Installation; Installation Steps - Teletek electronics iRIS4 Installation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

2. INSTALLATION

The panel must be installed in a clean dry place and must not be subjected to impacts or vibrations (Figure 2). It must
be situated far from heating appliances. The temperature must be within -5ºС and + 40ºC. The fire panel is not water-
proof!
Attention: The front cover of iRIS4 panel is mounted to the box bottom with hinges fixed with dismountable
rivets. The angle of opening of the front cover must not be greater than 110° - see Figure 3!

2.1. Installation Steps

Remove the packing and observe the panel for any damages during the transpiration. If there are visible
defects, contact your local distributer immediately and cancel the installation.
Perform wall mounting (see item 2.2), built-in mounting (see item 2.3) or wall mounting in modular structure
(see item 2.4) according the type of installation.
Choose inlets for the cables of the main power supply, loops, sounders, control devices, etc. Remove the metal
cap element just from those holes for cable running (Figure 5).
Route the external cables onto the metal bottom, BUT DO NOT make any connections at this stage. ENTER
THE MAINS CABLE THROUGH ITS OWN CABLE ENTRY POINT AND KEEP MAINS WIRING AWAY FROM
SYSTEM AND OTHER LOW VOLTAGE WIRING.
Connect the mains supply and earth wire to the power supply terminal and make sure that the connections are
tight and stable (see item 4.1) BUT DO NOT apply the main electrical supply at this stage.
Position the accumulator battery/batteries in an upright position and fix the metal clamp - Figure 14, position 5.
When you finish with power up and testing steps, and the panel is in normal operation mode, close and lock the
front cover with the securing key/keys.
Keep the keys in a safe place for authorised access of technical personnel only.
Attention: The drawings further in this installation manual are illustrative and simplified for better presentation.
The front door of the panel cannot be dismounted or removed during the installation process. Take care about
all factory mounted components like PCBs, power supply unit, power terminals, grounding points, etc, to not
be harmed during the installation!
Figure 2
iRIS4 - Addressable Fire Alarm Panel – Installation Manual
Figure 3
9

Advertisement

Table of Contents
loading

Table of Contents