SECTION 9 - SERVICE AND TROUBLESHOOTING
TABLE 31 – ENTERING/LEAVING CHILLED
LIQUID TEMP. SENSOR, COOLER
INLET TEMPERATURE SENSOR,
AND SUCTION TEMPERATURE
SENSOR: TEMPERATURE/VOLTAGE
CORRELATION
VOLTAGE
TEMP°F
(SIGNAL INPUT
TO RETURN)
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
150
TEMP°C
1.33
-12
1.39
-11
1.46
-10
1.51
-9
1.58
-8
1.65
-7
1.71
-6
1.78
-4
1.85
-3
1.91
-2
1.98
-1
2.05
0
2.12
1
2.19
2
2.26
3
2.33
4
2.40
6
2.47
7
2.53
8
2.60
9
2.65
10
2.73
11
2.80
12
2.86
13
2.92
14
2.98
16
3.05
17
3.11
18
3.17
19
3.23
20
3.29
21
3.34
22
3.39
23
3.45
24
3.5
26
3.54
27
Liquid & Refrigerant Sensor Test Points
(Table 31)
Entering Chilled Liquid Sensor
J6-5 = +5 VDC regulated supply to sensor.
J6-8 = VDC input signal to the microboard. See
Table 31 for voltage readings that correspond
to specific liquid temperatures.
J6-2 = drain (shield connection = 0 VDC) Return
Leaving Chilled Liquid Temperature Sensor
J6-4 = +5 VDC regulated supply to sensor.
J6-7 = VDC input signal to the microboard. See
Table 31 for voltage readings that correspond
to specific liquid temperatures.
J6-1 = drain (shield connection = 0 VDC) Return