Figure 25 - Standard Two-Pass Left Side Inlet/Outlet Connections; Table 8 - Standard Two-Pass Left Side Inlet/Outlet Connections - York YVAA Installation Operation & Maintenance

Air-cooled screw liquid chillers, air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

SECTION 5 - TECHNICAL DATA

Figure 25 - Standard two-pass left side inlet/outlet connections

Table 8 - Standard two-pass left side inlet/outlet connections

YVAA
Model
0459/1549
0491/1731
0361/1271
0391/1381
0456/1606
0399/1409
0469/1649
Note: The minimum and maximum flow rates listed here only represent the span of flows for a group of available evaporator options. Actual
chiller flow rates vary based on specific evaporator configurations. The application datasheet or nameplate must be referenced for specific flow
limits for every chiller.
Note: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Contact your Johnson Controls Sales Office for ratings and further information.
74
All dimensions - in. (mm)
A
B
C1
C2
D
164.5
203.1
0.5
15.5
47.5
(4179)
(5160)
(12)
(394)
(1207)
164.5
203.1
0.5
15.5
47.5
(4179)
(5160)
(12)
(394)
(1207)
164.5
203.1
0.5
15.5
47.5
(4179)
(5160)
(12)
(394)
(1207)
164.5
203.1
0.5
15.5
47.5
(4179)
(5160)
(12)
(394)
(1207)
164.5
203.1
0.5
15.5
47.5
(4179)
(5160)
(12)
(394)
(1207)
164.5
203.1
0.5
15.5
47.5
(4179)
(5160)
(12)
(394)
(1207)
164.5
203.1
0.5
15.5
47.5
(4179)
(5160)
(12)
(394)
(1207)
Minimum
Water
E-nozzle
chilled water
volume gal
size
flow rate
(l)
GPM (l/s)
8
59 (220)
360 (23)
8
59 (220)
360 (23)
8
56 (210)
360 (23)
8
56 (210)
360 (23)
8
59 (220)
360 (23)
8
56 (210)
360 (23)
8
59 (220)
360 (23)
Form 201.47-ICOM1
Issue date: 17/11/2022
Maximum
chilled water
flow rate
GPM (l/s)
1870 (118)
1870 (118)
1570 (99)
1570 (99)
1870 (118)
1570 (99)
1870 (118)
JOHNSON CONTROLS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents