SECTION 8 - MICROPANEL
Sound limit setpoint
PROGRAM
SOUND LIMIT SETPOINT
This indicates the sound limit setpoint programmed at
the time of the fault, if the sound limit option is activat-
ed at the factory. If the option is not factory activated,
the display will not appear.
Eductor differential temperature
PROGRAM
◄DEF XXXXX LO XXXXX HI XXXXX
EDUCTOR DIFFERENTIAL
This message indicates the programmed eductor dif-
ferential temperature at the time of the fault.
136
= XXX %
= XXX °F
Eductor safety time
PROGRAM
◄DEF XXXXX LO XXXXX HI XXXXX
EDUCTOR SAFETY TIME
This message indicates the eductor safety time pro-
grammed at the time of the fault.
Motor temperature unload
PROGRAM ◄DEF XXXXX LO XXXXX HI XXXXX
MOTOR TEMPERATURE UNLOAD
This message indicates the motor temperature pro-
grammed at the time of the fault.
Form 201.47-ICOM1
Issue date: 17/11/2022
= XXX MIN
= XXX °F