Pylontech Pelio-L-5.12 Operation Manual page 42

Lithium-ion phosphate battery
Hide thumbs Also See for Pelio-L-5.12:
Table of Contents

Advertisement

50℃.
-
Ensure the operation current is no more than 90Amps for long time, and the
battery enclosure shall avoid direct sunlight.
If problem remains after above troubleshooting steps, please extract the logs from
the battery using the USB, switch off the module and send the logs to your local
distributor for help.
2) Voltage, SOC
a) Low Voltage: When the battery discharges to 45V or less, battery protection will
turn on.
Solution: Charge the battery till the red light turns off.
b) Cell voltage high. The module voltage is lower than 56V, SOC LED does not all on.
The module protection disappears when discharge.
Solution: keep charge the module by 55-56V or keep the system cycle. The BMS
can balance the cell during cycling.
c)
High Voltage: If charging voltage above 57V, battery protection will turn on.
Solution: Check whether voltage is too high or not, if it is, to change the settings
on power supply side. And discharge the module.
If problem remains after above troubleshooting steps, please extract the logs from
the battery using the USB, switch off the module and send the logs to your local
distributor for help.
3) Current
a)
If current exceeds 90A for long time, battery protection will turn on.
Solution: Check whether current is too large or not, if it is, change the settings on
inverter side.
If problem remains after above troubleshooting steps, please extract the logs
from the battery using the USB, switch off the module and send the logs to your
local distributor for help.
4) HV lock
a)
Cell voltage higher than 4V or module voltage higher than 59.2V.
Solution: Battery system requires properly established communication with

Advertisement

Table of Contents
loading