YASKAWA ELECTRIC TOBP C730600 24D 1000-Series Option SI-S3/V, SI-S3/T Installation Manual
9 Fault Diagnosis and Possible Solutions
External Fault Input from CANopen Option
EF0
The alarm function for an external device has been triggered.
⇒ Remove the cause of the external fault.
⇒ Reset the external fault input from the upper controller (PLC) device.
⇒ Check the program used by the upper controller (PLC) and make the
appropriate corrections.
CANopen Option Fault
oFA00
CANopen Option is not properly connected.
⇒ Connect an option that is compatible with the drive.
CANopen Option Fault
oFA01
CANopen Option is not properly connected.
⇒ Turn the power off and check the connectors between the drive and
CANopen Option.
CANopen Option Fault
oFA03
CANopen Option self-diagnostics error.
⇒ Replace the CANopen Option. Contact Yaskawa for assistance.
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution