6
1.60
38.2
1.62
38.7
1.64
39.3
1.66
39.9
1.68
40.4
1.70
41.0
1.72
41.6
1.74
42.1
1.76
42.7
1.78
43.3
1.80
43.9
1.82
44.4
1.84
45.0
1.86
45.6
1.88
46.2
1.90
46.7
1.91
47.3
1.93
47.9
1.95
48.5
1.97
49.1
1.99
49.7
2.01
50.3
2.03
50.8
2.05
51.4
2.07
52.0
2.09
52.6
2.11
53.2
2.13
53.8
2.15
54.5
2.17
55.0
VOLTAGE
TEMP. (ºF)
2.19
55.6
2.21
56.3
2.23
56.9
2.25
57.5
2.27
58.1
2.29
58.7
2.30
59.4
2.32
60.0
2.34
60.6
2.36
61.3
2.38
61.9
2.40
62.5
2.42
63.2
2.44
63.8
2.46
64.5
2.48
65.1
2.50
65.8
2.52
66.5
2.54
67.1
2.56
67.8
2.58
68.5
2.60
69.2
2.62
69.9
2.64
70.6
2.66
71.3
2.68
72.0
2.70
72.7
2.71
73.4
2.73
74.2
2.75
74.9
2.77
2.79
2.81
2.83
FORM 201.21-NM3 (616)
VOLTAGE
2.85
2.87
2.89
2.91
2.93
2.95
2.97
2.99
3.01
3.03
3.05
3.07
3.09
3.11
3.13
3.14
3.16
3.18
3.20
3.22
3.24
3.26
3.28
3.30
3.32
3.34
3.36
3.38
3.40
3.42
JOHNSON CONTROLS