9 Fault Diagnosis and Possible Solutions
LED Operator Display
Cause
CANopen Option hardware fault.
LED Operator Display
to
oFA30 to oFA43
Cause
CANopen Option hardware fault
LED Operator Display
Cause
The object dictionary settings were
different from the settings stored in the
EEPROM of the CANopen Option,
and Node Reset (NMT 81h xxh) was
performed while the drive was running
36
CANopen Option Fault
oFA04
CANopen Option Flash write mode
⇒ Replace the CANopen Option. Contact Yaskawa for assistance.
CANopen Option Fault (port A)
Communication ID error
⇒ Replace the CANopen Option. Contact Yaskawa for assistance.
Programming Error 1
PE1
Object content mapping was changed from the default, and Node Reset was
sent while the drive was running.
⇒ Stop the drive before performing Node Reset
⇒ Save the object dictionary settings using Store Parameters (object 1010
(hex)) before performing Node Reset.
YASKAWA ELECTRIC TOBP C730600 24D 1000-Series Option SI-S3/V, SI-S3/T Installation Manual
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution