1)
The cable,
2) The maximum power of inverter or DC loads.
3) The parameter of breaker. The maximum short circuit current for calculation of
each module is 2000A.
4) The connection diagram of each stack and how much power supported
Battery
KIT W
√
1
Max power
√
2
Max power
1 sets of power cable hold maximum 100A
1~4 modules
5~8 modules
KIT G
1 set of cable
√
80A/4kW
√
100A/5kW
Icu of breaker
>=10kA
>=20kA
2 sets of cable
3 sets of cable
160A/8kW
current.
4 sets of cable